Storage and Commodities · Trigger

What Fire Code Rules Apply to Outdoor Storage?

Reviewed by a licensed Professional Engineer · NY, NJ, PA, MD, DE · Last reviewed · Code basis: IFC 2024 (2025 Fire Code of New York State); 2022 NYC Fire Code; IFC 2018 (NJ Uniform Fire Code, Philadelphia Fire Code); IFC 2021 (PA local adoption); NFPA 1 (2024) in MD and DE

General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.

Combustible materials stored outdoors at a warehouse or industrial site must stay at least 10 ft from every lot line and no more than 20 ft high under International Fire Code (IFC) Section 315.4, with the lot line distance cut to 3 ft for piles 6 ft high or less. Pallets, finished lumber, tires and lithium-ion batteries each carry tighter rules for pile size, separation from buildings and other piles, fire apparatus access and water supply, and most IFC jurisdictions require an operational permit once a yard holds more than 2,500 cu ft of combustible material.

The rules come from the general storage section of the fire code plus the material chapters, so the material on the ground decides which numbers apply. This article sets out the outdoor storage thresholds, how they are measured, the exceptions, and what a yard needs once the rules apply in New York, New Jersey, Pennsylvania, Maryland and Delaware. Storage inside buildings is a separate question with its own articles in the Storage and Commodities series.

At a Glance: Outdoor Storage Fire Code Rules

  • Threshold(s) with units: general combustibles 10 ft from lot lines (3 ft for piles 6 ft high or less) and 20 ft maximum height; pallet piles 400 sq ft; finished lumber piles 150,000 cu ft; tire piles 5,000 sq ft, 50,000 cu ft and 10 ft high; lithium-ion battery piles 900 sq ft and 10 ft high (2024 IFC); operational permit above 2,500 cu ft of combustible material.
  • Code, edition, section: IFC Section 315.4 (2018, 2021 and 2024 editions); Section 315.7 for pallets (2018, 2021 and 2024); Section 2809 for finished lumber; Sections 3405 to 3408 for tires; 2024 IFC Section 320.4.3 for lithium-ion batteries; National Fire Protection Association (NFPA) 1, Fire Code (2024), Chapters 31, 33 and 34 (outdoor idle pallets in Section 34.11.3) in Maryland and Delaware.
  • Main exceptions: the 3 ft lot line distance for low piles; a smaller distance where the fire code official finds no hazard to the adjoining property; shorter pallet separations in front of blank masonry walls; alternative methods approved by the fire code official.
  • What applies once triggered: a dimensioned site plan, fire apparatus access roads within 150 ft of all of the yard, clear lanes between piles, hydrants within 400 ft, fencing for lumber and tire yards, and no storage under the canopy of a sprinklered building unless sprinklers extend beneath it.
  • Permit or filing: an operational permit under IFC Section 105.5 (2021 and 2024) or Section 105.6 (2018 edition and the New York City Fire Code), or the fire marshal’s site plan review in Maryland and Delaware.
  • Who decides: the fire code official: the local fire official in New Jersey, the Fire Department of the City of New York (FDNY), the municipal code official in New York State and Pennsylvania, and the State or local fire marshal in Maryland and Delaware.

What Are the Outdoor Storage Thresholds?

The IFC sets one baseline rule for all combustible materials in the open and then tightens it for the materials that burn hardest or pile highest. The table lists the outdoor storage limits by material with the section in the 2021 IFC. The 2018 and 2024 editions use the same section numbers except where the table says otherwise.

