Water Supply · Calculation

How Do You Calculate Standpipe Demand and Pressure?

Reviewed by a licensed Professional Engineer · NY, NJ, PA, MD, DE · Last reviewed · Code basis: NFPA 14 Chapter 7 and Chapter 9 (edition referenced by the adopted building code); NFPA 13 (2022) Chapter 28; 2022 NYC Building Code Appendix Q (NFPA 14 (2016) as modified); IBC Section 905

General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.

Standpipe demand is calculated by fixing the flow at the hydraulically most remote hose outlets, adding 250 gpm for each additional standpipe up to the cap, then starting at the required residual pressure at the most remote outlet and adding elevation and friction loss back to the pump discharge or the fire department connection. For a Class I or Class III system under NFPA 14, the National Fire Protection Association standard for standpipe and hose systems, the starting point is 100 psi residual at the most remote 2.5 in. outlet, 500 gpm on the most remote standpipe and 250 gpm on each additional standpipe, with the combined demand capped at 1,250 gpm, or 1,000 gpm where the building is sprinklered throughout (NFPA 14, Chapter 7).

The pressure side is plain hydraulics: 0.433 psi for every foot of elevation plus Hazen-Williams friction loss through the riser, the feed main, the fittings and the valves. An 8-story office with two standpipes and its most remote outlet 90 ft above the pump discharge needs 750 gpm at about 147 psi at the pump. This article lays out the inputs, the method, that worked example, a second variant for a sprinklered building with three standpipes, the errors reviewers catch most often and the point where the hand method stops.

At a Glance: Standpipe Demand and Pressure

  • What is calculated: the total standpipe flow in gpm and the residual pressure in psi required at the pump discharge, the fire department connection (FDC) or the water supply connection so that the most remote hose outlet receives its design pressure at its design flow.
  • Method in one line: fix 250 gpm at each of the two most remote outlets, add 250 gpm per additional standpipe up to the cap, start at 100 psi at the top outlet and add 0.433 psi per ft of elevation plus Hazen-Williams friction back to the supply point.
  • Inputs needed: standpipe class, number of standpipes, height of the most remote outlet above the supply point, pipe sizes and lengths, fitting and valve equivalent lengths, hose valve loss, the water supply curve and the pump curve where a pump exists.
  • Code and section: NFPA 14 Chapter 7 (design and hydraulic requirements) in the edition referenced by the adopted building code; NFPA 13 (2022) Chapter 28 for the hydraulic calculation method; 2022 New York City (NYC) Building Code Appendix Q, which names NFPA 14 (2016) and modifies it.
  • Typical result range (units): 500 to 1,250 gpm total flow; 130 to 200 psi at the pump discharge for a single-zone building up to about 12 stories, climbing with height until a second zone is needed.
  • Most common input error: starting at 65 psi instead of 100 psi at the most remote 2.5 in. outlet, which understates the pump pressure by 35 psi before any elevation or friction is counted.

What Inputs Does a Standpipe Calculation Need?

A standpipe calculation needs fewer inputs than a sprinkler calculation, but each one moves the answer by a large amount. The flow side depends on the class of system and the number of standpipes. The pressure side depends on height, pipe, fittings and the water supply.

InputUnitsSource
Standpipe class (I, II or III)ClassInternational Building Code (IBC) Section 905 and the fire department; Class I and III use 2.5 in. outlets, Class II uses 1.5 in. hose stations
Number of standpipesCountThe architectural plans: one standpipe per required exit stair, plus horizontal exits and roof outlets where required
Height of the most remote outlet above the supply pointftSections and the pump room elevation; measured to the hose valve, not the floor
Pipe sizes and lengthsin. and ftThe riser diagram; NFPA 14 Chapter 7 sets minimum riser sizes, with 6 in. the usual Class I riser in a taller building
Fittings and valvesEquivalent ftThe equivalent length table in NFPA 13 (2022) Chapter 28, adjusted for the C factor used
Hose valve and pressure-regulating device losspsi at the design flowThe manufacturer’s data sheet for the listed valve; typically a few psi at 250 gpm
Water supply curvegpm and psiA hydrant flow test no more than 12 months old (NFPA 13 (2022) Section 4.5.1.1 as applied to combined systems) or the public utility’s letter
Fire pump curvegpm and psiThe certified pump curve: rated point, churn pressure and the 150 percent point
DurationMinutesNFPA 14 Chapter 9 sets a 30-minute supply duration for sizing tanks and confirming the public supply

The class is the first thing to settle, because it fixes both the outlet size and the design pressure. DGA’s explainer on what a standpipe system is and how NFPA 14 Classes I, II and III differ covers the classes; this article assumes a Class I or Class III system, which is what nearly every high-rise and large commercial building in the region requires. Whether the building needs a standpipe at all is a separate question, answered in when a building needs a standpipe under IBC 905.3.

