Free Engineering Tool · NFPA 92 / NFPA 72 Annex B

Fire Plume Temperature and Velocity Calculator

Centerline temperature, gas velocity and width of a fire plume at a chosen height above the fire, from the Heskestad plume equations with the virtual origin. The chart shows how temperature and velocity fall off with height and where the flames end.

  • Based on NFPA 92 / NFPA 72 Annex B
  • Free, runs in your browser; your inputs stay on your device
  • Screening tool, not reviewed or sealed by a licensed engineer
  • Last updated October 2026

Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.

Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.

Fire

Enter a negative value when the virtual origin lies below the fuel surface. A measured or separately correlated value (for example for deep storage arrays) can be used here.

Ambient Air

The plume equations assume uniform, uncontaminated ambient air. They stop applying where the plume enters a hot smoke layer or a temperature-stratified space.

Result

Centerline temperature
0
Centerline velocity
0
Plume radius
0
Mean flame height
0

Temperature and Velocity Against Height

Keep these results

About This Tool

Above the flames, a fire plume behaves like a buoyant plume from a point source located at the virtual origin z0. The Heskestad relations give the centerline temperature rise ΔT0 = 9.1 [T∞ / (g cp2 ρ∞2)]1/3 Qc2/3 (z − z0)−5/3 and the centerline velocity u0 = 3.4 [g / (cp ρ∞ T∞)]1/3 Qc1/3 (z − z0)−1/3. In normal air at 20 °C these become ΔT0 = 25.0 Qc2/3 (z − z0)−5/3 and u0 = 1.03 Qc1/3 (z − z0)−1/3, with heights in meters, Qc in kW and the rise in kelvin. The plume radius to the point where the rise has fallen to half the centerline value is b = 0.12 (T0 / T∞)1/2 (z − z0).

Qc is the convective part of the heat release rate, typically 0.6 to 0.8 of the total; 0.7 is a common design value. The virtual origin is z0 = 0.083 Q2/5 − 1.02 D from the total heat release rate and the fire diameter, or it can be entered directly when a measured or separately correlated value is available. The mean flame height L = 0.235 Q2/5 − 1.02 D marks where the plume equations start to apply. The peak gas velocity occurs just below the flame tip and is shown in the velocity tile.

Worked example

A 1,000 Btu/s (1,055 kW) fire on a 4 ft diameter area with a convective fraction of 0.7, in 68 °F air at sea level, has a mean flame height of 8.4 ft and a virtual origin 0.3 ft above the fuel. At 20 ft above the fuel the centerline temperature is 253 °F (a rise of 185 °F), the gas velocity is 16.8 ft/s and the plume is about 5.5 ft wide. At 12 ft the centerline is at 511 °F; at 40 ft it is down to 126 °F. Doubling the fire to 2,000 Btu/s raises the 20 ft value to 401 °F.

Assumptions and limits

The equations describe the time-averaged centerline of an axisymmetric plume rising through still, uniform ambient air, away from walls. They do not apply inside the flames: when the chosen height is below the mean flame height and the computed rise exceeds about 500 K (900 °F), the result is withheld. Measured mean centerline temperatures in large pool fires reach a rise of about 900 K low in the flame. The relations also stop applying where the plume enters a hot ceiling layer, where it impinges on a ceiling, or in a temperature-stratified space, and the local temperature fluctuates well above and below the mean.

When to bring in an engineer

Plume temperatures drive exposure of structural members, detector and sprinkler response and smoke filling. DGA performs fire modeling for exposures and tenability, and smoke control design for atriums and large spaces.

References

  1. NFPA 92, Standard for Smoke Control Systems, National Fire Protection Association, 2024 edition: axisymmetric plume relations.
  2. NFPA 72, National Fire Alarm and Signaling Code, National Fire Protection Association, 2025 edition, Annex B (Engineering Guide for Automatic Fire Detector Spacing).
  3. G. Heskestad, “Engineering Relations for Fire Plumes,” Fire Safety Journal, Vol. 7, 1984, pp. 25 to 32.
  4. G. Heskestad, “Virtual Origins of Fire Plumes,” Fire Safety Journal, Vol. 5, 1983, pp. 109 to 114.
  5. G. Heskestad, “Peak Gas Velocities and Flame Heights of Buoyancy-Controlled Turbulent Diffusion Flames,” 18th Symposium (International) on Combustion, The Combustion Institute, 1981, pp. 951 to 960.
  6. U.S. Nuclear Regulatory Commission, Fire Dynamics Tools (FDTs), NUREG-1805, 2004, Chapter 9 (centerline temperature of a buoyant fire plume).

Frequently Asked Questions

What is the virtual origin of a fire plume?

It is the height of the imaginary point source from which the plume above the flames appears to rise. For low, spread-out fires it lies below the fuel surface, and for tall, intense fires it lies above it. Measuring heights from the virtual origin makes the point-source plume equations fit real fires.

Why does the calculator not show a temperature inside the flames?

The plume equations are fitted to the region above the flames and predict unrealistically high values close to the fire. Inside the flames the mean centerline rise levels off at roughly 500 K near the flame tip and up to about 900 K lower down, so the tool reports that range instead of a number.

What convective fraction should I use?

Most flaming fires convect 60 to 80 percent of their heat release, with the rest radiated. A value of 0.7 is common for design. Clean-burning fuels such as alcohols convect more, about 0.8, and sooty fuels radiate more.

How does ambient temperature or altitude change the result?

Warmer or thinner air raises the centerline temperature rise and the velocity for the same fire, because the air has less density to absorb the heat. The calculator uses the ambient temperature and pressure to compute the air density with the ideal gas law.

Related Tools and Services

More fire dynamics and detection calculators

Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.

Related Reading

Articles from DGA Insights on the code and the method behind this calculator.

Quick inquiry

Need these results reviewed for a submittal?

Your name, a way to reach you, and where the project is. One of our licensed PEs replies within one business day. Every inquiry is confidential.