Approvals by Jurisdiction · Comparison

Who Reviews Fire Protection Plans in Pennsylvania?

General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.

In Pennsylvania, fire protection plans are reviewed by whoever enforces the Uniform Construction Code (UCC) where the building sits: the municipality’s own certified code office, a certified third-party agency, or the Pennsylvania Department of Labor and Industry (L&I). The municipality’s election to enforce the UCC or opt out, the type of building and who owns it decide which of the three reviews the plans, and in most cases the owner does not get to pick.

Pennsylvania has no statewide fire code, so sprinkler, standpipe and fire alarm drawings are reviewed as part of the UCC building permit, which has used the 2021 International Codes (I-Codes) since January 1, 2026. This article compares the three reviewers side by side, shows how to find out which one has a given project, lists the cases where L&I reviews no matter where the building is, and explains where the local fire marshal fits.

At a Glance: Municipal or L&I Plan Review in Pennsylvania

  • Option A, local enforcement: the municipal code office reviews, using its own certified code officials, a third-party agency it retains, another municipality, or L&I under contract (34 Pa. Code 403.102(g)).
  • Option B, state enforcement: L&I reviews commercial plans in municipalities that opted out of UCC enforcement and every state-owned building statewide (34 Pa. Code 403.141(a) and (c)).
  • Deciding factor: the municipality’s election under 34 Pa. Code 403.102 and 403.103, shown on L&I’s Municipal Elections and Contact List, then whether the building is residential or commercial as 34 Pa. Code 401.1 defines them.
  • When A applies: in every municipality that enforces the UCC, which L&I puts at over 90 percent of Pennsylvania’s 2,562 municipalities (as of November 2026), for commercial and residential work alike.
  • When B applies: commercial work in an opt-out municipality, state-owned buildings anywhere, and work a municipality has contracted to L&I. Residential work in an opt-out municipality goes instead to a certified third-party agency the applicant hires (403.103(b)).
  • Cost and complexity direction: each reviewer sets its own fees, with municipal and third-party agency fees governed by 34 Pa. Code 401.2a; complexity rises where a locally adopted fire code adds fire department permits on top of the UCC review.

The Three Reviewers of Pennsylvania Fire Protection Plans

Every UCC reviewer must hold an L&I certification for the work reviewed. 34 Pa. Code 401.3(a) bars anyone from performing plan review or inspection under the UCC without current certification in the applicable category, and fire protection plan review is one of the examinations in the building plans examiner category listed in 34 Pa. Code 401.6. Within that rule, three kinds of reviewer handle fire protection plans.

The municipal code office. A municipality that adopts the UCC by ordinance enforces it through its own employed code officials, an intermunicipal agreement or a contract with another municipality (34 Pa. Code 403.102(a) and (g)). Philadelphia’s Department of Licenses and Inspections and Pittsburgh’s Department of Permits, Licenses and Inspections are the code offices of the state’s two largest cities.

A certified third-party agency. A third-party agency is a person or firm certified by L&I as a construction code official and contracted to review plans, inspect or enforce under the act (34 Pa. Code 401.1). An enforcing municipality may retain one or more agencies to act for it (403.102(g)(2)), and in an opt-out municipality an applicant for a residential building permit must hire one (403.103(b)).

The Department of Labor and Industry. L&I enforces the UCC for all buildings other than residential and utility and miscellaneous use structures in municipalities with no enforcement ordinance, and it reviews and inspects state-owned buildings everywhere (34 Pa. Code 403.141(a) and (c)). A municipality may also contract with L&I for plan review, inspection and enforcement of structures other than one- and two-family dwellings and utility and miscellaneous use structures (403.102(g)(5)).

The line between residential and commercial follows the UCC definitions in 34 Pa. Code 401.1. A residential building is a detached one- or two-family dwelling or a townhouse not more than 3 stories above grade plane, each with a separate means of egress; any other building, apartment buildings included, is commercial construction. Most fire protection plan review in Pennsylvania therefore happens on the commercial side.

Municipal Code Office, Third-Party Agency and L&I Side by Side

The three reviewers apply the same code and the same review clocks. They differ in when each one has the project, where the application goes and who hears an appeal. The table compares them as of November 2026.