Material stored outdoorsPile limitsSeparationAccess, water and fencingIFC section
General combustible materials (empty crates, packaging, rubber, cork, scrap wood)20 ft maximum height; no area limit in the section10 ft from lot lines, or 3 ft where the pile is 6 ft high or less; none under the canopy or overhang of a sprinklered building unless sprinklers extend beneath itAccess road within 150 ft of all of the yard (Section 503.1.1); hydrant within 400 ft (Section 507.5.1)315.4, 315.4.1, 315.4.2
Pallets stored as part of the business400 sq ft per pile; 20 ft high10 ft from lot lines; distance to buildings and other piles set by the number of pallets (50 or fewer, 51 to 200, over 200), wood or plastic, and the construction and openings of the facing wallSame access road and hydrant rules315.7 (2018, 2021 and 2024); 2810 at pallet manufacturing and recycling yards
Finished lumber20 ft high; 150,000 cu ft per pilePiles divided by fire apparatus access roads into grid units no larger than 50 ft by 150 ft6 ft fence around permanent storage; hydrant and hose system, or portable extinguishers within 75 ft of travel2809.2 to 2809.5
Tires5,000 sq ft, 50,000 cu ft and 10 ft high per pile; groups of piles up to 150,000 cu ft40 ft between piles and from other stored products; 50 ft from lot lines and buildings for piles over 500 tires; 75 ft between groupsAccess road within 150 ft of every pile and at least 20 ft from it; 6 ft fence above 20,000 cu ft; water reaching all of the yard with 500 ft of hose; grass cleared 40 ft and brush 100 ft3405 to 3408
Lithium-ion batteries (New York State)900 sq ft and 10 ft high per pile20 ft from buildings, lot lines, public ways and means of egress; 10 ft between pilesSame access road and hydrant rules320.4.3 (2024 only)

Limits paraphrased from the IFC; the pallet separation tables are summarized, not reproduced. Maryland and Delaware apply NFPA 1 (2024) instead, as the jurisdiction table below shows.

Two points stand out in the outdoor storage table. The 20 ft height limit applies to almost everything that is not a tire or a battery. And the separation to the building, the distance owners most often want to shrink, is set by the material chapters rather than by Section 315.4, which governs only the lot line, the height and storage under overhangs for general combustibles.

Figure 1: The Distances That Govern an Outdoor Yard

LOT LINE PILE A 20 ft max height Tires: 10 ft max PILE B Pallets: 400 sq ft max Tires: 5,000 sq ft max 10 ft min Clear lane between piles: tires 40 ft, lithium-ion battery piles 10 ft WAREHOUSE sprinklered Canopy: no storage beneath unless sprinklered under it Separation to building, by material: tires 50 ft, lithium-ion 20 ft, pallets by pile size and wall type Hydrant: all of the yard within 400 ft along the access route FIRE APPARATUS ACCESS ROAD: 20 ft wide, within 150 ft of all of the yard Lot line: 10 ft minimum, or 3 ft where the pile is 6 ft high or less (IFC Section 315.4). Not to scale. Building and pile separations depend on the material stored.
Under IFC Section 315.4 a combustible pile stays at least 10 ft from the lot line, or 3 ft if it is 6 ft high or less, and no higher than 20 ft. Section 503.1.1 brings a fire apparatus access road at least 20 ft wide within 150 ft of every part of the yard, Section 507.5.1 requires on-site hydrants where any part of the yard is more than 400 ft from one, and tire piles need 40 ft between piles and 50 ft to buildings and lot lines.

How Is Outdoor Storage Measured?

Pile height is measured from the ground to the top of the stored material, and the 6 ft and 20 ft limits apply to the highest point of the pile, not its average. Pile area is the continuous footprint of the pile, so two stacks with no clear space between them count as one pile. Pile volume is the gross length times width times height, which is also how the 2,500 cu ft permit threshold is read.

Outdoor storage separations are measured horizontally from the nearest edge of the pile. A lot line includes the line between the site and a public street, so a yard along a road needs the same 10 ft as a yard beside a neighbor. Separation to a building is measured to the exterior wall, a canopy or overhang above the pile is checked separately under Section 315.4.1, and separation between piles is measured edge to edge across the clear lane.

Worked example: a distribution warehouse keeps idle wood pallets (48 by 40 in, about 6 in tall) in its yard in piles 24 ft by 16 ft 8 in and 10 ft high. Each pile covers 400 sq ft, the IFC maximum under Section 315.7.4, and holds 4,000 cu ft, so a single pile already exceeds the 2,500 cu ft permit threshold. At 20 pallets per stack and 30 stacks per pile, each pile holds about 600 pallets, which puts it in the over-200-pallet column of the Section 315.7 separation tables.

Two results follow from the pallet arithmetic. A pile of 200 pallets is only about 10 stacks of 20, roughly 133 sq ft, so nearly every working pallet pile lands in the largest separation category. And Section 315.7.2 sets a flat 10 ft from the lot line for pallet piles, without the 3 ft relief that Section 315.4 gives low piles of other combustibles.

Figure 2: Does This Outdoor Storage Trigger the Code?

