Storage and Commodities · Definition

What Is Encapsulation in Storage Sprinkler Design?

Reviewed by a licensed Professional Engineer · NY, NJ, PA, MD, DE · Last reviewed · Code basis: NFPA 13 (2016 NYC Appendix Q, 2019, 2022, 2025) Ch. 3, 20, 21, 22, 23; 2021 IFC 3201.3; 2024 IFC (NYS) Ch. 32; 2018 IFC (NJ UFC) Ch. 32; 2021 IBC 413.1; NFPA 1 (2024) Ch. 34

General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.

Encapsulation, in NFPA 13 (the National Fire Protection Association’s Standard for the Installation of Sprinkler Systems), means a pallet load of combustible goods packaged so that plastic sheeting covers its whole top and every one of its sides. Stretch wrap around the sides alone does not qualify, and neither does a top cover with openings over more than half its area. Encapsulation matters because the plastic sheds sprinkler water off the load, so the control mode density/area criteria in NFPA 13 ask for more ceiling protection for encapsulated Class I to IV commodities than for the same goods left open to the spray.

Encapsulation is a packaging condition, not a commodity class. A pallet of Class II goods stays Class II when it is wrapped; what changes is the design entry the sprinkler designer reads in the storage criteria. This article explains what counts as encapsulated, where the code defines the term, why encapsulation changes the ceiling sprinkler design and how an owner checks for it on a walk-through.

At a Glance: Encapsulated Storage

  • Definition: a pallet load of combustible commodities enclosed on the top and all sides by plastic sheeting, or combustible items individually wrapped in plastic and stacked exposed on the pallet.
  • Governing code and section: NFPA 13 Chapter 3 (the definition, Section 3.3.68 in 2022, and its Annex A explanation), applied through the storage criteria in Chapter 21 for control mode density/area (CMDA) sprinklers, Chapter 22 for control mode specific application (CMSA) sprinklers and Chapter 23 for early suppression fast response (ESFR) sprinklers. The 2021 International Fire Code (IFC) Section 3201.3 requires high-piled storage construction documents to show where banded or encapsulated commodities are stored.
  • Who prepares it or who it applies to: owners and operators of warehouses, distribution centers and stockrooms whose palletized or rack storage falls under the NFPA 13 storage chapters; the sprinkler designer and the fire protection engineer apply it to the design.
  • When it’s required: the design has to account for encapsulation whenever wrapped loads are stored under the sprinklers, and the packaging has to be checked again at every tenant, supplier or storage height change.
  • Typical output: an encapsulated or nonencapsulated entry for each commodity and storage area on the high-piled storage plan and in the sprinkler design basis.
  • Often confused with: banding (stretch wrap on the sides only) and cartoned plastics, which is a packaging category in the commodity classification, not encapsulation.

What Counts as Encapsulated Storage?

The encapsulation test looks only at the outside of the pallet load: whether plastic closes off the top and every side. The table sorts the packaging found in most warehouses, with the reason each one does or does not meet the NFPA 13 definition.

Packaging conditionEncapsulated?Reason
Shrink hood or plastic sheet over the top and down all 4 sidesYesPlastic closes the top and every side, which is the core of the Chapter 3 definition.
Stretch wrap on the sides plus a plastic top sheet held under the wrapYesThe wrap closes the sides and the sheet closes the top, so the load is enclosed even though 2 materials do the work.
Stretch wrap around the sides only, top openNoSide-only wrapping is banding, which the Annex A explanation excludes from the term.
Plastic top sheet or cap only, sides open or paper-wrappedNoThe definition needs the sides enclosed in plastic as well as the top.
Top cover with holes, vents or pick cut-outs over half its areaNoThe annex drops the term once the openings in the top cover exceed half of the cover’s area.
Cartons with a plastic or waterproof top coverConditionalAn intact waterproof top counts toward encapsulation if openings stay at or under half its area; the sides still have to be enclosed.
Bags: combustible items individually wrapped or bagged in plastic and stacked exposed on the palletYesThe definition extends to plastic-wrapped items stored exposed in the pallet load, even with no outer wrap. The bag material also counts in the commodity class.
Plastic-bagged items inside a closed carton, crate or other large container that is not plasticNoThe annex excludes plastic-enclosed goods held inside a large enclosed container made of another material.
Noncombustible goods on wood pallets under a plastic sheetNoThe definition covers combustible commodities; the pallet and the sheet are handled in the commodity classification instead.