ReviewerWhen it reviewsHow to fileReview clockAppeals go to
Municipal code office (own staff)The municipality adopted the UCC by ordinance and enforces with its own certified staff (34 Pa. Code 403.102(a), (g)(1))Permit application to the municipal permit office with the construction documents 403.42a requires, including fire protection shop drawingsCommercial: grant or deny within 30 business days (403.43(a)). Residential: 15 business days, or 5 with a design professional’s certification (403.63(a))The municipal board of appeals (403.121, 403.122)
Third-party agency retained by the municipalityThe municipality enforces through one or more agencies it retains (403.102(g)(2))As the municipality directs; the agency acts as the municipality’s code officialThe same 30 and 15 business day clocksThe municipal board of appeals (403.121, 403.122)
Third-party agency hired by the applicantResidential building permits in an opt-out municipality (403.103(b))Directly with an agency L&I has certified for residential plan review and inspectionResidential: 15 business days, or 5 with certification (403.63(a))34 Pa. Code 403.103 names no appeals body for this path
L&ICommercial work in an opt-out municipality (403.103(g), 403.141(c)); state-owned buildings statewide (403.141(a)); work a municipality contracts to L&I (403.102(g)(5))Application to L&I with three sets of construction documents (403.42a(b)); in an opt-out municipality the municipality tells the applicant in writing and copies L&I (403.103(g))Commercial: 30 business days (403.43(a))The Industrial Board, which holds the first hearing within 45 days of receipt (403.141(d))

The commercial clock is not a deemed approval. Under 34 Pa. Code 403.43(a) the code official must grant or deny a commercial application within 30 business days of filing, a denial must be in writing and cite the code provisions, and the official and applicant may agree in writing to a longer period. The residential clock in 403.63(a) works differently: an application not acted on in time is deemed approved.

Whichever body reviews, the fire protection content of the submittal is the same. 34 Pa. Code 403.42a(f)(3) requires fire protection system shop drawings that show code compliance, carry the information the referenced standards in International Building Code (IBC) Chapter 9 require, and are approved before installation begins. The filing sequence from application to inspection is set out in DGA’s guide to fire protection plan review under the PA UCC.

Figure 1: Three Review Paths Under the PA UCC

Municipal code office COVERS Commercial and residential work in opt-in municipalities FILED WITH The municipal permit office CLOCK 30 business days commercial; 15 residential (403.43, 403.63) APPEALS Municipal board of appeals (403.121, 403.122) Third-party agency COVERS Work a municipality assigns it; residential work in opt-out municipalities FILED WITH As the municipality directs, or the agency the applicant hires CLOCK Same 30 and 15 business day clocks as a code office APPEALS Board of the municipality where it acts for one L&I COVERS Commercial work in opt-out municipalities; state-owned buildings statewide FILED WITH L&I, with three sets of documents (403.42a(b)) CLOCK 30 business days commercial (403.43(a)) APPEALS Industrial Board, first hearing within 45 days Clocks are the maximum time to grant or deny an application under 34 Pa. Code Chapter 403, as of November 2026.
All three paths apply the same Uniform Construction Code and the same review clocks: 30 business days to grant or deny a commercial application (34 Pa. Code 403.43(a)) and 15 business days for a residential one (403.63(a)). What changes is who reviews, where the application is filed and which board hears an appeal: a municipal board under 403.121 and 403.122, or the Industrial Board for L&I decisions under 403.141(d).

Opens the Project Desk with your sentence. Our licensed PEs review every brief and reply within one business day.

How to Find Out Who Reviews Plans in a Pennsylvania Municipality

The starting point is L&I’s Municipal Elections and Contact List, a county-by-county table of all 2,562 Pennsylvania municipalities. For each one it shows whether the municipality opted in or out of UCC enforcement, whether it kept local amendments adopted before July 1, 1999, and the contact for its building code official. The list shows no last-updated date, so a call to the listed contact before filing is worth the few minutes it takes.

The list gives one of three answers. An opt-in municipality reviews plans itself or through the agency, municipality or L&I contract it uses, and the listed contact says which. An opt-out municipality sends commercial applicants to L&I and residential applicants to a certified third-party agency, and a state-owned building goes to L&I whatever the list says.

