Free Engineering Tool · NFPA 80A

Exterior Fire Exposure Calculator

When one building burns, radiant heat from its windows or a flaming wall can ignite the building next door. Enter the exposing face, its openings and the separation; the calculator returns the incident heat flux, the separation that keeps it below the ignition criterion and the allowable openings, by the radiation method behind NFPA 80A.

  • Based on NFPA 80A
  • Free, runs in your browser; your inputs stay on your device
  • Screening tool, not reviewed or sealed by a licensed engineer
  • Last updated October 2026

Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.

Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.

Exposing Building

Exposed Building

Openings are taken as spread evenly over the face, with blank wall between them no wider than one third of the separation. For one large opening or a tight group, enter that opening or the smallest rectangle around the group as its own face at 100 percent.

Result

Incident heat flux
0
Recommended separation
0
View factor, centered
0
Allowable openings
0
Average emissive power
0
Opposite a corner
0

Exposure Plan and Heat Flux

Keep these results

About This Tool

NFPA 80A treats a burning building face as a flat rectangular radiator. Fire inside the building radiates through its windows and doors or, where the wall itself is combustible and burning, from the whole face. The openings are assumed to be spread evenly, so the face is replaced by a uniform emitter with an average emissive power E × p, where E is the emissive power of an opening and p is the fraction of the face that is open. The heat flux reaching the exposed building straight across from the center of the face is q″ = E p F, and the exposed building is taken as safe while q″ stays at or below the critical heat flux of its exterior.

View factor. For a target opposite the center of a face W wide and H high at distance d, F = (2/π) [X/√(1+X²) tan−1(Y/√(1+X²)) + Y/√(1+Y²) tan−1(X/√(1+Y²))], with X = W/(2d) and Y = H/(2d). The 2/π form is four corner rectangles of half the width and half the height added together; putting the full width and height into it overstates the factor by a wide margin. A target opposite a corner sees one full W by H rectangle: (1/2π) times the same bracket with X = W/d and Y = H/d. The view factor calculator covers any other target position.

Emissive power. From a temperature, E = εσT4 with σ = 5.67 × 10−11 kW/m²·K4; openings into a fully involved room are usually taken as black. NFPA 80A does not ask for a temperature. Its separation tables rest on a tolerable flux of 12.5 kW/m² at the exposed face and allowable view factors of 0.14, 0.07 and 0.035 for light, moderate and severe exposures, which correspond to openings radiating 89.3, 178.6 and 357.1 kW/m². Severity follows the fire load and the interior finish of the exposing building. The UK method in BR 187 uses 84 kW/m² for residential, office and assembly uses and 168 kW/m² for shops, industrial and storage buildings, with a criterion of 12.6 kW/m².

Criterion and results. 12.5 kW/m² (0.3 cal/cm²·s) is the level below which piloted ignition of wood is unlikely, the case when burning brands land on a heated wall; 33.5 kW/m² (0.8 cal/cm²·s) is the level for ignition of wood with no pilot. The calculator solves for the distance at which the flux falls to the criterion. NFPA 80A adds 5 ft (1.5 m) to that distance for flames projecting from the openings. BR 187 assumes a mirror image of the building on the far side of the boundary, so the flux is checked at twice the boundary distance and the boundary distance is half the radiation distance. The allowable openings percentage is the criterion divided by E F at the distance entered (less 5 ft under NFPA 80A), which is how the enclosing rectangle tables are read.

Worked example

The long wall of a two-story retail building is 60 ft wide and 20 ft high (18.3 m by 6.1 m), with 30 percent of it in windows and doors and a moderate fire load. A wood-sided building stands 30 ft (9.14 m) away. The openings average 178.6 × 0.30 = 53.6 kW/m². Opposite the center, X = 30/30 = 1.0 and Y = 10/30 = 0.333, so F = 0.257 and the flux is 13.8 kW/m², above 12.5. The flux falls to 12.5 kW/m² at 32.3 ft, so NFPA 80A would ask for 37.3 ft. At the 30 ft available, the openings would have to drop to about 22 percent, or the extra openings would need protection.

Assumptions and limits

The method is a steady, peak-intensity radiation check with no credit for absorption in the air, glazing on the exposed building or wind. It assumes the openings are spread evenly, with blank wall between them no wider than about one third of the separation; for a few large openings or a cluster, check the smallest rectangle around them and the largest single opening as faces of their own and keep the worst answer. The separations assume the fire department arrives and protects exposures early in the fire, so they are not meant to hold off a fully developed fire left to burn. Flame contact, burning brands, wind-tilted flames and fire spread up the building’s own face are outside the method. Sprinkler credits and the code limits on openings by fire separation distance, such as IBC Section 705.8, are separate requirements and are not applied here.

When to bring in an engineer

Exposure separation comes up with new buildings near property lines, additions with large glazed walls, outdoor storage yards and owners asking whether a neighbor’s fire could reach them. DGA reviews these under the building and fire codes in code consulting and carries complex faces, wind and time-dependent fires through fire modeling.

References

  1. NFPA 80A, Recommended Practice for Protection of Buildings from Exterior Fire Exposures, National Fire Protection Association, 2022 edition (a 2027 edition is in the 2026 revision cycle): Section 4.4 and Annex A.4.4.7, exposure severity and the separation basis.
  2. McGuire, J.H., “Fire and the Spatial Separation of Buildings,” Fire Technology, 1 (4), 1965, pp. 278 to 287.
  3. Law, M., Heat Radiation from Fires and Building Separation, Fire Research Technical Paper No. 5, HMSO, London, 1963.
  4. Chitty, R., External Fire Spread: Building Separation and Boundary Distances, BR 187, 2nd ed., BRE, 2014.
  5. Howell, J.R., A Catalog of Radiation Heat Transfer Configuration Factors, University of Texas at Austin (online): plane element to a parallel rectangle.
  6. International Code Council, International Building Code, current edition, Section 705.8: openings in exterior walls by fire separation distance.

Frequently Asked Questions

How far apart should buildings be to prevent fire spread by radiation?

It depends on the size of the burning face, how much of it is open, the fire load inside and what the neighboring wall is made of. Under NFPA 80A the separation is the distance at which radiant heat from the openings falls to 12.5 kW/m2, plus 5 ft for flames projecting from the windows. A 60 ft by 20 ft wall at moderate severity needs about 74 ft if it is fully open, but about 28 ft if only 20 percent of it is windows and doors.

What heat flux ignites wood siding?

About 12.5 kW/m2 (roughly 4,000 Btu/hr per square foot) when a pilot such as a burning brand is present, and about 33.5 kW/m2 with no pilot. These classic thresholds come from tests on wood. Painted or weathered surfaces, vinyl siding and plastics behave differently, so the calculator lets you enter another critical flux.

What is the difference between NFPA 80A and BR 187?

Both use the same radiation model: a uniform rectangular radiator, a target opposite its center and a piloted ignition criterion near 12.5 kW/m2. NFPA 80A gives a building to building separation, sets the radiation from the exposure severity and adds 5 ft for flame projection. BR 187 is the UK method; it measures to the site boundary and assumes an identical building on the other side, so the boundary distance is half the separation.

Does the building code use this calculation?

Not directly. The IBC limits exterior wall openings and sets fire-resistance ratings by fire separation distance in its own tables. NFPA 80A is a recommended practice that owners, designers and authorities having jurisdiction use for exposure assessments, and the radiation method supports alternative designs and evaluations of existing buildings.

Related Tools and Services

More flammable liquids, gases and radiation calculators

Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.