Free Engineering Tool · NFPA 30
Flammable Liquid Classification Calculator
Classify a liquid from its closed-cup flash point and boiling point: the NFPA 30 class, from IA to IIIB, and the GHS and OSHA flammable liquid category, on one temperature scale. A second mode estimates the flash point and boiling point of a hydrocarbon blend from its composition for screening.
- Based on NFPA 30
- Free, runs in your browser; your inputs stay on your device
- Screening tool, not reviewed or sealed by a licensed engineer
- Last updated October 2026
Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.
Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.
Liquid
For a mixture without a constant boiling point, NFPA 30 uses the 20 percent evaporated point of an ASTM D86 distillation, while GHS uses the initial boiling point. The boiling point only matters below a flash point of about 73 °F (23 °C).
| Component | Percent |
|---|
Screening estimate for blends of the listed hydrocarbons, which mix nearly ideally. Alcohols, ketones, water and other polar liquids do not, and need a measured flash point.
Classification
Where the Liquid Falls
About This Tool
NFPA 30 sorts liquids by closed-cup flash point. Below 100 °F (37.8 °C) a liquid is flammable, Class I: Class IA and IB have flash points below 73 °F (22.8 °C) and are split by boiling point at 100 °F, and Class IC runs from 73 to 100 °F. At or above 100 °F a liquid is combustible: Class II up to 140 °F (60 °C), Class IIIA up to 200 °F (93 °C) and Class IIIB above that. For a mixture without a single boiling point, NFPA 30 takes the 20 percent evaporated point of an ASTM D86 distillation.
The GHS, which OSHA adopted for flammable liquids in 29 CFR 1910.106, uses four categories with nearly the same breaks in Celsius: Category 1 and 2 below 23 °C (73.4 °F), split by an initial boiling point of 35 °C (95 °F); Category 3 from 23 to 60 °C; and Category 4 above 60 up to 93 °C (199.4 °F). Because the two systems round differently, a liquid at 73 °F is NFPA 30 Class IC but still GHS Category 2, and one at 200 °F is Class IIIB and outside the GHS flammable liquid class. OSHA also moves a liquid heated for use to within 30 °F (16.7 °C) of its flash point into a more hazardous group; enter a handling temperature to see it.
The estimate mode uses the principle behind the closed-cup test: a liquid flashes when the vapor over it reaches the lower flammable limit. For a blend of similar hydrocarbons, each component’s partial pressure is its mole fraction times its vapor pressure (Raoult’s law), and the flash point is the temperature at which Σ xi pi / (P · LFLi) = 1 (Le Chatelier’s rule). The bubble point, where the partial pressures add to one atmosphere, stands in for the boiling point. Vapor pressures come from NIST Antoine fits and the limits from US Bureau of Mines data; for the preset liquids the estimates fall within about 5 °C (9 °F) of published closed-cup values, usually on the low side.
Worked example
A parts-washer solvent with a closed-cup flash point of 105 °F and a boiling point of 310 °F is NFPA 30 Class II, 5 °F above the Class IC line, and GHS Category 3. Warmed to 85 °F in use, it is within 30 °F of its flash point, so OSHA treats it like a Category 3 liquid with a flash point below 100 °F. A blend of 60 percent n-heptane and 40 percent toluene by mass is estimated to flash at about 28 °F (−2 °C) and to start boiling at 217 °F (103 °C): Class IB and Category 2. At an atmospheric pressure of 12.1 psia, typical of a high-altitude site, the same blend would flash at about 23 °F.
Assumptions and limits
The class of a liquid must rest on a closed-cup flash point measured by a standard method, such as ASTM D56 or D93, and corrected to standard pressure. The estimate mode is limited to the listed hydrocarbons, which mix nearly ideally; alcohols, ketones, esters, water and other polar liquids do not follow Raoult’s law and need test data. The tool does not cover gases, liquids with a vapor pressure above 40 psia at 100 °F, unstable liquids or other hazard classes. Results close to a class boundary should be confirmed by testing.
When to bring in an engineer
The class sets allowable quantities, container and cabinet limits, electrical classification and the storage protection scheme. DGA provides code consulting on NFPA 30 and the fire code, and designs fire protection for flammable liquid storage rooms and warehouses.
References
- NFPA 30, Flammable and Combustible Liquids Code, National Fire Protection Association, 2024 edition: definitions of flash point and boiling point and the classification of flammable and combustible liquids.
- US Occupational Safety and Health Administration, 29 CFR 1910.106, Flammable Liquids: paragraphs (a)(5) boiling point, (a)(14) flashpoint and (a)(19) flammable liquid categories, including liquids heated for use.
- United Nations, Globally Harmonized System of Classification and Labelling of Chemicals (GHS), current revision, Chapter 2.6: Flammable Liquids.
- W.A. Affens and G.W. McLaren, “Flammability Properties of Hydrocarbon Solutions in Air,” Journal of Chemical and Engineering Data, Vol. 17, No. 4, pp. 482 to 488, 1972.
- National Institute of Standards and Technology, NIST Chemistry WebBook, SRD 69: Antoine vapor pressure parameters, molecular weights and normal boiling points.
- M.G. Zabetakis, Flammability Characteristics of Combustible Gases and Vapors, Bulletin 627, US Bureau of Mines, 1965: lower flammable limits.
- National Institute for Occupational Safety and Health, NIOSH Pocket Guide to Chemical Hazards: published closed-cup flash points used to check the estimates.
Frequently Asked Questions
What is the difference between Class IB and Class IC?
Both are flammable liquids under NFPA 30. Class IB has a closed-cup flash point below 73 F (22.8 C) and a boiling point at or above 100 F (37.8 C). Class IC has a flash point from 73 F up to 100 F, regardless of boiling point.
Is a Class II liquid flammable or combustible?
Combustible. NFPA 30 calls liquids with a flash point at or above 100 F combustible: Class II from 100 to 140 F, Class IIIA from 140 to 200 F and Class IIIB at 200 F and above. Under GHS and OSHA, a Class II liquid is a Category 3 flammable liquid.
How do NFPA 30 classes compare with GHS categories?
Roughly, Class IA and IB match Categories 1 and 2, Class IC and II fall in Category 3, and most Class IIIA liquids are Category 4. The breakpoints differ slightly (73 F against 73.4 F, 200 F against 199.4 F, and different boiling point rules), so liquids near a boundary can land differently in the two systems.
Can the flash point of a mixture be calculated?
For blends of similar hydrocarbons, yes, as an estimate: the flash point is where the vapor over the liquid reaches the mixture’s lower flammable limit, found from Raoult’s law and Le Chatelier’s rule. The more volatile component dominates, so a small amount of a light solvent can lower the flash point a lot. The result is a screening value; classification needs a measured closed-cup flash point.
Related Tools and Services
More flammable liquids, gases and radiation calculators →
Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.
Related Reading
Articles from DGA Insights on the code and the method behind this calculator.