The reason the test stops at the outside of the load is water. A ceiling sprinkler can wet a corrugated carton, and wet cardboard burns slowly; a sprinkler cannot wet cardboard that sits under a plastic sheet. The definition therefore asks only whether plastic closes off the top and every side, not how thick the film is.

Figure 1: Where the Plastic Has to Be

ENCAPSULATED BANDED: NOT ENCAPSULATED Plastic on the top and all 4 sides Spray runs off; cartons below stay dry Stretch wrap on the sides, top open Spray lands on and wets the carton tops A top cover with openings over half its area does not count as encapsulation.
Under the NFPA 13 Chapter 3 definition, a pallet load of combustible goods is encapsulated only when plastic closes the top and all 4 sides. Stretch wrap on the sides alone is banding, and a top cover with openings over half its area also falls outside the term.

Where the Code Defines Encapsulation

NFPA 13 defines encapsulation in Chapter 3, its definitions chapter, as a packaging method in which plastic sheeting wraps the whole top and every side of a pallet load holding combustible goods. The same definition extends the term to combustible items that are each wrapped in plastic and stored exposed on the pallet. The Annex A explanation that goes with the definition lists the exclusions: side-only stretch wrap (banding), loads of entirely noncombustible goods, top covers with openings over half their area, and plastic-wrapped goods inside a large enclosed container that is not plastic.

Encapsulation does not change the commodity class. NFPA 13 Chapter 20 classifies the product, its packaging and the pallet as Class I to IV or as a Group A, B or C plastic, and DGA’s guide to commodity classification under NFPA 13 covers that step. The protection criteria in Chapters 21 to 23 then ask a second question, whether the load is encapsulated, and set the design from both answers.

The fire codes do not write their own encapsulation design rules; they send the sprinkler design to NFPA 13. The 2021 IFC, Section 3201.3, lists the location of banded or encapsulated commodities among the items a high-piled storage submittal must show, next to the commodity classification and the storage heights. The Fire Code of New York State and the New Jersey Uniform Fire Code carry the same high-piled storage chapter, Chapter 32, and NFPA 1, the Fire Code used in Maryland and Delaware, covers high-piled storage in Chapter 34.

Why Encapsulation Changes the Ceiling Sprinkler Design

Ceiling sprinklers control a storage fire partly by wetting the cartons around the fire before the flames reach them. Plastic sheeting defeats that: water runs off the top sheet and down the side film, the cardboard underneath stays dry, and fire can spread inside the wrap where the spray cannot reach. The NFPA 13 storage criteria grew out of full-scale fire tests, and encapsulated loads in those tests needed more water than the same goods left open.

A common belief on warehouse floors is that wrapping protects the load. Shrink hoods and top sheets do keep product dry in a roof leak or a small sprinkler discharge. In a fire, the same plastic keeps sprinkler water off the cardboard that would otherwise slow the spread.

In the CMDA criteria of NFPA 13 Chapter 21, encapsulation is one of the inputs that selects the design. For rack storage of Class I to IV commodities, the encapsulated entries call for a higher ceiling density than nonencapsulated storage at the same height and aisle width, and the size of the increase depends on the commodity class and the storage height. In the 2022 edition, racks up to 25 ft take a 25 percent density increase for encapsulated Class I to III and 50 percent for encapsulated Class IV (Sections 21.4.1.6.1 and 21.4.1.6.2), and racks over 25 ft take 25 percent (Section 21.4.2.2). For palletized and solid-piled storage, the Chapter 21 criteria cover encapsulated loads only to 15 ft, or to 20 ft for solid-piled and palletized storage with K-11.2 or larger sprinklers (Section 21.2.3.1), against 30 ft for open loads, so wrapping alone can push an existing system past its limit with no change in commodity.

CMSA sprinklers, covered in NFPA 13 Chapter 22, have no density to adjust. Each CMSA table entry names a sprinkler, a pressure and a number of design sprinklers for a stated commodity and storage arrangement. The CMSA tables make no distinction between encapsulated and nonencapsulated loads, so wrapping alone does not change a CMSA design. The commodity, storage height and ceiling height still have to fit the entry used.

