Approvals by Jurisdiction · Jurisdiction
Does Pennsylvania Have a Statewide Fire Code?
General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.
No. Pennsylvania has no statewide fire code: the Uniform Construction Code (UCC) adopts the International Fire Code (IFC) only to the extent the other adopted codes reference it (34 Pa. Code 403.21), so a full fire code, with operational permits, existing-building rules and maintenance requirements, applies only where a municipality has adopted one by ordinance.
The UCC is a construction code. It governs fire protection systems when a building is built, altered or changes occupancy, and it reaches occupied buildings mainly when new work is done. Everything a fire marshal enforces after the certificate of occupancy depends on the local ordinance, which is why the same warehouse can face operational permits and annual inspections in one township and none across the road. This article explains what Pennsylvania adopts instead, how the model IFC compares with what actually applies, who enforces it and how to find the local rule.
At a Glance: Fire Code in Pennsylvania
- Jurisdiction: Pennsylvania, all 2,562 municipalities listed by the Department of Labor and Industry (L&I).
- Local code and edition: the UCC, 34 Pa. Code Chapter 403, on the 2021 International Codes (I-Codes) since January 1, 2026, with the 2021 IFC adopted by reference only; municipal fire codes adopted by ordinance, for example the 2018 IFC in Philadelphia and Bethlehem and the 2021 IFC in Reading (as of November 2026).
- Agency (authority having jurisdiction, AHJ): for construction, the municipal building code official, a certified third-party agency or L&I; for fire code matters, the official the municipal ordinance names, usually a fire marshal or fire code official.
- Filing or permit name: a UCC building permit for fire protection work (34 Pa. Code 403.42), with fire protection shop drawings approved before installation (403.42a(f)(3)); fire code operational permits only where a local ordinance provides them.
- Key difference from the model code: the IFC is not adopted as a standalone code statewide, so there are no statewide operational permits, fire inspections of occupied buildings or inspection, testing and maintenance (ITM) schedules.
- Review time range (as of November 2026): 30 business days for the building code official to grant or deny a commercial UCC permit application (34 Pa. Code 403.43(a)); 15 business days for residential, or 5 where a licensed design professional prepared and certified the drawings (403.63(a)). No statewide clock applies to municipal fire code permits.
Pennsylvania Has No Statewide Fire Code
Pennsylvania’s building rules come from the Pennsylvania Construction Code Act (Act 45 of 1999), which applies to the construction, alteration, repair and occupancy of all buildings in the Commonwealth (Act 45 section 104(a)). The Act produced one statewide construction code, the UCC, and no companion fire prevention code. New Jersey, New York, Maryland and Delaware each have a fire code with force across the state, which makes Pennsylvania the outlier in the region.
The practical result is a two-layer system. The UCC layer is uniform: every municipality either enforces it, hires a certified third-party agency to enforce it, or leaves commercial enforcement to L&I. The fire code layer is optional and local: a city, borough or township decides whether to adopt a fire code, which edition, which appendices and which amendments.
Figure 1: Fire Code Structure: Pennsylvania vs Its Neighbors
| State | Statewide fire code? | Fire code basis (as of November 2026) | Who enforces the fire code |
|---|---|---|---|
| Pennsylvania | No | 2021 IFC only as referenced by the UCC (34 Pa. Code 403.21); full IFC only by municipal ordinance, usually the 2018 or 2021 edition | The fire official the municipal ordinance names; no one where no fire code was adopted |
| New Jersey | Yes | Uniform Fire Code, N.J.A.C. 5:70 (New Jersey Administrative Code), with the State Fire Prevention Code on the 2018 IFC (5:70-3.1) | Department of Community Affairs (DCA) Division of Fire Safety with local enforcing agencies |
| New York State | Yes | 2025 Fire Code of New York State, 19 NYCRR (New York Codes, Rules and Regulations) Part 1225, derived from the 2024 IFC; New York City enforces its own 2022 NYC Fire Code | City, town, village or county code enforcement programs under 19 NYCRR Part 1203; the Fire Department of the City of New York (FDNY) in New York City |
| Maryland | Yes | State Fire Prevention Code, COMAR (Code of Maryland Regulations) 29.06.01: National Fire Protection Association (NFPA) 1 and NFPA 101 (2024), effective June 23, 2025 | State Fire Marshal or a designated county or municipal fire official (COMAR 29.06.01.04A) |
| Delaware | Yes | State Fire Prevention Regulations, 1 Del. Admin. Code 701 to 710 (2026 edition): NFPA 1 and NFPA 101 (2024) | Office of the State Fire Marshal, except in cities with their own fire marshal’s office, such as Wilmington |
What Pennsylvania Adopts Instead of a Fire Code
The UCC adopts the International Code Council (ICC) family of codes in 34 Pa. Code 403.21, with listed exceptions and modifications. The IFC appears in that list only to the extent the other adopted codes reference it, so fire code text enters the UCC piece by piece, where the International Building Code (IBC) or another adopted code points to it. Appendices to the adopted codes are not adopted unless listed (403.21(c)).