What Is the Method, Step by Step?

The method runs from the top of the building down to the supply, the opposite direction from the water. Every step adds pressure, so the number only grows.

  1. Fix the flow at the most remote outlets. On the hydraulically most remote standpipe, flow 250 gpm from the top outlet and 250 gpm from the next outlet below it, 500 gpm in total (NFPA 14 Chapter 7).
  2. Add the other standpipes. Flow 250 gpm from the top outlet of each additional standpipe, until the total reaches 1,250 gpm, or 1,000 gpm where the building is sprinklered throughout. A fourth standpipe in a sprinklered building adds no flow because the cap has been reached.
  3. Start at the required pressure. Set 100 psi residual at the most remote 2.5 in. outlet (65 psi at the most remote 1.5 in. outlet for a Class II system). Add the hose valve loss from the manufacturer’s data.
  4. Add elevation. Multiply the height from the most remote outlet down to the supply point by 0.433 psi per ft.
  5. Add friction. Work down each pipe segment with the Hazen-Williams formula using the flow in that segment and the equivalent length of pipe plus fittings and valves. The flow steps up at each point where another outlet or standpipe joins.
  6. Check the lower outlets. Where the static pressure at any hose connection would exceed 175 psi, NFPA 14 Chapter 7 calls for a pressure-regulating valve (PRV) at that outlet, and a 1.5 in. outlet also needs a device where its residual pressure would exceed 100 psi; no part of the system may exceed 350 psi in NFPA 14 (2016), or 400 psi in the 2019 edition.
  7. Compare with the supply or size the pump. Plot the demand point against the supply curve. If the supply cannot deliver the flow at the pressure, the gap sets the pump’s net pressure at the demand flow.

Figure 1: Formula Card: Standpipe Demand and Pressure

Qtotal = 500 gpm (most remote standpipe) + 250 gpm × (additional standpipes), not more than 1,250 gpm, or 1,000 gpm if sprinklered throughout

Psupply = 100 psi + Phose valve + 0.433 × H + Σ (pf × Leq)

pf = 4.52 × Q1.85 ÷ (C1.85 × d4.87) psi per ft

Legend: H is the height of the most remote outlet above the supply point in ft; Q is the flow in the segment in gpm; C is the Hazen-Williams coefficient (120 for new black steel); d is the internal diameter in in.; Leq is the pipe length plus fitting equivalent lengths in ft.

The flow comes from NFPA 14 Chapter 7: 250 gpm at each of the two most remote outlets, 250 gpm per additional standpipe, capped at 1,250 gpm or 1,000 gpm sprinklered. The pressure is 100 psi at the most remote 2.5 in. outlet plus 0.433 psi per ft of elevation plus Hazen-Williams friction, the method NFPA 13 (2022) Chapter 28 sets out for hydraulic calculations.

The friction term is the only part that needs a formula. DGA’s Hazen-Williams friction loss calculator returns psi per ft for any flow, diameter and C factor, which is enough to run every segment of a standpipe by hand.

Worked Example: an 8-Story Office With Two Standpipes

The building is an 8-story office with two exit stairs, so two Class I standpipes. Floor-to-floor height is 12 ft, the hose valves sit 6 ft above each floor and the pump discharge is at the first floor, so the most remote outlet on the 8th floor is 90 ft above the pump discharge.

Both risers are 6 in. Schedule 40 black steel (6.065 in. internal diameter, C = 120), and the feed main from the pump to the base of the remote riser is 30 ft of 6 in. pipe with a check valve, a gate valve, two elbows and a tee.

The flow is 500 gpm on the remote standpipe (250 gpm at the 8th-floor outlet and 250 gpm at the 7th-floor outlet) plus 250 gpm at the top outlet of the second standpipe: 750 gpm total, well under the 1,250 gpm cap. The pressure build-up from the top outlet to the pump discharge is tabulated below, using a 3 psi hose valve loss from a typical listed 2.5 in. valve and NFPA 13 (2022) Chapter 28 equivalent lengths for 6 in. fittings (30 ft per tee, 14 ft per elbow, 32 ft per swing check, 3 ft per gate valve).