ESFR sprinklers in NFPA 13 Chapter 23 are tested to suppress a fire, not only to control it, and the Class I to IV entries in the ESFR criteria apply to encapsulated and nonencapsulated loads alike. That is one reason warehouses holding a lot of wrapped product lean toward ESFR, and DGA’s comparison of ESFR and CMSA sprinklers for warehouses covers the other trade-offs. Encapsulation still has to be recorded under ESFR, because the design does not stretch to commodities, heights or arrangements outside the table entry used.

Opens the Project Desk with your sentence. Our licensed PEs review every brief and reply within one business day.

How Encapsulation Differs From Banding and Cartoning

Three packaging words get mixed up on storage plans. Banding is stretch wrap around the sides of a pallet load to hold it together in transit, and NFPA 13 does not treat banding as encapsulation because the top stays open to the spray. Encapsulation adds plastic over the top, so the whole load is closed off.

Cartoned is a separate idea from encapsulated. In the NFPA 13 commodity classification, a cartoned Group A plastic is one packed in corrugated cartons, which lowers the hazard compared with exposed plastic. For Group A plastics, the protection criteria key on cartoned or exposed and on expanded or nonexpanded, while encapsulation is the condition that raises the demand for Class I to IV goods. Encapsulation does not change the Group A design: NFPA 13 counts encapsulated plastic as exposed Group A, and the plastics decision tree in Chapter 21 does not use encapsulation as a factor.

Figure 2: Encapsulated or Not: Common Packaging

Encapsulated (higher CMDA demand for Class I to IV)
  • Shrink hood over the top and all 4 sides
  • Stretch wrap on the sides plus a plastic top sheet under the wrap
  • Stretch hood film that closes over the top of the load
  • Items in plastic bags stacked exposed on the pallet
  • Cartons with an intact waterproof top cover inside full side wrap
Not encapsulated
  • Stretch wrap around the sides only (banding)
  • Plastic top cap with open or paper-wrapped sides
  • Top sheet cut open for picking over more than half its area
  • Plastic-bagged items inside a closed carton or crate
  • Noncombustible goods on a wood pallet under plastic
A load is encapsulated when plastic closes the top and every side, including individually bagged items stacked exposed on the pallet. Side-only stretch wrap, a top cover more than half open and plastic-bagged goods inside a closed nonplastic container all fall outside the NFPA 13 term.

How to Check a Warehouse for Encapsulated Storage

An owner or facility manager can find most encapsulated storage with a walk of the receiving dock and the storage aisles. The encapsulation check is visual: look at the top of each load, then at its sides, and note where that load sits in the building.

  1. Start at receiving. Note which suppliers ship shrink-hooded or top-sheeted pallets, and whether the dock removes the wrap before putaway. Wrap taken off at the dock does not count in the racks.
  2. Look at the tops of stored loads. A plastic sheet, cap or hood across the top is the first sign. Loads above about 15 ft may need a lift or a pole camera to see.
  3. Check the sides. Film around all 4 sides plus a covered top is encapsulated; side wrap with an open top is banding.
  4. Check for openings. A top sheet cut open over more than half its area for case picking no longer counts, so pick faces and reserve locations can differ.
  5. Look for bags. Product in plastic bags stacked exposed on the pallet counts as encapsulated even with no outer wrap.
  6. Record the result. Note encapsulated loads by area, rack bay and storage height, and compare them with the hydraulic design information sign at the riser and the approved high-piled storage plan.

Seasonal stock and new suppliers change the encapsulation picture more often than the racks change. A building checked in spring can hold shrink-hooded holiday goods by fall, so the walk-through belongs in the annual review of the high-piled storage plan and in any evaluation of a new tenant’s storage.

When Encapsulation Matters for a Project

Encapsulation becomes a design question whenever storage falls under the NFPA 13 storage chapters, which for Class I to IV commodities means storage over 12 ft (NFPA 13 (2022) Section 4.3.1.5 keeps storage up to 12 ft in Chapter 4 as low-piled), and whenever the fire code’s high-piled storage rules apply. The usual triggers are a new building or tenant, a change of supplier or packaging, a higher storage height, and a fire official or insurer visit that finds wrapped loads the design never assumed.

