Free Engineering Tool · NFPA 13
Hazen-Williams Friction Loss Calculator
Friction loss for a pipe run by the Hazen-Williams formula used in NFPA 13. Pick the pipe, material and flow, count the fittings and valves, and get the pressure loss, total equivalent length and velocity in US or SI units.
- Based on NFPA 13
- Free, runs in your browser; your inputs stay on your device
- Screening tool, not reviewed or sealed by a licensed engineer
- Last updated October 2026
Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.
Flow and Pipe
Fittings and Valves
Equivalent lengths from the NFPA 13 table for Schedule 40 steel at C = 120, adjusted for the C-factor and the inside diameter.
| Fitting or valve | Count | Each | Total |
|---|---|---|---|
| 45° elbow | - | - | |
| 90° standard elbow | - | - | |
| 90° long-turn elbow | - | - | |
| Tee or cross, flow turned 90° | - | - | |
| Butterfly valve | - | - | |
| Gate valve | - | - | |
| Swing check valve | - | - | |
| Fittings and valves | - | ||
Leave out the fitting connected directly to a sprinkler and tees or crosses with straight-through flow. Alarm, dry pipe and deluge valves, strainers and backflow preventers go in as the manufacturer’s listed equivalent length.
Result
Friction Loss Against Flow
About This Tool
NFPA 13 calculates pipe friction loss with the Hazen-Williams formula, p = 4.52 · Q1.85 / (C1.85 · d4.87), where p is the loss in psi per foot of pipe, Q the flow in gpm, C the friction loss coefficient and d the actual inside diameter in inches. In SI units the standard gives p = 6.05 × 105 · Q1.85 / (C1.85 · d4.87) in bar per meter, with Q in L/min and d in mm; the calculator uses the form that matches the units selected and reports SI pressures in kPa. The total loss is p times the straight pipe length plus the equivalent length of the fittings and valves.
Fittings and valves come from the NFPA 13 equivalent pipe length chart, which gives each elbow, tee and valve as feet of Schedule 40 steel pipe with C = 120. For other C-factors the chart values are multiplied by 0.713 (C 100), 1.16 (C 130), 1.33 (C 140) or 1.51 (C 150). The loss in a fitting does not change with the pipe’s C-factor, but a foot of rougher pipe loses more, so fewer feet of it represent the same fitting. For pipe with a different inside diameter, such as Schedule 10, the lengths are multiplied by (actual inside diameter / Schedule 40 inside diameter)4.87. Alarm, dry pipe and deluge valves, strainers and backflow preventers have listed values from the manufacturer and go in the other devices field.
The C-factor presets follow NFPA 13: 120 for black or galvanized steel in wet and deluge systems, 100 for the same pipe in dry and preaction systems, 140 for cement-lined ductile iron and 150 for copper, stainless steel and listed plastic. The tool also reports the velocity, 0.4085 · Q / d2 in ft/s, and the velocity pressure, 0.001123 · Q2 / d4 in psi, and flags velocities above 20 ft/s.
Worked example
A dry pipe system (C = 100) carries 250 gpm through 150 ft of 2-1/2 in. Schedule 10 steel with two standard elbows, one tee with the flow turned and one butterfly valve. The chart gives 6 + 6 + 12 + 7 = 31 ft. The C multiplier is 0.713 and the diameter factor is (2.635 / 2.469)4.87 = 1.373, so the fittings count as 30.3 ft and the run as 180.3 ft. The loss is 0.220 psi/ft, or 39.6 psi in total, at 14.7 ft/s. The same run in Schedule 40 pipe would lose 51.9 psi.
Assumptions and limits
Hazen-Williams applies to water near ordinary temperatures in turbulent flow; use Darcy-Weisbach for antifreeze and other fluids. The calculator covers one run of one size and material. Leave out the fitting connected directly to a sprinkler and tees or crosses with straight-through flow, as NFPA 13 does. Where the chart has no value for a fitting at a given size, the tool asks for the listed value. Elevation and velocity pressure changes along the system are not included in the friction loss.
When to bring in an engineer
One pipe run is a check, not a design: a sprinkler system needs every branch line, main and fitting balanced against the water supply. DGA prepares sealed hydraulic calculations and provides third-party review of calculations prepared by others.
References
- NFPA 13, Standard for the Installation of Sprinkler Systems, National Fire Protection Association, 2025 edition, Chapter 28: Hazen-Williams formula, equivalent pipe length chart for valves and fittings, C value multipliers, inside diameter adjustment and C values.
- G.S. Williams and A. Hazen, Hydraulic Tables, 3rd edition, Wiley, New York, 1920.
- ASME B36.10M, Welded and Seamless Wrought Steel Pipe, American Society of Mechanical Engineers: Schedule 40 and Schedule 10 dimensions.
Frequently Asked Questions
What C-factor should I use?
NFPA 13 sets the design C-factor by pipe material and system type: 120 for black or galvanized steel in wet and deluge systems, 100 for the same pipe in dry and preaction systems, 140 for cement-lined ductile iron and 150 for copper, stainless steel and listed plastic pipe. The standard that governs the project takes precedence.
Why do the fitting lengths go down when C is 100?
The equivalent length chart is written in feet of C 120 pipe. A foot of C 100 pipe has more friction, so fewer feet of it produce the same loss as the fitting. NFPA 13 applies a multiplier of 0.713 for C 100 and larger multipliers for smoother pipe.
How do I handle Schedule 10 or other pipe?
Use the actual inside diameter for the pipe friction and multiply the chart lengths by the actual inside diameter divided by the Schedule 40 inside diameter, raised to the 4.87 power. The calculator does both when Schedule 10 or another inside diameter is selected.
Which fittings are left out of the count?
NFPA 13 leaves out the fitting connected directly to a sprinkler and tees or crosses where the flow goes straight through. Count each elbow, each tee or cross where the flow turns, and each valve in the run.
Related Tools and Services
More water supply and hydraulics calculators →
Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.
Related Reading
Articles from DGA Insights on the code and the method behind this calculator.