Combustible material stored in the open on a warehouse or industrial site
More than 2,500 cu ft of combustible material or scrap tires, or more than 100,000 board feet of lumber?
NoNo permit, limits still apply10 ft to lot lines (3 ft at 6 ft high or less), 20 ft maximum height and the material limits for pallets, lumber and tires
Yes
PermitOperational permit and site planIFC Section 105.5 (2021, 2024) or Section 105.6 (2018)
SiteAccess roads, lanes and hydrantsSections 503 and 507, plus 315.7, 2809 or 3405 to 3408 by material
Pile height, size and separation limits apply to outdoor combustible storage of any quantity. Crossing 2,500 cu ft of combustible material or scrap tires, or 100,000 board feet of lumber, adds an operational permit in IFC jurisdictions, and with it the fire code official’s review of the site plan, access roads and hydrants.

What Exceptions and Alternatives Apply?

IFC Section 315.4 has two exceptions to the 10 ft lot line distance. The distance drops to 3 ft where the pile is no more than 6 ft high, and the fire code official may reduce it where no hazard to the adjoining property exists. Neither exception changes the 20 ft height limit.

The pallet separation tables in Section 315.7 build their own relief into the wall type. A blank masonry or concrete wall with no openings earns the shortest distance to a pallet pile, protected openings earn more, and a combustible wall or one with unprotected openings such as windows earns the longest, up to 90 ft for large wood pallet piles and more for plastic. Plastic pallets are treated more severely than wood, and listing to UL 2335 or FM 4996 (the Underwriters Laboratories and FM Approvals pallet fire tests) affects how plastic pallets are classified.

Lithium-ion battery storage under the 2024 IFC can sit 3 ft from a building or lot line instead of 20 ft where a 2-hour fire-resistance-rated wall with no openings, carried 5 ft beyond the storage above and on each side, stands between them, or where the batteries sit inside approved prefabricated structures with a 2-hour enclosure (Section 320.4.3). Outside these written exceptions, an owner who needs a smaller separation uses the alternative-methods provisions in IFC Chapter 1: an engineering analysis, typically a radiant heat exposure calculation for the pile and the facing wall, submitted to the fire code official for approval.

Code minimum vs what insurers expect: insurers often ask for more distance between outdoor pallet or combustible storage and the building than the fire code requires. FM Global’s guidance on idle pallet storage and exterior fire exposure (Data Sheets 8-24 and 1-20, paraphrased) ties the distance to the wall construction and the building’s sprinkler protection, so a yard laid out to the code minimum can still draw an insurer recommendation.

Opens the Project Desk with your sentence. Our licensed PEs review every brief and reply within one business day.

What Applies Once the Outdoor Storage Rules Are Triggered?

A yard with more than a few piles becomes a site layout question for the fire code official, who wants to see that apparatus can reach every pile, that hose can reach every face of every pile, and that the piles cannot spread fire to the building or the neighbor. The permit, the site plan, the access lanes and the water supply are the four items that follow once the outdoor storage thresholds are met.

Operational permits for outdoor storage are listed in IFC Section 105.6 in the 2018 edition, used by the New Jersey Uniform Fire Code and Philadelphia, and in Section 105.5 in the 2021 and 2024 editions. The table gives the model code thresholds, which a jurisdiction can amend.

Operational permitRequired when the site stores
Miscellaneous combustible storageMore than 2,500 cu ft gross volume of combustible containers, packaging, rubber, cork or similar material, including idle pallets
Lumber yards and woodworking plantsMore than 100,000 board feet of lumber
Wood productsMore than 200 cu ft of chips, hogged material, lumber or plywood
Storage of scrap tires and tire byproductsMore than 2,500 cu ft total volume of scrap tires
Lithium-ion batteries (2024 IFC)More than 15 cu ft of stored lithium-ion or lithium metal batteries

Most fire code officials ask for a dimensioned site plan with the permit application. The plan shows each pile’s footprint, height and material, the distances to lot lines, buildings and other piles, the fire apparatus access roads with their widths, and the hydrants. The yard site plan is a different document from the high-piled storage plan required for indoor storage, although a site with both usually submits them together.