Since January 1, 2026 the adopted family is the 2021 I-Codes, under Regulation #12-125, which implemented the decisions of the UCC Review and Advisory Council (RAC). The RAC adopted the 2021 IFC by reference only, without modification. Act 45 section 304(c)(4) let a permit issue under the code in effect when a design or construction contract was signed if the application was filed within six months of the new regulations taking effect, and Philadelphia made the 2021 codes mandatory for applications received on or after July 1, 2026.
A fire code with full force is a municipal decision. The table shows how four municipalities have handled it, as read in their own codes. The editions differ, the appendices differ, and one ordinance ties the township to later IFC revisions instead of a fixed year.
| Municipality | Fire code adopted | Source |
|---|---|---|
| Philadelphia | Philadelphia Fire Code on the 2018 IFC, with city amendments; the city’s Department of Licenses and Inspections applies the 2021 IFC only where the 2021 building codes reference it | The Philadelphia Code, Title 4, Subcode F; Philadelphia Department of Licenses and Inspections applicable codes list |
| Bethlehem | 2018 IFC adopted in its entirety with local modifications, plus Appendices B, C, D, E, F, H, I and L | Codified Ordinances Article 1501, Section 1501.04, as restated by Ordinance 2022-15 |
| Reading | 2021 IFC, adopted as the City of Reading Fire Prevention Code, with Appendix Chapters A to N and local amendments | City Code Chapter 180, Part 14, Section 180-1401 (amendments in 180-1407) |
| Lower Merion Township | IFC as later supplemented and revised, with Appendices B to G, plus NFPA 101 (2000 edition) | Township Code Chapter 78 (Fire Prevention), Article II (Adoption of Standards; General Regulations) |
Adoptions as read in each municipality’s published code, as of November 2026. Local amendments are not shown. The Philadelphia Department of Licenses and Inspections shares the abbreviation L&I with the state Department of Labor and Industry; the two are separate agencies.
A Pennsylvania municipality is not required to adopt a fire code. Where none was adopted, the UCC is the only code that sets fire protection requirements, and those requirements reach a building only through a construction permit.
How the Model IFC Compares With What Applies in Pennsylvania
The model IFC does two jobs: it adds construction requirements alongside the IBC, and it governs how a building is operated and maintained once it is occupied. The UCC keeps most of the first job and none of the second. The table shows where each topic lands.
| Topic | Statewide rule (UCC) | Local rule (where a fire code is adopted) |
|---|---|---|
| New fire protection systems | UCC building permit (34 Pa. Code 403.42); 2021 IBC Chapter 9 with NFPA 13 (2019) for sprinklers; shop drawings approved before installation (403.42a(f)(3)); added, altered or relocated standpipe piping is not an ordinary repair and needs a permit (403.42(d)) | The same UCC permit, plus fire code items the ordinance assigns to the fire official, such as fire service features under IFC Chapter 5 |
| Existing buildings | Legal occupancy of a structure existing on April 9, 2004 may continue without change unless the UCC provides otherwise (403.1(d)(3)); alterations and changes of occupancy follow the 2021 International Existing Building Code (IEBC) | IFC Chapter 11 construction requirements for existing buildings and the general fire safety chapters, as adopted and amended |
| Operational permits | None | IFC Section 105.6 (2018 IFC) or 105.5 (2021 IFC), where the ordinance keeps the permit list; high-piled storage, hot work and assembly events are common examples |
| Inspection, testing and maintenance (ITM) | No recurring ITM schedule; the UCC lists maintenance in its scope (34 Pa. Code 403.1(a)(1)), but its permits and inspections apply when a system is installed, altered or repaired | IFC Section 901.6, which points to NFPA 25 for water-based systems and NFPA 72 for fire alarm systems; Philadelphia adds annual certification filed with the city’s Department of Licenses and Inspections |
Two consequences follow. A municipality’s fire code edition can lag or lead the UCC: Philadelphia and Bethlehem pair the 2021 IBC with a 2018 fire code, so a design team may receive comments written against two editions on the same project. And where no fire code was adopted, no local fire official enforces an ITM schedule on a sprinkler or alarm system.
