Free Engineering Tool · Hydraulic egress model
Egress Time Calculator
Estimate how long a group of occupants takes to leave a floor through a corridor, a stair door, a stair and an exit door. The calculator uses the hydraulic model of crowd movement to find speeds and flows, the component that controls the flow, the queue it creates and the time for the last person to get out.
- Based on Hydraulic egress model
- Free, runs in your browser; your inputs stay on your device
- Screening tool, not reviewed or sealed by a licensed engineer
- Last updated October 2026
Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.
Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.
Occupants and Route
The delay covers detection, alarm and pre-movement time; leave it at 0 for movement time only. A starting density of 0.175 persons/ft² (1.9 persons/m²) gives the largest flow; crowds denser than that move more slowly.
Floor and Doors
Stair
Handrail offset is from the wall to the handrail centerline (0 if none). The effective width is the smaller of the clear width less 6 in. (152 mm) per side and the width between handrail centerlines less 3.5 in. (89 mm) per side.
Result
| Component | Speed | Flow | Travel |
|---|
Evacuation Timeline
About This Tool
The hydraulic model treats a moving crowd like a fluid. Walking speed falls in a straight line as the crowd gets denser: S = k (1 − a D), with D the density in persons per unit area, a = 2.86 ft² (0.266 m²) per person, and k = 275 ft/min (1.40 m/s) for corridors, aisles, ramps and doorways. For stairs k depends on the steps: 196, 212, 229 and 242 ft/min for 7.5/10, 7/11, 6.5/12 and 6.5/13 in. riser and tread, with speed measured along the slope. Below 0.05 persons/ft² people walk at their own pace, and at about 0.35 persons/ft² movement stops.
The specific flow, persons per minute per foot of effective width, is speed times density, Fs = S D. It peaks at 0.175 persons/ft² at k / (4a): about 24 persons/min/ft for corridors and doors and 18.5 for a 7/11 stair. The effective width is the clear width less a boundary layer people keep from each edge: 6 in. at stair walls and door jambs, 8 in. at corridor walls, and 3.5 in. beyond a handrail centerline where that is narrower. The flow is Fc = Fs We. Where the route narrows, the flow arriving is divided by the next effective width; if that exceeds the maximum, a queue forms and the flow is capped. A door that closes behind each user is limited to about 50 persons/min per leaf.
The time for everyone to leave is the travel time of the first person along the route plus the population divided by the flow through the controlling component, the narrowest point in terms of capacity. NFPA 130 uses the same structure for rail stations, walking time plus waiting time at the controlling element, with its own capacities. Stair travel per story is the floor-to-floor height times the slope length per unit rise, √(R² + T²) / R, plus the travel across the landings.
Worked example
Of a floor’s occupants, 150 use one stair. They start at 0.10 persons/ft² in a 72 in. corridor (56 in. effective), walk 196 ft/min and arrive at 92 persons/min. The 36 in. stair door is 24 in. effective and passes 24.04 × 2.0 = 48.1 persons/min, so a queue of up to 71 people builds in the corridor. The 48 in. stair with handrails 3 in. from the walls is 35 in. effective and carries the 48 persons/min at 141 ft/min. Four stories at 12 ft with 16 ft of landings per story is 153 ft of stair travel. The first person is out after 37 + 65 = 102 s; the stair door controls, so the last person is out after 102 + 150 / 48.1 × 60 = 289 s, about 4.8 minutes.
Assumptions and limits
Everyone starts moving together and moves without stopping, with no counterflow, no people with mobility impairments and no merging flows from other floors. The speed and flow data come from drills and normal pedestrian movement and may not reflect a real emergency or today’s population, so add a margin or test a range of inputs. For a whole building, merging at each floor and the order in which floors enter the stair change the result; that needs a second-order calculation or an evacuation model.
When to bring in an engineer
A movement time is only half of a performance-based egress design; it is compared with the time before conditions become untenable. DGA prepares egress analyses and life safety plans and fire and evacuation modeling for timed egress and equivalency submittals.
References
- Fruin, J.J., Pedestrian Planning and Design, Metropolitan Association of Urban Designers and Environmental Planners, New York, 1971: walking speed, density and flow on level routes and stairs.
- Pauls, J.L., “Calculating Evacuation Times for Tall Buildings,” Fire Safety Journal, Vol. 12, No. 3, 1987, pp. 213 to 236: stair flows and the effective width concept.
- Predtechenskii, V.M. and Milinskii, A.I., Planning for Foot Traffic Flow in Buildings, Amerind Publishing, New Delhi, 1978 (translated from the 1969 Russian edition for the National Bureau of Standards): density, speed and flow relationships and stair travel distances.
- NFPA 130, Standard for Fixed Guideway Transit and Passenger Rail Systems, National Fire Protection Association, 2026 edition: station egress calculations with walking time and waiting time at the controlling element.
- Kuligowski, E.D., Peacock, R.D. and Hoskins, B.L., A Review of Building Evacuation Models, 2nd Edition, NIST Technical Note 1680, National Institute of Standards and Technology, Gaithersburg, MD, 2010.
Frequently Asked Questions
How is evacuation time calculated with the hydraulic model?
Find the speed and flow in each part of the route from the crowd density, find the component with the lowest flow capacity, and add the travel time of the first person to the population divided by that controlling flow. Add detection, alarm and pre-movement time to get the full required safe egress time.
How many people per minute can go through a door?
About 24 persons per minute per foot of effective width, where the effective width is the clear width less 6 inches at each jamb. A 36 inch door is 24 inches effective, so about 48 persons per minute. A door that closes behind each user is limited to about 50 persons per minute per leaf whatever its width.
How fast do people walk down stairs in an evacuation?
At low density people descend a 7 inch riser, 11 inch tread stair at about 180 feet per minute along the slope. At the density that gives the largest flow, about 0.175 persons per square foot, the speed drops to about 106 feet per minute.
What is RSET?
Required safe egress time is the time from ignition until occupants reach a place of safety: detection, notification, pre-movement and movement time. A performance-based design shows it is shorter, with a margin, than the available safe egress time before conditions become untenable.
Related Tools and Services
More egress and occupant load calculators →
Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.
Related Reading
Articles from DGA Insights on the code and the method behind this calculator.