Free Engineering Tool · NFPA 13 / NFPA 291
Sprinkler Demand vs. Water Supply Analysis
Check a sprinkler system demand against the water supply. Enter the hydrant flow test and the system demand point, add the hose stream allowance, and read the available pressure and the safety margin at the total demand on N1.85 paper.
- Based on NFPA 13 / NFPA 291
- Free, runs in your browser; your inputs stay on your device
- Screening tool, not reviewed or sealed by a licensed engineer
- Last updated October 2026
Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.
Project Information
Water Supply (Flow Test)
System Demand
Supply Check
Supply and Demand Graph
About This Tool
The supply is modeled from the static pressure and the flow test point with the Hazen-Williams relationship P(Q) = PS − (PS − PR) · (Q / QF)1.85, which plots as a straight line on N1.85 paper. The sprinkler demand is plotted as a point, the hose stream allowance is added at the same pressure, and the tool reports two margins: sprinkler only, and sprinkler plus hose.
NFPA 13 does not set a safety margin, but many authorities having jurisdiction require one, so confirm the number that applies to the project before relying on the result.
When to bring in an engineer
A negative or thin margin usually means larger pipe, a different design approach or a fire pump. DGA prepares sealed hydraulic calculations and fire pump designs; the article Do You Need a Fire Pump? explains how the decision is made.
Frequently Asked Questions
Why are water supply curves plotted on N^1.85 paper?
Hazen-Williams friction loss varies with flow raised to the 1.85 power. Stretching the flow axis by that power turns the supply curve into a straight line from the static point through the test point, so it can be drawn and read with a ruler.
Where is the hose stream allowance added?
This tool adds the hose stream allowance to the system flow at the same pressure as the sprinkler demand, so the demand extends horizontally to the total flow. The safety margin is then read at that total flow.
What does a negative safety margin mean?
The supply cannot deliver the demand pressure at that flow. Typical fixes are larger pipe, a lower-demand design or a fire pump, and the choice depends on the building and the water purveyor.
Related Tools and Services
More water supply and hydraulics calculators →
Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.
Related Reading
Articles from DGA Insights on the code and the method behind this calculator.