Act 45 also leaves some state life safety rules in place outside the UCC. Section 104(d)(3) says nothing in the Act preempts licensure or federal certification requirements for health care facilities and state institutions, including building and life safety code standards, so those buildings answer to their licensing agency’s rules as well.
DGA confirms which building and fire codes govern a site and prepares code analyses for fire protection projects across New York, New Jersey, Pennsylvania, Maryland and Delaware. Project briefs get confirmation and preliminary code feedback within one business day. See where DGA works →
Who Enforces Fire Code Items in Pennsylvania, and How to Find the Local Ordinance
Construction enforcement follows the municipality’s UCC election. L&I states that over 90 percent of municipalities enforce locally, and under 34 Pa. Code 403.102(g) an enforcing municipality uses its own certified code officials, certified third-party agencies, an intermunicipal agreement or a contract with L&I.
Where a municipality opted out, L&I enforces the UCC for all buildings except residential and utility and miscellaneous use structures (403.141(c)), and L&I keeps sole jurisdiction over state-owned buildings everywhere (403.141(a)). DGA’s companion articles explain who reviews fire protection plans in Pennsylvania and how UCC plan review works step by step.
Fire code enforcement follows the fire code ordinance. Bethlehem’s Article 1501 assigns enforcement to the Bethlehem Fire Department, Bureau of Inspections, and makes the Fire Marshal and the fire code official the same office. In Philadelphia, the city’s Department of Licenses and Inspections inspects fire code complaints, and the Board of Safety and Fire Prevention in the Philadelphia Fire Department hears appeals of fire code violation notices. DGA’s guide to Philadelphia fire protection approvals covers the city’s filings in detail.
Finding the rule for a given site takes four checks:
- The UCC election. L&I’s Municipal Elections and Contact List shows, county by county, whether each municipality enforces the UCC or opted out, and gives the building code official’s contact.
- The fire prevention chapter. The municipality’s codified ordinances, usually published online by a code publisher, show whether a fire prevention chapter adopts the IFC and, if so, which edition.
- Appendices and amendments. The adopting section lists the appendices adopted and the local amendments, which can add sprinkler, alarm or key box requirements beyond the model text.
- The fire official. The fire marshal’s office confirms which permits it issues and whether it reviews plans before the building permit or inspects after it.
Figure 2: Which Fire Rules Apply to a Pennsylvania Building?
DGA’s Fire Code Cheat Sheet for NY, NJ, PA, MD and DE lists the statewide editions in one place; the municipal fire code still has to be read for each Pennsylvania site. The fire official’s office can confirm whether an amendment was adopted after the code publisher’s last update.
What No Statewide Fire Code Means for Permits, Operations and Existing Buildings
For new construction and alterations, the UCC permit is the fire protection approval everywhere in the state. Sprinkler, standpipe and fire alarm work is reviewed with the building permit or as a deferred submittal, and the municipality’s fire code adds requirements only where it was adopted. A high-piled storage project shows the split clearly: DGA’s article on getting a high-piled storage permit in Pennsylvania walks through the UCC permit that applies everywhere and the operational permit that exists only under a local fire code.