StepFlowEquivalent lengthLoss per ftAdded pressureRunning total
Residual at the 8th-floor outlet250 gpm100.0 psi100.0 psi
Hose valve loss250 gpm3.0 psi103.0 psi
Elevation, 90 ft × 0.43339.0 psi142.0 psi
Riser, 8th-floor to 7th-floor outlet250 gpm12 ft pipe + 30 ft tee = 42 ft0.0027 psi/ft0.1 psi142.1 psi
Riser, 7th-floor outlet to base500 gpm78 ft pipe + six tees 180 ft + elbow 14 ft = 272 ft0.0098 psi/ft2.7 psi144.8 psi
Feed main, riser base to pump discharge750 gpm30 ft pipe + 93 ft fittings and valves = 123 ft0.0207 psi/ft2.5 psi147.3 psi

The demand is therefore 750 gpm at about 147 psi at the pump discharge. Elevation accounts for 39 psi of the 47 psi added above the outlet pressure; friction through 6 in. pipe at these flows adds only about 5 psi. That proportion is typical: in a standpipe calculation height dominates, and the pipe size matters far less than it does in a sprinkler system.

Figure 2: Pressure Build-Up From the Most Remote Outlet to the Pump

87654321 PUMP 8th floor: 250 gpm at 100 psi 7th floor: 250 gpm 250 gpm Most remote standpipe: 500 gpm Standpipe B Standpipe A, 6 in. Standpipe B, 6 in. 1st-floor outlet: 142 psi residualat 750 gpm; 169 psi static at churn, below the 175 psi limit 90 ft × 0.433 = 39 psi Pump discharge: 750 gpm at 147 psi 100 psi outlet + 3 psi hose valve + 39 psi elevation + 5.3 psi friction (6 in. riser and feed main, C = 120) Red outlets flow in the design; black outlets are closed. Floor-to-floor 12 ft, hose valves 6 ft above the floor.
With 250 gpm at each of the two most remote outlets of standpipe A and 250 gpm at the top of standpipe B, the demand is 750 gpm. The pressure climbs from 100 psi at the 8th-floor outlet by 3 psi of hose valve loss, 39 psi of elevation over 90 ft and 5.3 psi of friction to 147 psi at the pump discharge.

The second half of the example is the lower-floor check. At 750 gpm the first-floor outlet, 6 ft above the pump, sees about 142 psi residual: the 147 psi at the pump less 2.5 psi through the feed main and 2.6 psi of elevation. That is under 175 psi, but the 175 psi trigger in NFPA 14 Chapter 7 is static pressure, so the flowing number does not settle the question. The static case at churn decides it.

Suppose the pump is rated 750 gpm at 110 psi net, selected because the city main delivers 37 psi residual at 750 gpm (37 psi + 110 psi = 147 psi), and the certified curve shows churn at 120 percent of rated net pressure, or 132 psi. With 40 psi static on the suction, the discharge at churn is 172 psi and the first-floor outlet static is about 169 psi. That clears 175 psi by 6 psi, so no PRVs are needed on this building; a pump with a steeper curve, churning at 140 percent of rated net pressure, would push the first-floor outlet to about 191 psi and PRVs on the lower floors would follow. The pump selection itself, including the churn and 150 percent checks against NFPA 20, the fire pump standard, is covered in how to size a fire pump for rated flow and pressure.

Opens the Project Desk with your sentence. Our licensed PEs review every brief and reply within one business day.

Variant: a Sprinklered Building With Three Standpipes

Now take the same 8-story building, sprinklered throughout, with a larger floor plate that needs three exit stairs and three standpipes. The flow is 500 gpm on the remote standpipe plus 250 gpm on each of the other two, 1,000 gpm, which lands exactly on the sprinklered cap of 1,000 gpm. A fourth standpipe would not raise the demand.

The pressure path is the same as the first example until the feed main, which now carries 1,000 gpm: 0.0352 psi per ft over 123 equivalent ft adds 4.3 psi instead of 2.5 psi, so the pump discharge demand becomes about 149 psi. The sprinkler system shares the risers, which raises the question of how the two demands combine.

Under NFPA 14 Chapter 7, where the building is sprinklered throughout, the combined system is designed for the larger of the standpipe demand and the sprinkler demand including its hose allowance, not the sum. A light hazard office sprinkler demand of roughly 400 gpm with hose at 60 psi is far below 1,000 gpm at 149 psi, so the standpipe demand governs and the sprinkler floor control valves hang off a riser already sized for it. How to plot that demand point against the supply, and what to do when the supply curve falls short, is the subject of how to plot sprinkler demand against the supply curve.

