Compartment Fire Temperature Calculator

Estimate the average temperature of the hot gas layer in a room before flashover. Pick an open door or window, forced ventilation or a closed room, enter the fire size, the room and its linings, and the calculator plots the upper layer temperature against time using the hand methods described in NFPA 555.

  • Based on NFPA 555
  • Free, runs in your browser; your inputs stay on your device
  • Screening tool, not reviewed or sealed by a licensed engineer
  • Last updated October 2026

Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.

Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.

Method and Fire

Room and Openings

Closed room: leakage keeps the pressure down, but no air flows in or out.

Walls and Ceiling

Result

Upper layer temperature
0
Wall heat transfer coefficient
0
Thermal penetration time
0
Ventilation limit
0

Upper Layer Temperature Over Time

Time (min)Upper layer Rise Wall hk
Keep these results

About This Tool

A fire in a room heats a layer of hot gas under the ceiling. Its temperature depends on how fast the fire releases heat, how much of that heat leaves with the gases flowing out, and how much soaks into the walls and ceiling. Three correlations cover the common cases. With a door or window open, the method of McCaffrey, Quintiere and Harkleroad (MQH) gives the temperature rise as ΔTg = 480 (Q / (√g cp ρ∞ T∞ Ao√Ho))2/3 × (hkAT / (√g cp ρ∞ Ao√Ho))−1/3, which with standard air at 295 K becomes the familiar ΔTg = 6.85 (Q2 / (Ao√Ho hkAT))1/3. Ao√Ho is the ventilation factor of the opening and AT is the area of the walls, floor and ceiling less the opening.

The wall heat transfer coefficient hk changes with time. Until the lining heats through, at the thermal penetration time tp = (ρc/k)(δ/2)2, it is √(kρc/t); after that it is k/δ. Lining properties come from a list of common materials published with the NUREG-1805 Fire Dynamics Tools, or can be entered directly. With forced ventilation the method of Foote, Pagni and Alvares uses the supply mass flow instead of the opening: ΔTg/T∞ = 0.63 (Q/(ṁcpT∞))0.72 (hkAT/(ṁcp))−0.36, and the energy balance of Deal and Beyler, Q/(ṁcp + hkAT) with hk = 0.4 max(√(kρc/t), k/δ), is shown as a check. For a closed room, Beyler’s solution of the transient energy balance gives ΔTg = (2K2/K12)(K1√t − 1 + e−K1√t), where K1 holds the wall losses and K2 the fire, both divided by the heat capacity of the room air.

Worked example

A 500 kW fire burns in a 14 by 12 ft room, 8 ft high, lined with 5/8 in. gypsum board, with one 3 by 7 ft door open and 70 °F ambient air. The lining area is 731 ft2 and the ventilation factor is 55.6 ft5/2 (2.85 m5/2), so the door can feed about 4,300 kW of burning, well above the fire. The board heats through after about 6.5 minutes. At 5 minutes hk is 4.3 Btu/h·ft2·°F and the upper layer is about 534 °F; at 10 minutes hk has dropped to k/δ, 1.9 Btu/h·ft2·°F, and the layer is about 681 °F (360 °C), a rise of 611 °F that is still below the usual flashover criterion of a 500 °C rise.

Assumptions and limits

All three methods give a single average temperature for the upper layer. They do not predict local temperatures near the flames or the plume, so they are not suited to sprinkler or detector response or to flame impingement on a target. The fire size is an input and is held steady. The MQH correlation was fit to tests in rooms up to 2.7 m high with upper layer temperatures up to about 600 °C; the forced-ventilation data covered roughly 100 to 300 °C; the closed-room solution was checked against rises up to about 150 °C. The temperature steps up by about a quarter at tp because the two forms of hk do not meet there; that is a feature of the published method. Linings are treated as one material, with combustible linings and multiple layers outside the method.

When to bring in an engineer

Hand methods are a quick screen. When the answer feeds a performance-based design, a tenability analysis or an equivalency, a zone or CFD model with a defined design fire is usually expected. DGA provides fire and smoke modeling and prepares equivalency reports that rely on it.

References

  1. NFPA 555, Guide on Methods for Evaluating Potential for Room Flashover, National Fire Protection Association, 2021 edition: hand methods for upper layer temperature and flashover.
  2. McCaffrey, B.J., Quintiere, J.G., and Harkleroad, M.F., “Estimating Room Temperatures and the Likelihood of Flashover Using Fire Test Data Correlations,” Fire Technology, Vol. 17, No. 2, 1981, pp. 98 to 119.
  3. Foote, K.L., Pagni, P.J., and Alvares, N.J., “Temperature Correlations for Forced-Ventilated Compartment Fires,” Fire Safety Science, Proceedings of the First International Symposium, 1986, pp. 139 to 148.
  4. Deal, S., and Beyler, C.L., “Correlating Preflashover Room Fire Temperatures,” Journal of Fire Protection Engineering, Vol. 2, No. 2, 1990, pp. 33 to 48.
  5. Beyler, C.L., “Analysis of Compartment Fires with Overhead Forced Ventilation,” Fire Safety Science, Proceedings of the Third International Symposium, 1991, pp. 291 to 300.
  6. Iqbal, N., and Salley, M.H., Fire Dynamics Tools (FDTs): Quantitative Fire Hazard Analysis Methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program, NUREG-1805, 2004, Chapter 2, and Supplement 1, 2013: method and lining material properties.
  7. Gross, D., Data Sources for Parameters Used in Predictive Modeling of Fire Growth and Smoke Spread, NBSIR 85-3223, National Bureau of Standards, 1985, Table 3: thermal properties of assorted materials at room temperature.

Frequently Asked Questions

What is the MQH method?

It is a correlation by McCaffrey, Quintiere and Harkleroad for the average hot gas layer temperature in a room with an open door or window. It ties the temperature rise to the fire heat release rate, the ventilation factor of the opening (area times the square root of its height) and the heat lost to the walls through an effective heat transfer coefficient. It was fit to more than 100 room fire tests and applies to layer temperatures up to about 600 degrees C.

What is the thermal penetration time?

It is the time for heat to reach through a wall or ceiling lining, estimated as (rho c / k) times the square of half the thickness. Before it, the lining behaves like a thick solid and absorbs heat quickly, so the coefficient is the square root of k rho c over time. After it, heat flows steadily through the lining and the coefficient is the conductivity divided by the thickness.

Which method fits a room with mechanical supply and exhaust?

Use the forced ventilation mode, which applies the Foote, Pagni and Alvares correlation with the supply air mass flow, and compare it with the Deal and Beyler energy balance shown beside it. If the room is sealed with no airflow, use the closed room mode, and if a door or window is open, use the MQH mode.

Does the calculator predict flashover?

It flags a temperature rise of about 500 degrees C, the common flashover criterion. To find the fire size needed for flashover directly, the flashover calculator compares the MQH, Babrauskas and Thomas correlations for the same room.

Related Tools and Services

More fire dynamics and detection calculators

Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.

Related Reading

Articles from DGA Insights on the code and the method behind this calculator.

Quick inquiry

Need these results reviewed for a submittal?

Your name, a way to reach you, and where the project is. One of our licensed PEs replies within one business day. Every inquiry is confidential.

Prefer to describe it first? Open the Project Desk