Owners and design teams sometimes ask which reviewer to choose. Outside opt-out residential work there is no choice: the municipality’s election and the building type fix the reviewer, and a municipality that stops enforcing must give 180 days’ notice (34 Pa. Code 403.102(e)), so the answer can change between projects. An enforcing municipality must also give each applicant a list of the other permits needed before the building permit (403.102(n)), which is a practical place to learn whether a local fire department permit or sign-off applies.

Figure 2: Which Body Reviews the Plans?

Fire protection plans for a PA building Is the building state-owned? Act 45 section 105(b); 34 Pa. Code 403.141(a) YES L&I reviews Sole jurisdiction, any municipality NO Does the municipality enforce the UCC? L&I Municipal Elections and Contact List OPT-IN Municipal review Own certified staff, a retained third-party agency, another town or L&I by contract 403.102(g) OPT-OUT Is it a residential building? 1 or 2 family or townhouse, 3 stories max YES NO, COMMERCIAL Applicant hires a third-party agency Certified for the work, 403.103(b) L&I reviews commercial work 403.103(g) and 403.141(c) L&I reports that over 90 percent of the 2,562 municipalities enforce the UCC locally.
Three questions decide the reviewer: state ownership sends a building to L&I under 34 Pa. Code 403.141(a); a municipality that enforces the UCC reviews through its own staff, a third-party agency, another municipality or L&I by contract (403.102(g)); in an opt-out municipality, commercial work goes to L&I (403.141(c)) and residential work to a certified third-party agency the applicant hires (403.103(b)).

When L&I Reviews Regardless of the Municipality

L&I has sole jurisdiction over every state-owned building in Pennsylvania. Section 105(b) of the Pennsylvania Construction Code Act (Act 45 of 1999) and 34 Pa. Code 403.141(a) give L&I plan review and inspection of those buildings, with notice to the municipality, which may observe and may see the plans on request. A sprinkler retrofit in a state agency building therefore goes to L&I even inside an opt-in city.

L&I also holds sole jurisdiction over all elevators statewide. Fire service access elevators and occupant evacuation elevators, which Pennsylvania kept in its adoption of 2021 IBC Sections 3007 and 3008, fall under that elevator jurisdiction for the elevator equipment itself, so a high-rise can have its sprinkler plans reviewed locally and its elevator equipment reviewed by L&I. L&I has stated that its amended elevator regulation, 34 Pa. Code Chapter 405, takes effect December 20, 2026.

Two narrower cases bring L&I in as well. Accessibility under UCC Chapter 11 stays with L&I until the municipality employs or contracts with a code administrator certified as an accessibility inspector and plans examiner (34 Pa. Code 403.102(o)). And because a municipality may hand commercial plan review to L&I by contract under 403.102(g)(5), an opt-in status on the list does not always mean the municipal office does the review.

Other state approvals sit beside the UCC review rather than inside it. 34 Pa. Code 403.42a(n) lists approvals the application may also need, such as those under the Health Care Facilities Act, and each comes from the agency that administers that law.

Where Each Pennsylvania Reviewer Has No Authority

Each reviewer works inside limits that Chapter 403 sets. The limits matter most when a project team files with the wrong office or assumes a contract covers more than it does.

  • Municipal code office: cannot review a state-owned building, which belongs to L&I under 34 Pa. Code 403.141(a), and its board of appeals may not rule on accessibility (403.121(g)).
  • Third-party agency: may act only in the categories L&I certified it for (401.3(a)); L&I’s list of certified third-party agencies for buildings shows whether each agency is certified for residential work, commercial work or both.
  • L&I by municipal contract: a contract under 403.102(g)(5) cannot cover one- and two-family dwellings or utility and miscellaneous use structures.
  • L&I in an opt-out municipality: does not review residential buildings, which go to the applicant’s third-party agency (403.103(b), 403.141(c)).
  • Every reviewer: accessibility modification and technical infeasibility requests go to the Accessibility Advisory Board, not to the plan reviewer’s appeal board (403.122(k), 403.142).

