Free Engineering Tool · NUREG-1805 data

Building Material Thermal Properties

Look up room-temperature thermal conductivity, density, specific heat, thermal inertia kρc and diffusivity for 23 common building and lining materials, then find how long heat takes to penetrate a layer and whether it behaves as thermally thick or thin.

  • Based on NUREG-1805 data
  • Free, runs in your browser; your inputs stay on your device
  • Screening tool, not reviewed or sealed by a licensed engineer
  • Last updated October 2026

Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.

Thermal Properties at Room Temperature

k thermal conductivity, ρ density, c specific heat, kρc thermal inertia, α = k/ρc thermal diffusivity. kρc and α are calculated from the listed k, ρ and c. Select a name to load it into the calculator. Sources: NUREG-1805 = NRC Fire Dynamics Tools table of interior lining materials; NBSIR 85-3223 = National Bureau of Standards data for assorted materials.

Thermal Penetration Time

Thermal penetration time
0
At the exposure time
0
Thermal inertia kρc
0
Thermal diffusivity α
0

Thermal Inertia Compared

Keep these results

About This Tool

Three properties describe how a solid takes up heat. Thermal conductivity k sets the rate of steady conduction, and the volumetric heat capacity ρc sets how much heat a unit volume stores per degree. Their product, the thermal inertia kρc, controls how fast an exposed surface heats up: materials with low kρc, such as foam plastics and fibrous insulation, reach high surface temperatures quickly, which is why they ignite sooner and why compartments lined with them lose less heat from the hot gas layer. The thermal diffusivity α = k / (ρc) controls how fast a temperature change travels into the material.

The table combines two public sources. Fifteen rows are the interior lining materials tabulated in NUREG-1805 (NRC Fire Dynamics Tools), and eight are room-temperature values from NBSIR 85-3223 (National Bureau of Standards). Thermal inertia and diffusivity are calculated from the listed k, ρ and c, so they can differ by a few percent from the rounded products printed in the sources.

The calculator gives the thermal penetration time used in the McCaffrey, Quintiere and Harkleroad (MQH) method of NFPA 555 and NUREG-1805: tp = (ρc / k) · (δ / 2)2, where δ is the layer thickness. Before tp the layer is thermally thick: the heat has not reached the back face and the effective wall conductance is hk = √(kρc / t). After tp it is thermally thin and hk = k / δ. Enter an exposure time to see which applies.

Worked example

A room is lined with 13 mm gypsum board (k = 0.17 W/m·K, ρ = 960 kg/m³, c = 1.1 kJ/kg·K). The penetration time is (960 × 1100 / 0.17) × (0.0065)2 = 262 s, about 4.4 minutes, so for a 20 minute fire the board is thermally thin and hk = 0.17 / 0.013 = 13.1 W/m²·K. A 200 mm concrete wall has a penetration time of 11,250 s (187.5 minutes), so at 20 minutes it is still thermally thick, with hk = √(1.6 × 2400 × 750 / 1200) = 49.0 W/m²·K.

Assumptions and limits

Values are for dry material at room temperature. In a fire, gypsum gives off its water of crystallization, concrete loses moisture and some materials char, melt or shrink, so properties at high temperature can differ greatly. The penetration time treats a single homogeneous layer and marks a gradual change with a single time; for layered assemblies or anything near the transition, use a conduction model. Product values vary by manufacturer, density and moisture content, so use test data for a specific product when it matters. For metals, which heat through in seconds, use a lumped heat capacity method for member temperatures. Fire resistance ratings come from tested or listed assemblies, not from these properties.

When to bring in an engineer

Lining properties feed compartment temperature estimates, ignition and flame spread analysis, and heat transfer through barriers. DGA uses them in fire and smoke modeling and in equivalency reports where a substitute material or assembly has to be justified.

References

  1. Iqbal, N., and Salley, M.H., Fire Dynamics Tools (FDTs): Quantitative Fire Hazard Analysis Methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program, NUREG-1805, U.S. Nuclear Regulatory Commission, 2004, Chapter 2; and NUREG-1805 Supplement 1, Vol. 2, 2013, Appendix A: thermal properties for common interior lining materials and the thermal penetration time.
  2. Klote, J.H., and Milke, J.A., Principles of Smoke Management, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, 2002: source cited by NUREG-1805 for the lining table.
  3. Gross, D., Data Sources for Parameters Used in Predictive Modeling of Fire Growth and Smoke Spread, NBSIR 85-3223, National Bureau of Standards, 1985, Table 3: thermal properties of assorted materials at room temperature.
  4. McCaffrey, B.J., Quintiere, J.G., and Harkleroad, M.F., “Estimating Room Temperatures and the Likelihood of Flashover Using Fire Test Data Correlations,” Fire Technology, Vol. 17, No. 2, 1981, pp. 98 to 119.
  5. NFPA 555, Guide on Methods for Evaluating Potential for Room Flashover, National Fire Protection Association, 2021 edition: MQH method, effective heat transfer coefficient and thermal penetration time.
  6. NFPA 921, Guide for Fire and Explosion Investigations, National Fire Protection Association, 2024 edition: thermal inertia and ignition of solid fuels.

Frequently Asked Questions

What is thermal inertia (k rho c)?

Thermal inertia is the product of thermal conductivity, density and specific heat. It measures how strongly a surface resists heating when it is suddenly exposed to a heat flux. Under the same exposure the surface temperature rises in proportion to one over the square root of k rho c, so foam insulation, with a k rho c thousands of times lower than concrete, heats and ignites far faster.

What does thermally thick mean?

A layer is thermally thick while the heat from the exposed side has not yet reached the back face, so it behaves as if it were infinitely deep. Once heat reaches the back face the layer is thermally thin, and steady conduction through its thickness governs heat loss. The thermal penetration time marks the switch.

How do you calculate thermal penetration time?

Use tp = (rho c / k) x (delta / 2)^2 with delta the layer thickness. For 16 mm gypsum board with k = 0.17 W/m.K, rho = 960 kg/m3 and c = 1,100 J/kg.K, tp = (960 x 1100 / 0.17) x 0.008^2 = 398 s, or about 6.6 minutes.

Why do material properties change in a fire?

Conductivity and specific heat depend on temperature, and many building materials change chemically as they heat. Gypsum and concrete absorb heat to drive off water, wood chars, and plastics soften or melt. Room-temperature values are a starting point for hand calculations, not a substitute for high-temperature data in a detailed heat transfer model.

Related Tools and Services

More reference data and conversions calculators

Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.

Quick inquiry

Need these results reviewed for a submittal?

Your name, a way to reach you, and where the project is. One of our licensed PEs replies within one business day. Every inquiry is confidential.

Prefer to describe it first? Open the Project Desk