FDS Mesh Size Calculator

Size an FDS mesh from the design fire. Enter the heat release rate and the domain, and get the characteristic fire diameter D*, the cell size for coarse, moderate and fine resolution, and IJK cell counts that suit the FDS pressure solver.

  • Based on NIST FDS User’s Guide
  • Free, runs in your browser; your inputs stay on your device
  • Screening tool, not reviewed or sealed by a licensed engineer
  • Last updated October 2026

Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.

Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.

Design Fire

Computational Domain

Resolution

D*/dx is the number of cells across the characteristic fire diameter. Values of about 4 to 16 span the resolutions used in US NRC fire model validation work. No single value is an acceptable minimum: confirm the mesh with a sensitivity study.

Result

Characteristic fire diameter D*
0
Cell size
0
Total cells
0
Fire Froude number Q*
0
LevelD*/dxCellI × J × KTotal

Cell Size and Cell Count by Resolution

Keep these results

About This Tool

For a buoyant fire plume, the length scale that matters is not the physical size of the burner but the characteristic fire diameter, D* = (Q / (ρ∞ cp T∞ √g))2/5, where Q is the heat release rate and ρ∞, cp and T∞ are the density, specific heat and absolute temperature of the ambient air. The FDS User’s Guide measures mesh resolution as D*/δx, the number of cells across that diameter. The calculator takes the air density from the ideal gas law at sea-level pressure, cp = 1.005 kJ/(kg·K) and g = 9.81 m/s2; at 20 °C a 1 MW fire has a D* of 0.96 m.

Three levels are shown: D*/δx of 4 (coarse), 10 (moderate) and 16 (fine), which span the range used in the US NRC and EPRI fire model validation study, NUREG-1824, with a custom ratio for anything else. For each level the tool divides the domain into cells of that size. FDS solves for pressure with fast Fourier transforms in the y and z directions, which run best when the cell counts J and K are products of 2, 3 and 5, so those counts are rounded up to the next such number (37 becomes 40, 109 becomes 120). The x count is left as is. The FDS guide notes that the speed gain is usually small, so this is a convenience rather than a rule.

When a fire base diameter is entered, the tool also reports the fire Froude number, Q* = Q / (ρ∞ cp T∞ √(gD) D2), which equals (D*/D)5/2. Values well above 1 describe tall, jet-like fires; values well below 1 describe wide, low fires. Q* is one of the parameters NUREG-1824 uses to describe the range over which the models were validated.

Worked example

A 2.5 MW retail fire in a 30 m by 20 m mall space 6 m high, at 20 °C, has D* = 1.38 m. At the moderate level the cell size is 0.138 m and the mesh is 217 × 150 × 45, about 1.46 million cells, with the y count raised from 145 to 150 and the z count from 44 to 45. The coarse level gives 0.35 m cells and 94,000 cells; the fine level gives 0.086 m cells and about 6.0 million. With a 1.5 m fuel footprint, Q* is 0.82.

Assumptions and limits

D* uses the peak heat release rate entered; a growing fire is resolved more coarsely early on, when D* is smaller. Uniform cubic cells are assumed, and refined meshes near the fire, stretched grids and multiple meshes are not modeled. The FDS User’s Guide is explicit that no D*/δx value is an acceptable minimum on its own: the resolution needed depends on the quantity being predicted, and the mesh should be confirmed with a sensitivity study in which results stop changing as the cells get smaller.

When to bring in an engineer

Mesh choice, the design fire and validation all sit in a performance-based analysis that a reviewing authority will check. DGA performs fire and smoke modeling for smoke control, tenability and equivalency reports, and provides smoke control design.

References

  1. K. McGrattan, S. Hostikka, R. McDermott, J. Floyd, M. Vanella and others, Fire Dynamics Simulator User’s Guide, NIST Special Publication 1019, Sixth Edition, National Institute of Standards and Technology: mesh resolution and the characteristic fire diameter; mesh dimensions and the FFT pressure solver.
  2. US Nuclear Regulatory Commission and Electric Power Research Institute, Verification and Validation of Selected Fire Models for Nuclear Power Plant Applications, NUREG-1824 (EPRI 1011999), Volume 7: Fire Dynamics Simulator, 2007, and NUREG-1824 Supplement 1 (EPRI 3002002182), 2016.
  3. E.E. Zukoski, T. Kubota and B. Cetegen, “Entrainment in Fire Plumes,” Fire Safety Journal, Vol. 3, pp. 107 to 121, 1980/81: the dimensionless heat release rate Q*.

Frequently Asked Questions

What D*/dx should I use in FDS?

There is no single correct value. Ratios of about 4 to 16 cover the range used in the US NRC validation study, with 10 a common middle choice for smoke movement. The FDS User’s Guide says no value should be treated as an acceptable minimum, so run the model at two or three resolutions and check that the results you care about stop changing.

How do I calculate the characteristic fire diameter D*?

Divide the heat release rate in kW by the product of ambient air density, specific heat, absolute temperature and the square root of gravity, then raise the result to the power 2/5. At 20 C that denominator is about 1,111, so a 1,000 kW fire gives (1000 / 1111)^0.4 = 0.96 m.

Why should FDS mesh cell counts be multiples of 2, 3 and 5?

The default FDS pressure solver uses fast Fourier transforms in the y and z directions, which are most efficient when the number of cells in those directions factors into 2, 3 and 5. The x direction is not affected. FDS documentation notes the speed difference is usually small.

Does the cell size depend on the room size?

The cell size comes from the fire, through D*, not from the room. The room size sets how many cells are needed, which drives run time and memory. Large domains often use finer cells near the fire and coarser cells far away, split across several meshes.

Related Tools and Services

More fire dynamics and detection calculators

Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.

Quick inquiry

Need these results reviewed for a submittal?

Your name, a way to reach you, and where the project is. One of our licensed PEs replies within one business day. Every inquiry is confidential.

Prefer to describe it first? Open the Project Desk