Free Engineering Tool · NFPA 72 Annex B
Ceiling Jet Temperature and Velocity Calculator
Maximum gas temperature and velocity in the ceiling jet at a given distance from a steady fire, by the Alpert correlations. Covers fires away from walls, against a wall and in a corner, and gives the depth of the hot layer of gas flowing under the ceiling.
- Based on NFPA 72 Annex B
- Free, runs in your browser; your inputs stay on your device
- Screening tool, not reviewed or sealed by a licensed engineer
- Last updated October 2026
Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.
Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.
Fire and Ceiling
For a sprinkler or heat detector, use the radial distance to the device; with a square layout at spacing S the farthest point is 0.707 S from a device. “Away from walls” assumes the fire is at least about 1.8 ceiling heights from any wall.
Result
Temperature and Velocity Against Distance
About This Tool
When a fire plume strikes a flat ceiling it turns and spreads outward as a thin, fast layer of hot gas, the ceiling jet. Sprinklers and heat detectors sit in this flow, so its temperature and velocity set how fast they respond. Alpert correlated full-scale fire tests from 0.6 to 98 MW under ceilings 4.6 to 18 m high. In SI units, with ΔT in °C, Q in kW and lengths in meters, the maximum excess temperature is ΔT = 16.9 Q2/3 / H5/3 in the turning region (r/H ≤ 0.18) and ΔT = 5.38 (Q / r)2/3 / H beyond it. The maximum velocity is U = 0.947 (Q / H)1/3 for r/H ≤ 0.15 and U = 0.197 (Q / H)1/3 / (r/H)5/6 beyond.
H is the ceiling height above the top of the fuel and r is the horizontal distance from the fire axis. A fire against a flat wall is treated by doubling the heat release rate and a fire in a 90° corner by multiplying it by four, which accounts for the wall blocking air entrainment. The ceiling jet depth, the distance below the ceiling where the temperature rise has fallen to 37 percent of its maximum, follows 0.112 H [1 − e−2.24 r/H] for r/H between 0.26 and 2.0, about a tenth of the ceiling height.
Worked example
A steady 1,000 Btu/s (1,055 kW) fire under a 15 ft ceiling, in 68 °F air, produces a ceiling jet at 172 °F moving at 5.6 ft/s at a sprinkler 10 ft from the fire axis (r/H = 0.67), in a layer about 1.3 ft deep. Directly above the fire the gas reaches 318 °F at 19 ft/s. The same fire against a wall gives 234 °F and 7.0 ft/s at the 10 ft point, and in a corner 331 °F and 8.8 ft/s.
Assumptions and limits
The fire is steady and the ceiling is smooth, flat and unconfined, with no hot upper layer yet formed and no beams or soffits interrupting the flow. The values are the maxima within the jet, found close to the ceiling; a device mounted lower may see much less. The correlations are based on the total heat release rate of the original tests, and the flames are assumed to end well below the ceiling. For a growing fire, the time for gas to travel to the device and the lag of the device itself matter; use the detector activation time calculator.
When to bring in an engineer
Ceiling jet estimates support performance-based detector and sprinkler spacing, high-ceiling and sloped-ceiling layouts, and equivalency requests. DGA provides fire alarm design and fire modeling for these cases.
References
- NFPA 72, National Fire Alarm and Signaling Code, National Fire Protection Association, 2025 edition, Annex B (Engineering Guide for Automatic Fire Detector Spacing).
- R.L. Alpert, “Calculation of Response Time of Ceiling-Mounted Fire Detectors,” Fire Technology, Vol. 8, No. 3, 1972, pp. 181 to 195.
- V. Motevalli and C.H. Marks, “Characterizing the Unconfined Ceiling Jet Under Steady-State Conditions: A Reassessment,” Fire Safety Science, Proceedings of the Third International Symposium, 1991, pp. 301 to 312.
- D.D. Evans and D.W. Stroup, Methods to Calculate the Response Time of Heat and Smoke Detectors Installed Below Large Unobstructed Ceilings, NBSIR 85-3167, National Bureau of Standards, 1985.
- U.S. Nuclear Regulatory Commission, Fire Dynamics Tools (FDTs), NUREG-1805, 2004, Chapter 10 (sprinkler response time).
Frequently Asked Questions
What is a ceiling jet?
It is the thin, fast-moving layer of hot gas that spreads radially under a ceiling after the fire plume strikes it. It is usually only about 5 to 12 percent of the ceiling height deep, with the hottest and fastest gas close to the ceiling surface, where sprinklers and heat detectors are installed.
What is the turning region?
It is the area directly above the fire, out to about 0.15 to 0.18 times the ceiling height, where the rising plume turns to flow horizontally. In this region the temperature and velocity equal the plume values at the ceiling and do not depend on the distance from the axis.
Why double or quadruple the heat release rate near walls?
A wall or corner blocks part of the air the plume would otherwise draw in, so the plume stays hotter. By symmetry, a fire against a wall behaves like half of a fire twice as large, and a fire in a corner like a quarter of a fire four times as large. Tests show a fire that only touches a wall at one point behaves almost like a fire away from walls.
Can I use this for a growing fire?
Yes, as a quasi-steady estimate using the heat release rate at the moment of interest, provided the fire grows slowly compared with the gas travel time. For t-squared fires the detector activation time calculator uses correlations made for growing fires and includes the device response lag.
Related Tools and Services
More fire dynamics and detection calculators →
Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.