For operations, the local ordinance decides almost everything. Operational permits, fire lane enforcement, housekeeping, assembly occupant limits and periodic fire inspections are fire code functions, so they appear only where a municipality adopted the IFC or another fire code. Philadelphia is the strongest example: the city’s Department of Licenses and Inspections requires annual certification of sprinkler, standpipe, fire alarm, special hazard and emergency power systems, filed online in eCLIPSE by a licensed inspector, with failed systems corrected and recertified within 45 days.
For existing buildings, the UCC does not require retrofits on its own. The legal occupancy of a structure that existed on April 9, 2004 may continue without change unless the UCC provides otherwise (34 Pa. Code 403.1(d)(3)), and upgrades are triggered by alterations, additions or changes of occupancy under the 2021 IEBC. Retroactive fire protection, where it exists, comes from local law, such as Philadelphia Building Code Section B-903.2.11.7, which required certain existing buildings with a story 45 ft or more above the lowest level of fire department vehicle access to sprinkler the basement and the level of exit discharge by December 31, 2021.
Enforcement and appeals follow the same split. UCC violations are handled under the enforcement subchapter of Chapter 403 (Sections 403.81 to 403.86), and UCC appeals go to the municipal board of appeals or, for L&I decisions, the Industrial Board (403.141(d)). Fire code violations go through the municipality’s own process: in Philadelphia, appeals to the Board of Safety and Fire Prevention are due within 30 days of the violation notice, with a fee of $150 per building as of November 2026. DGA’s work in the city is outlined on the Philadelphia fire protection consultant page.
Key Takeaway: Pennsylvania has no statewide fire code. The UCC (34 Pa. Code Chapter 403, 2021 I-Codes since January 1, 2026) adopts the IFC only where the other adopted codes reference it, so operational permits, fire inspections and ITM enforcement exist only where a municipality adopted a fire code by ordinance, such as the 2018 IFC in Philadelphia and Bethlehem or the 2021 IFC in Reading. Check the UCC election and the local fire prevention chapter before designing or buying in Pennsylvania.
Frequently Asked Questions
Is the International Fire Code law in Pennsylvania?
Conditional: only in part statewide. The UCC adopts the 2021 IFC only to the extent the other adopted codes reference it (34 Pa. Code 403.21), and the full IFC, with operational permits and maintenance rules, is law only in municipalities that adopted it by ordinance, such as Bethlehem (2018 IFC) and Reading (2021 IFC).
Which fire code does Philadelphia use?
The Philadelphia Fire Code, Subcode F of Title 4 of The Philadelphia Code, based on the 2018 IFC with city amendments. The Philadelphia Department of Licenses and Inspections applies the 2021 IFC only where the 2021 building codes reference it.
Who inspects existing buildings for fire safety in Pennsylvania?
The municipal fire official, where the municipality adopted a fire code. The UCC lets the legal occupancy of a building existing on April 9, 2004 continue without change unless the UCC provides otherwise (34 Pa. Code 403.1(d)(3)), so routine fire inspections of occupied buildings come from local ordinances; in Philadelphia, the Department of Licenses and Inspections inspects fire code complaints.
Does the PA UCC cover sprinkler maintenance?
Conditional: the UCC lists maintenance in its scope (34 Pa. Code 403.1(a)(1)), but its permits and inspections apply when a sprinkler system is installed, altered or repaired, and it sets no recurring inspection and testing schedule. That schedule comes from a municipal fire code adopting IFC Section 901.6, which points to NFPA 25, or from a local program such as Philadelphia’s annual fire protection certification.
More in Approvals by Jurisdiction
- How Does AHJ Review Work in NYC, NJ and Philadelphia?
- How Do Pittsburgh Fire Protection Approvals Work?
- How Do Federal Agencies Review Leased-Space Fire Protection?
- What Is Maryland’s Sprinkler Law for New Homes?
- Does the Pennsylvania Fire and Panic Act Still Apply?
- What Does NYC Require for Construction Site Fire Safety?
This article is general information, not a code determination for any project. State and municipal code adoptions, local amendments and enforcement practice change; confirm the adopted codes and the authority having jurisdiction for the project.
Planning a Project in Pennsylvania?
Send the municipality, the building use and the scope of work. DGA confirms the UCC enforcement path and any local fire code, then sets out the fire protection requirements that apply before design starts. Project briefs get confirmation and preliminary code feedback within one business day.