Free Engineering Tool · NFPA 92

Flame Height Calculator

Mean flame height of a buoyant fire from its heat release rate and burning area, by the Heskestad correlation. The tool also gives the equivalent diameter of a rectangular or irregular fuel area, the NFPA 92 limiting elevation and the virtual origin of the plume, with a drawing to scale.

  • Based on NFPA 92
  • Free, runs in your browser; your inputs stay on your device
  • Screening tool, not reviewed or sealed by a licensed engineer
  • Last updated October 2026

Screening tool, not engineering advice. This calculator estimates results with simplified published methods. It has not been reviewed or sealed by a licensed engineer for your project, and DGA does not warrant that its results are accurate, complete or suitable for any use. Check every result independently and have the licensed professional responsible for your project review it before you rely on it. Use is subject to the Terms of Use.

Advanced method. The correlations behind this tool come from research and test data with narrow ranges of validity. Outside those ranges results can be wrong by a wide margin, and they are no substitute for a fire model or an analysis by a qualified fire protection engineer.

Fire Size and Area

Ambient Air and Fuel

The standard coefficient covers most fuels in air at about 20 °C (68 °F) and sea-level pressure. Switch to the adjusted form for hot or high-altitude locations, or for fuels such as hydrogen whose heat release per unit mass of air differs from the usual 2,900 to 3,200 kJ/kg.

Heat released per unit mass of air is the fuel’s lower heat of combustion divided by its stoichiometric air-to-fuel mass ratio. It is close to 3,000 kJ/kg (1,290 Btu/lb) for most hydrocarbons, wood and plastics.

Result

Mean flame height
0
Equivalent diameter
0
NFPA 92 limiting elevation
0
Virtual origin
0

Flame and Plume to Scale

Keep these results

About This Tool

The mean flame height is the height above the fuel surface at which flames are present half of the time. For buoyant fires such as pool fires, burning furniture, pallet stacks and storage, the Heskestad correlation gives L = 0.235 Q2/5 − 1.02 D, with L and the fire diameter D in meters and the total heat release rate Q in kW. It holds from small pool fires up to large fires, except for high-velocity gas jets, where the momentum of the release controls the flame.

For a fuel area that is not round, D is the equivalent diameter, the diameter of a circle of the same area: D = √(4Af / π). The coefficient 0.235 applies to ordinary fuels in air near 20 °C and sea-level pressure. The adjusted mode computes it as A = 15.6 [cpT∞ / (gρ∞2(Hc/r)3)]1/5, where Hc/r is the heat released per kilogram of air consumed. That quantity is close to 3,000 kJ/kg for most fuels, which is the same observation behind oxygen consumption calorimetry. Hot air and low pressure at altitude make the flames taller.

Two related heights are shown. NFPA 92 uses a limiting elevation zl = 0.166 Qc2/5, based on the convective heat release rate, to decide which plume mass flow equation applies; below it, the plume still contains flame. The virtual origin z0 = 0.083 Q2/5 − 1.02 D is the apparent point source of the plume above the flames, and is negative (below the fuel surface) for low, spread-out fires.

Worked example

A fire of 1,000 Btu/s (1,055 kW) on a 4 ft (1.22 m) circular area has a mean flame height of 8.4 ft, an L/D ratio of 2.1, a limiting elevation of 7.6 ft with a convective fraction of 0.7, and a virtual origin 0.3 ft above the fuel. Spread the same fire over an 8 ft by 6 ft pallet area (equivalent diameter 7.8 ft) and the flames drop to 4.5 ft. Moved to a site near 5,000 ft elevation (24.9 in. Hg) on a 95 °F day, the original fire has a coefficient of 0.260 and a flame height of 9.7 ft.

Assumptions and limits

The fire burns on a horizontal surface in still, uncontaminated air, away from walls. The result is a time-averaged height; individual flame tips reach well above it. When the formula gives zero or a negative height the fire burns as scattered flamelets and the correlation does not apply. Fires much wider than they are tall, and long narrow fuel areas that behave like line fires, are outside most of the test data. Wind, walls and corners lengthen flames, and a hot upper layer changes the flame and plume once the flames reach it.

When to bring in an engineer

Flame height feeds target heating, sprinkler and detector response, smoke production and exposure to structure. DGA prepares fire and smoke modeling and smoke control design where the design fire and its plume set the outcome.

References

  1. NFPA 92, Standard for Smoke Control Systems, National Fire Protection Association, 2024 edition: limiting elevation and mass flow of the axisymmetric plume.
  2. G. Heskestad, “Luminous Heights of Turbulent Diffusion Flames,” Fire Safety Journal, Vol. 5, 1983, pp. 103 to 108.
  3. G. Heskestad, “Virtual Origins of Fire Plumes,” Fire Safety Journal, Vol. 5, 1983, pp. 109 to 114.
  4. C. Huggett, “Estimation of Rate of Heat Release by Means of Oxygen Consumption Measurements,” Fire and Materials, Vol. 4, 1980, pp. 61 to 65.
  5. U.S. Nuclear Regulatory Commission, Fire Dynamics Tools (FDTs): Quantitative Fire Hazard Analysis Methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program, NUREG-1805, 2004, Chapter 3 (flame height of pool fires).

Frequently Asked Questions

What is the mean flame height of a fire?

It is the height above the burning surface at which flames are present 50 percent of the time. It is measured by averaging many video frames or by eye, and it is the value the Heskestad correlation predicts. The tallest flame tips reach higher than the mean height, and the steady, continuous flame is lower.

How do I handle a rectangular or irregular fuel area?

Use the equivalent diameter, the diameter of a circle with the same plan area. This works well for roughly square or round fuel areas. When the length is more than about three times the width, the fire behaves more like a line fire and the equivalent diameter can misstate the flame height.

Why can the calculator show no flame height?

For a low heat release rate spread over a large area the correlation returns zero or a negative number. Physically the fire then burns as many small flamelets near the fuel surface rather than as one flame, and the correlation does not apply.

What is the NFPA 92 limiting elevation?

It is the height, based on the convective heat release rate, below which the plume is considered to contain flame. NFPA 92 uses it to choose between the plume mass flow equation for heights within the flames and the one for heights above them.

Related Tools and Services

More fire dynamics and detection calculators

Engineering aid only, provided as is and without warranty. Results depend on the inputs and on the simplifying assumptions of the method summarized on each tool page, and DGA has not verified them for your application. They do not replace code-required design, testing or review by the licensed engineer responsible for the project. Use of the tools is subject to the Terms of Use.

Related Reading

Articles from DGA Insights on the code and the method behind this calculator.

Quick inquiry

Need these results reviewed for a submittal?

Your name, a way to reach you, and where the project is. One of our licensed PEs replies within one business day. Every inquiry is confidential.