Fire apparatus access roads must reach within 150 ft of all portions of a facility, measured along an approved route, under IFC Section 503.1.1, and the rule covers outdoor facilities as well as buildings. The roads are at least 20 ft wide with 13 ft 6 in of vertical clearance (Section 503.2.1), and piles may not encroach on them (Section 503.4). Lumber yards add the 50 ft by 150 ft grid of access roads, and tire yards keep every pile within 150 ft of a road but at least 20 ft from it, so a burning pile does not block the apparatus fighting it.

An approved water supply able to deliver the required fire flow is required for the premises under IFC Section 507.1, and on-site hydrants and mains are required where any part of the facility is more than 400 ft from a hydrant on an access road (Section 507.5.1). IFC Appendix B calculates fire flow for buildings, not open piles, so the fire code official sets the yard’s fire flow by an approved method under Section 507.3. A 3 ft clear space is kept around every hydrant (Section 507.5.5), and stacked pallets are a common reason a yard fails that rule.

Before the yard layout is fixed, a hydrant flow test on the nearest main shows what the water supply can deliver, and DGA’s hydrant flow test calculator turns the static, residual and pitot readings into available flow at 20 psi residual. Lumber yards need a hydrant and hose system installed to NFPA 24, the standard for private fire service mains, or portable extinguishers within 75 ft of travel (Section 2809.5). Tire yards need a water supply that reaches every part of the yard with no more than 500 ft of hose (Section 3408.1).

Fencing and housekeeping complete the outdoor storage requirements. Permanent lumber storage is fenced at least 6 ft high (Section 2809.4), and tire yards holding more than 20,000 cu ft are fenced at least 6 ft high with gates at least 20 ft wide (Section 3407). Tire yards also keep grass and weeds cleared for 40 ft and brush for 100 ft around the stored tires (Section 3405.5).

How Outdoor Storage Relates to Indoor Storage Rules

Outdoor piles are not high-piled combustible storage. IFC Chapter 32 applies to storage inside buildings above 12 ft, or 6 ft for certain high-hazard commodities where the fire code official requires it, and DGA’s guide to when IFC Chapter 32 applies to high-piled storage covers that trigger. The outdoor rules classify by material, while indoor sprinkler design classifies by commodity under NFPA 13, as explained in what commodity classification under NFPA 13 means.

The outdoor and indoor rules meet at the building wall. Product moved from the yard into the racks can change the indoor design basis, and lithium-ion batteries are the sharpest case: the outdoor limits in Section 320.4.3 do not answer whether the building’s sprinklers can handle the same batteries indoors, a question covered in how lithium-ion battery storage changes sprinkler design.

Which Fire Code Applies in Each State?

The IFC numbers in this article apply directly in New York State and New Jersey, and in Pennsylvania only where a municipality has adopted a fire code. New York City (NYC) writes its own Fire Code, and Maryland and Delaware enforce NFPA 1, whose outside storage chapters follow a similar structure with their own limits. The table shows the code in force for outdoor storage as of October 2026.

JurisdictionFire code and editionOutdoor storage rulesAuthority having jurisdiction (AHJ)Permit or filing
New York State (outside NYC)2025 Fire Code of New York State, based on the 2024 IFCSections 315.4, 315.7, 2809, 2810, 3405 to 3408 and 320.4.3City, town, village or county code enforcement officialOperating permit where the local program requires one under Title 19 of the New York Codes, Rules and Regulations (19 NYCRR) Part 1203
New York City2022 NYC Fire CodeFire Code Chapter 28 for lumber yards and wood waste materials and Chapter 34 for tire storage, plus the general precautions against fire in Chapter 3FDNY Bureau of Fire PreventionFDNY permit under Fire Code Section 105.6; Department of Buildings (DOB) filing for any building work
New JerseyUniform Fire Code (New Jersey Administrative Code, N.J.A.C. 5:70) on a 2018 IFC basis; Uniform Construction Code (UCC) on the 2024 International Codes for new buildingsSections 315.4, 315.7, 2809, 2810 and 3405 to 3408Local fire official, or the Division of Fire Safety where no local enforcing agency existsFire code permit under 2018 IFC Section 105.6 as amended by the Uniform Fire Code
PhiladelphiaPhiladelphia Fire Code on a 2018 IFC basisSame sections as the 2018 IFCDepartment of Licenses and Inspections (L&I) with the Philadelphia Fire DepartmentOperational permit under Section 105.6
Pennsylvania outside PhiladelphiaUCC on the 2021 International Codes for buildings; no statewide fire codeIFC sections only where the municipality has adopted a fire code by ordinanceMunicipal fire code official where one existsPermit under the local ordinance; UCC building permit for new structures
MarylandState Fire Prevention Code, Code of Maryland Regulations (COMAR) 29.06.01, adopting NFPA 1 (2024); 2021 International Building Code for buildingsNFPA 1 Chapter 34 (general storage, which applies indoors and outdoors, with outdoor idle pallets in Section 34.11.3), Chapter 31 (forest products) and Chapter 33 (outside storage of tires); Chapter 18 for access and water supplyState Fire Marshal or the county or city fire marshalFire marshal site plan review; county building permit
DelawareState Fire Prevention Regulations (Regulation 701, 2026 edition), adopting NFPA 1 (2024)The same NFPA 1 chapters, with Delaware amendmentsOffice of the State Fire Marshal; Wilmington Fire Marshal inside the cityState Fire Marshal site plan review before the county building permit