Where the Local Fire Marshal Fits in Pennsylvania Plan Review

The local fire marshal is not one of the three UCC reviewers. The UCC incorporates the International Fire Code (IFC) only to the extent the other adopted codes reference it (34 Pa. Code 403.21), and a municipality that wants the full IFC adopts it by its own ordinance. DGA’s article on whether Pennsylvania has a statewide fire code covers that split, and the Fire Code Cheat Sheet for NY, NJ, PA, MD and DE lists the adopted editions across the region.

Under the UCC, the building code official approves fire protection shop drawings before installation (34 Pa. Code 403.42a(f)(3)), and only a person certified by L&I in the applicable category may perform that review (401.3(a)). A fire marshal therefore approves UCC fire protection plans only where the municipality has made a certified fire official part of its code enforcement. Where a municipality has adopted a fire code by ordinance, the fire department can add its own permits and inspections on top of the UCC approval.

Pennsylvania’s two largest cities show how the split works in practice. Philadelphia’s Department of Licenses and Inspections issues the fire suppression systems permit through eCLIPSE, with a published review of 20 business days with plans as of November 2026, and enforces the Philadelphia Fire Code, while the Philadelphia Fire Department’s Board of Safety and Fire Prevention hears appeals of Fire Code violation notices. DGA’s guide to Philadelphia fire protection approvals walks through that city’s path.

In Pittsburgh, the Department of Permits, Licenses and Inspections issues the suppression systems and fire alarm permits through OneStopPGH. The Bureau of Fire issues its own permits there, such as hot work, hazardous materials storage and special event permits, separate from the plan review. DGA’s Pennsylvania and Philadelphia fire protection consulting page describes the firm’s work with reviewers across the state.

Key Takeaway: Pennsylvania fire protection plans are reviewed by whoever enforces the Uniform Construction Code where the building sits. In the municipalities that enforce, that is the municipal code office or a third-party agency it retains; in opt-out municipalities, L&I reviews commercial work and a certified third-party agency hired by the applicant reviews residential work; L&I reviews every state-owned building. L&I’s Municipal Elections and Contact List is the first check, and the 30 business day clock in 34 Pa. Code 403.43(a) applies to commercial work on every path.

Frequently Asked Questions

What is an opt-out municipality in Pennsylvania?

An opt-out municipality is one that elected not to administer and enforce the Uniform Construction Code. In those municipalities the Department of Labor and Industry reviews and inspects commercial work under 34 Pa. Code 403.141(c), and an applicant for a residential building permit hires a certified third-party agency under 34 Pa. Code 403.103(b). The Department’s Municipal Elections and Contact List shows the status of every municipality.

Does L&I review all commercial plans?

No. The Department of Labor and Industry reviews commercial plans in opt-out municipalities, in municipalities that contract with it under 34 Pa. Code 403.102(g)(5), and for state-owned buildings anywhere in Pennsylvania (34 Pa. Code 403.141(a)). In the municipalities that enforce the Uniform Construction Code, which the Department puts at over 90 percent of the total, the municipal code office or its third-party agency reviews commercial plans.

Can an owner choose the third-party agency?

Conditional: only for residential work in an opt-out municipality, where the applicant hires a third-party agency certified in the right categories (34 Pa. Code 403.103(b)). Where a municipality enforces through third-party agencies, the municipality retains them under 34 Pa. Code 403.102(g)(2), and commercial work in an opt-out municipality goes to the Department of Labor and Industry, so the owner does not pick the reviewer.

Does the fire marshal approve sprinkler plans in Pennsylvania?

No, not as a separate approval under the Uniform Construction Code. The building code official approves fire protection shop drawings before installation (34 Pa. Code 403.42a(f)(3)), and only a person certified by the Department of Labor and Industry in the applicable category may perform plan review (34 Pa. Code 401.3(a)). A fire marshal takes part only where the municipality has made a certified fire official part of its code enforcement, or where a locally adopted fire code adds fire department permits.

This article is general information, not a code determination for any project. Municipal elections, enforcement contracts and local fire code ordinances change; confirm the reviewing office and the adopted codes with the municipality where the building sits before filing.

Not Sure Who Reviews a Pennsylvania Project?

Send the address, the scope and the drawings in hand. DGA identifies the reviewing office, checks the design against the 2021 I-Codes and any local fire code, and prepares the fire protection documents the reviewer expects. Project briefs get confirmation and preliminary code feedback within one business day.

Send a Project Brief → View Related Services