Free Engineering Tool · NUREG-1805

Pool Fire Heat Release Rate Calculator

Pick a fuel, enter the pool size and the volume of liquid, and the calculator estimates how large the fire gets, how long it burns and how tall the flames are. It covers contained pools in a dike, curb or tray and thin unconfined spills, following the NUREG-1805 Fire Dynamics Tools method.

  • Based on NUREG-1805
  • Free, runs in your browser; your inputs stay on your device
  • Screening tool, not reviewed or sealed by a licensed engineer
  • Last updated October 2026

Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.

Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.

Fuel and Pool

An unconfined spill on a smooth floor spreads to a thin layer. A depth of about 0.7 mm (0.03 in.) is typical for most fuels; enter a measured or site-specific depth where one is known.

Fuel Properties

Result

Heat release rate
0
Burning rate per unit area
0
Burning duration
0
Mean flame height
0

Heat Release Rate and Pool Size

Keep these results

About This Tool

A burning pool of flammable liquid is one of the most common design fires in hazard analysis. Its size depends on how fast the liquid surface burns away per unit area. Large-pool tests show that the burning rate rises with diameter and levels off once the flames become optically thick, so the rate per unit area is written as m″ = m″∞ (1 − e−kβD), where m″∞ is the rate for a very large pool and kβ is an empirical constant for the fuel. The heat release rate is then Q = m″ · ΔHc · A. Alcohols burn with little soot and are handled with constant rates that step up with diameter (0.015, 0.022 and 0.029 kg/m²·s below 0.6 m, to 3 m and above 3 m).

A rectangular tray or spill is replaced by a circle of the same area, D = (4A/π)1/2. The burning duration is the fuel mass divided by the mass burning rate, t = Vρ / (m″A), which is the same as the fuel depth divided by the regression rate m″/ρ. The mean flame height uses the Heskestad correlation H = 0.235 Q2/5 − 1.02 D (Q in kW, lengths in m).

For an unconfined spill on a smooth floor, the liquid spreads until it is only a fraction of a millimeter deep. The spill area is the volume divided by the depth, with about 0.7 mm typical for most fuels. A layer this thin loses heat to the floor, so the burning rate is multiplied by a depth coefficient: 0.95 (1 − e−0.71δ) for gasoline, 0.91 (1 − e−0.58δ) for kerosene and JP-5, and 0.69 for other fuels at depths up to 5 mm (δ in mm). The fuel presets list the large-pool constants published for each liquid; every property can be edited.

Worked example

A 6 ft (1.83 m) diameter dike holds 55 gal (208 L) of gasoline. The diameter factor is 1 − e−2.1×1.83 = 0.979, so the burning rate is 0.055 × 0.979 = 0.0538 kg/m²·s. Over 2.63 m² (28.3 ft²) with 43,700 kJ/kg the fire releases about 6,180 kW, the flames average 19 ft (5.9 m) tall and the 154 kg of fuel lasts about 18 minutes. Spilled on an open floor at 0.7 mm, the same drum covers about 3,200 ft² (297 m²); with a depth coefficient of 0.37 the fire peaks near 266 MW but burns out in about 25 seconds.

Assumptions and limits

The correlations describe steady burning of a pool in the open, in still air, after the whole surface is involved. They do not include the growth period, wind, heating of the liquid by a hot compartment, or the extra feedback from walls and smoke layers that makes pools in rooms burn faster. Pools smaller than about 0.2 m burn in a different regime and are less predictable. Cryogenic fuels boil faster when first spilled on warm ground. Spill depths vary widely with the floor surface; carpet and rough or porous surfaces hold more liquid and can give larger, longer fires than the thin-layer values.

When to bring in an engineer

Pool fire size drives separation distances, structural exposure, detection and sprinkler design for flammable liquid areas. DGA builds design fires and runs fire modeling for these scenarios and provides code consulting on flammable liquid storage, containment and drainage.

References

  1. Iqbal, N., and Salley, M.H., Fire Dynamics Tools (FDTs): Quantitative Fire Hazard Analysis Methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program, NUREG-1805, U.S. Nuclear Regulatory Commission, 2004, Chapter 3; and NUREG-1805 Supplement 1, 2013.
  2. Babrauskas, V., “Estimating Large Pool Fire Burning Rates,” Fire Technology, 19 (4), 1983, pp. 251 to 261.
  3. Zabetakis, M.G., and Burgess, D.S., Research on the Hazards Associated with the Production and Handling of Liquid Hydrogen, Report of Investigations 5707, U.S. Bureau of Mines, 1961.
  4. Heskestad, G., “Luminous Heights of Turbulent Diffusion Flames,” Fire Safety Journal, 5 (2), 1983, pp. 103 to 108.
  5. Mealy, C.L., Benfer, M.E., and Gottuk, D.T., Fire Dynamics and Forensic Analysis of Liquid Fuel Fires, final report, grant 2008-DN-BX-K168, National Institute of Justice, 2011.
  6. NFPA 921, Guide for Fire and Explosion Investigations, National Fire Protection Association, 2024 edition: heat release rate and burning rate of liquid pool fires.

Frequently Asked Questions

How do you calculate the heat release rate of a pool fire?

Multiply the burning rate per unit area by the heat of combustion and the pool area. The burning rate per unit area for most hydrocarbons is the large-pool value times (1 – e^(-k beta D)), which accounts for smaller pools burning more slowly. A 1.83 m gasoline pool burns at about 0.054 kg/m2 s and releases about 6.2 MW.

How long will a pool fire burn?

Divide the mass of fuel by the mass burning rate of the whole pool, or equivalently divide the fuel depth by the regression rate (burning rate per unit area divided by liquid density). Large hydrocarbon pools regress at roughly 3 to 8 mm per minute, so a deep pool can burn for a long time while a thin spill burns out in seconds.

Why is a spill fire smaller per square foot than a pool fire?

A thin layer of liquid on a floor loses much of its heat to the floor, so less of the flame’s heat goes into evaporating fuel. Tests on smooth surfaces show burning rates of roughly one fifth to two thirds of the deep-pool value, which the depth coefficient captures. The spill covers a much larger area, so its total heat release rate can still be very high for a short time.

What is the equivalent diameter of a rectangular pool?

It is the diameter of a circle with the same area: D equals the square root of 4A divided by pi. It works best when the length is no more than about two to three times the width.

Related Tools and Services

More flammable liquids, gases and radiation calculators

Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.

Related Reading

Articles from DGA Insights on the code and the method behind this calculator.

Quick inquiry

Need these results reviewed for a submittal?

Your name, a way to reach you, and where the project is. One of our licensed PEs replies within one business day. Every inquiry is confidential.