Editions as listed in DGA’s Fire Code Cheat Sheet for NY, NJ, PA, MD and DE, as of October 2026. Local amendments are not shown.

In Maryland and Delaware the NFPA 1 limits, not the IFC numbers in this article, decide the outdoor yard layout, and the fire marshal’s plan review is where that layout is approved. For yards at distribution centers, manufacturing plants and recycling operations, DGA’s industrial and high-hazard facilities practice starts by confirming which of these codes governs the site.

Key Takeaway: outdoor combustible storage under the IFC starts at 10 ft from the lot line (3 ft for piles 6 ft high or less) and 20 ft maximum height, then tightens by material: 400 sq ft pallet piles with separations tied to the facing wall, 150,000 cu ft lumber piles on a 50 ft by 150 ft access grid, 5,000 sq ft tire piles 50 ft from lot lines and buildings, and 20 ft clearances for lithium-ion batteries in New York State. Above 2,500 cu ft most yards need a permit, a site plan, access roads within 150 ft and hydrants within 400 ft.

Frequently Asked Questions

How far must outdoor storage be from a property line?

10 ft for general combustible materials under IFC Section 315.4, reduced to 3 ft where the pile is 6 ft high or less, or further where the fire code official finds no hazard to the adjoining property. Pallet piles also need 10 ft, tire piles need 50 ft, and lithium-ion battery piles under the 2024 IFC need 20 ft.

Does an outdoor storage yard need a fire code permit?

Conditional: in most IFC jurisdictions, yes once the site stores more than 2,500 cu ft of combustible material, more than 100,000 board feet of lumber or more than 2,500 cu ft of scrap tires. The permit list is Section 105.6 in the 2018 IFC used in New Jersey and Philadelphia and Section 105.5 in the 2021 and 2024 editions, while New York State municipalities and the Maryland and Delaware fire marshals apply their own permit programs.

Can pallets be stacked against the warehouse wall?

Conditional: under the 2018, 2021 and 2024 IFC, a pallet pile must be separated from the building by a distance set by the number of pallets, the pallet material and the wall construction (Section 315.7), and the shortest distances apply only to blank masonry walls. Under every edition, nothing may be stored beneath the canopy of a sprinklered building unless sprinklers extend under it (Section 315.4.1).

How high can outdoor storage be piled?

20 ft for general combustible materials, pallets and finished lumber (IFC Sections 315.4.2, 315.7 and 2809.2). Tire piles are limited to 10 ft (Section 3405.1), and lithium-ion battery piles to 10 ft under the 2024 IFC (Section 320.4.3).

Is outdoor storage regulated as high-piled storage?

No. IFC Chapter 32 high-piled combustible storage covers storage inside buildings above 12 ft, or 6 ft for certain high-hazard commodities where the fire code official requires it. Outdoor piles follow Section 315 and the material chapters for lumber, pallets and tires instead.

This article is general information, not a substitute for a site-specific code review. Code editions, local amendments and fire official practice change; confirm the adopted code and the authority having jurisdiction for the site.

Planning an Outdoor Storage Yard?

Send the site plan, what will be stored and how high, and the jurisdiction. DGA checks the piles against the fire code separations, access roads and water supply, and prepares the site plan for the permit. Project briefs get confirmation and preliminary code feedback within one business day.

Send a Project Brief → View Related Services