Which Errors Show Up Most Often?

Standpipe calculations fail review for a short list of reasons, and nearly all of them come from the flow and pressure assumptions rather than the arithmetic. The table pairs each error with what it does to the answer.

ErrorEffect on the resultFix
Starting at 65 psi instead of 100 psiUnderstates the Class I or III demand pressure by 35 psi; 65 psi is the Class II value, and it applies to Class I outlets in New York City only because Appendix Q modifies NFPA 14 (2016) Section 7.8.1Use 100 psi at the most remote 2.5 in. outlet outside New York City
Forgetting elevationLeaves out 0.433 psi per ft, 39 psi in the example, the single largest termMeasure from the hose valve, not the floor, down to the pump discharge
Forgetting the second outlet on the remote standpipeUses 250 gpm instead of 500 gpm on the remote riser, understating flow by 250 gpm and friction in every downstream segmentFlow the two most remote outlets of the most remote standpipe
Forgetting the capA sprinklered building with five standpipes is calculated at 1,500 gpm instead of 1,000 gpm, oversizing the pump and the serviceStop adding standpipes at 1,250 gpm, or 1,000 gpm sprinklered throughout
Summing sprinkler and standpipe demandAdds 400 gpm to a 1,000 gpm standpipe demand that already governsUse the larger of the two demands in a building sprinklered throughout
Ignoring hose valve and PRV lossDrops 3 to 10 psi per outlet, and more through a pressure-regulating valve set near its floor pressureTake the loss at 250 gpm from the valve’s data sheet
Lower outlets above 175 psi without PRVsThe static case at pump churn, not the flowing case, is where outlets exceed 175 psi; a calculation that checks only the demand point misses itCheck static at churn plus suction pressure at every 2.5 in. outlet

Summing the two demands deserves a second warning because it looks conservative. The larger pump it produces churns at a higher pressure and drives the lower outlets over 175 psi, which then forces pressure-regulating valves the building never needed.

Where Does the Hand Method Stop and a Sealed Calculation Begin?

The hand method above is exact for a single-zone, automatic wet standpipe fed by one pump or one public connection. It stops being sufficient the moment the building has more than one pressure zone, an express riser feeding an upper zone, or pressure-regulating valves whose settings have to be computed floor by floor. NFPA 14 Chapter 7 sets the system pressure ceiling (350 psi in NFPA 14 (2016), 400 psi in the 2019 edition), New York City limits each zone to 300 ft, and a building that needs a second zone needs a pump-and-tank arrangement that a licensed Professional Engineer (PE) lays out with the fire department.

A manual standpipe changes the supply end of the calculation. NFPA 14 Chapter 7 allows a manual system to be calculated with the fire department pumper supplying the FDC, so the design point moves to the FDC inlet and the available pressure is the fire department’s pumper capacity set with the authority having jurisdiction (AHJ), less the hose lay from the hydrant. The outlet pressure and elevation terms do not change; only the supply point does.

New York City runs its own version of the standard. The 2022 NYC Building Code Appendix Q names NFPA 14 (2016) in Section Q105.1 and modifies it, among other things replacing the 100 psi minimum in Section 7.8.1 with 65 psi, limiting each standpipe zone to 300 ft, capping hose outlet pressure in the lowest zone at 210 psi and requiring in Section 7.7.2 that the system demand be supplied independently by the attached water supply and by each FDC. A standpipe calculation for a New York City building therefore starts from a different outlet pressure and has to be run twice, once from the pump and once from each FDC.

Pressure-regulating valves are a sizing problem of their own: each valve is set for its floor, the loss through it at 250 gpm comes from the manufacturer’s curve, and NFPA 14 Chapter 7 requires that the outlet pressure below the valve stays within the 175 psi and 100 psi limits across the full range of inlet pressures. Where a project has PRVs, zones or a manual system, the sealed hydraulic calculation goes to the AHJ with the standpipe drawings, and DGA runs it under the firm’s standpipe design service.

How Do the Jurisdictions Differ?

The method is the same in every state DGA works in, because every adopted building code reaches NFPA 14 through its Section 905. What differs is the NFPA 14 edition, the local modifications and who reviews the calculation.

JurisdictionAdopted code and NFPA 14 editionAHJFiling or permit
New York State (outside NYC)2025 Uniform Code (2024 IBC) Section 905; NFPA 14 in the edition referenced by the 2024 IBCLocal code enforcement official; local fire department for FDC locationBuilding permit with sealed standpipe drawings and hydraulic calculations
New York City2022 Building Code Section 905 and Appendix Q; NFPA 14 (2016) as modified: 65 psi at the most remote outlet (7.8.1), 300 ft zones (7.2.1 and 7.9.1), 210 psi maximum hose outlet pressure in the lowest zone, demand supplied by the water supply and by each FDC independently (7.7.2)Department of Buildings (DOB); Fire Department of New York (FDNY) for the FDC and hydrant arrangementDOB NOW sprinkler and standpipe work type with a sealed calculation
New JerseyUniform Construction Code (UCC), 2024 I-Codes effective August 17, 2026; NFPA 14 in the edition referenced by the 2024 IBCMunicipal construction official and fire protection subcode officialFire protection subcode permit under the UCC
PennsylvaniaUCC, 2021 I-Codes effective January 1, 2026; NFPA 14 in the edition referenced by the 2021 IBC; no statewide fire codeMunicipal or third-party code official; Philadelphia Department of Licenses and Inspections (L&I) in the cityBuilding permit with fire protection plans and calculations
MarylandCounty building permit on the 2021 IBC; NFPA 14 in the edition referenced by the 2021 IBC; State Fire Prevention Code is NFPA 1 (2024)County building official; State or county fire marshalCounty building permit; fire marshal plan review as the AHJ’s policy directs (COMAR 29.06.01.08)
DelawareCounty IBC (2021 in New Castle and Sussex, 2018 in Kent and Wilmington); State Fire Prevention Regulations, Regulation 701 (2026) with NFPA 1 (2024); NFPA 14 in the edition those codes referenceOffice of the State Fire Marshal; county building officialState Fire Marshal plan review before the county building permit (1 Del. Admin. Code 701)

Editions as of November 2026. Local amendments other than New York City’s Appendix Q are not shown.

Key Takeaway: Standpipe demand is 500 gpm on the most remote standpipe plus 250 gpm on each additional one, capped at 1,250 gpm or 1,000 gpm in a building sprinklered throughout; the pressure is 100 psi at the most remote 2.5 in. outlet plus 0.433 psi per ft of height plus friction. Height does most of the work: an 8-story office with its top outlet 90 ft above the pump needs about 147 psi at the discharge, of which 39 psi is elevation and only about 5 psi is friction. The step most calculations miss is the static check at pump churn, which decides whether the lower outlets need pressure-regulating valves.

Frequently Asked Questions

Is 65 psi an acceptable design pressure at the most remote standpipe outlet?

Conditional: 65 psi is the NFPA 14 value for a Class II 1.5 in. hose station, and it is the New York City value for Class I and III outlets because 2022 Building Code Appendix Q replaces 100 psi with 65 psi in NFPA 14 (2016) Section 7.8.1. Everywhere else in the region a Class I or III system is calculated at 100 psi residual at the most remote 2.5 in. outlet.

Does a combined sprinkler and standpipe system add the two demands together?

No. Where the building is sprinklered throughout, NFPA 14 Chapter 7 designs the combined system for the larger of the standpipe demand and the sprinkler demand including hose, and the standpipe demand almost always governs. Summing them oversizes the pump and pushes the lower outlets toward the 175 psi limit.

Does every standpipe in the building add 250 gpm to the demand?

No. The most remote standpipe counts 500 gpm and each additional standpipe adds 250 gpm only until the total reaches 1,250 gpm, or 1,000 gpm in a building sprinklered throughout. In a sprinklered building the fourth and later standpipes add nothing to the calculated flow.

When does a standpipe outlet need a pressure-regulating valve?

Conditional: NFPA 14 Chapter 7 calls for a pressure-regulating device where the static pressure at a hose connection would exceed 175 psi, and at a 1.5 in. outlet where the residual pressure would exceed 100 psi. Static pressure at pump churn plus suction pressure sets the count, so the check has to be run at churn, not at the demand point.

This article is general information, not a hydraulic calculation for any project. Code editions, local amendments and reviewer practice change; confirm the adopted code and the authority having jurisdiction for each project.

Need a Standpipe Calculation Sealed for Permit?

Send the riser diagram, the building height, the number of stairs and the flow test or pump data. DGA runs the standpipe demand and pressure calculation, checks the lower outlets at churn and seals the package for the AHJ. Project briefs get confirmation and preliminary code feedback within one business day.