Storage height and encapsulation are checked together, because each one moves the ceiling demand. DGA’s article on how high goods can be stored under ceiling-only sprinklers covers the height side of that check.

Which NFPA 13 Edition Applies in Each State?

The NFPA 13 definition of encapsulation reads essentially the same in every edition adopted across the region, so the walk-through check does not change from state to state. What changes is the edition, chapter and table the designer reads, and the official who reviews the storage plan. The table lists each jurisdiction’s NFPA 13 edition, the fire code chapter that governs high-piled storage and the reviewer, as of October 2026.

JurisdictionNFPA 13 editionFire code storage chapterReviewer
New York State (outside NYC)2022, through the 2025 Uniform Code (2024 I-Codes)Fire Code of New York State (2024 IFC basis), Chapter 32Local code enforcement official
New York City2016, as modified by Appendix Q of the 2022 NYC Building Code2022 NYC Fire Code, Chapter 32Department of Buildings (DOB) for the sprinkler filing; Fire Department of the City of New York (FDNY) for high-piled storage
New Jersey2022, through the Uniform Construction Code (UCC) on the 2024 I-Codes since August 17, 2026Uniform Fire Code (2018 IFC basis), Chapter 32Fire protection subcode official (UCC); local fire official (Uniform Fire Code)
Pennsylvania2019, through the UCC on the 2021 I-CodesNo statewide fire code; 2021 International Building Code (IBC) Section 413.1 sends high-piled storage to IFC Chapter 32 at permitMunicipal or third-party code official; Philadelphia Department of Licenses and Inspections (L&I) in the city
Maryland2019, through the 2021 IBC county permit path; NFPA 1 (2024) references the 2022 editionNFPA 1 (2024), Chapter 34, under the State Fire Prevention CodeCounty building official; State Fire Marshal or local fire marshal
Delaware2025, through Regulation 701 (2026)NFPA 1 (2024), Chapter 34Office of the State Fire Marshal (Wilmington Fire Marshal inside the city)

Adoptions as of October 2026. DGA’s Fire Code Cheat Sheet for NY, NJ, PA, MD and DE lists the base codes by state. Local amendments are not shown.

Key Takeaway: Encapsulation means plastic on the top and all 4 sides of a pallet load of combustible goods, or goods individually wrapped in plastic and stacked exposed. Side-only stretch wrap is banding and does not count. Encapsulation leaves the commodity class unchanged but raises the CMDA ceiling demand for Class I to IV storage, so an owner should check the tops of the loads, record where wrapped goods sit and compare that with the sprinkler design basis.

Frequently Asked Questions

Does stretch wrap count as encapsulation?

No. Stretch wrap around the sides of a pallet load with the top left open is banding, which NFPA 13 excludes from the term. The load becomes encapsulated when a plastic top sheet, cap or hood closes the top as well.

Does encapsulation change the commodity class?

No. NFPA 13 Chapter 20 classifies the product, packaging and pallet; encapsulation is a separate condition in the protection criteria. A Class III load stays Class III when wrapped, but the CMDA design for it may need a higher density.

Do ESFR sprinklers need a different design for encapsulated loads?

Conditional: for Class I to IV commodities, the ESFR criteria in NFPA 13 Chapter 23 apply the same entries to encapsulated and nonencapsulated loads, so the wrap alone does not change the design. The commodity class, storage height, ceiling height and arrangement still have to fall within the entry used.

Is a pallet with a plastic top sheet but no side wrap encapsulated?

No. The definition requires plastic on the top and on every side. A top sheet alone, or a top sheet over paper-wrapped sides, leaves the load nonencapsulated.

Do high-piled storage plans have to show encapsulated storage?

Yes. The 2021 IFC, Section 3201.3, lists the location of banded or encapsulated commodities among the items high-piled storage construction documents must show. The same information sets which NFPA 13 design entry the sprinkler system has to meet.

This article is general information, not a substitute for a project-specific code analysis. Code editions, local amendments and reviewer practice change; confirm the adopted code and the authority having jurisdiction for each project.

Wrapped Pallets Under an Older Sprinkler Design?

Send the storage layout, photos of the packaging and the sprinkler design basis. DGA checks whether the stored loads are encapsulated, compares them with the NFPA 13 criteria the system was designed to, and lists the options if they do not match. Project briefs get confirmation and preliminary code feedback within one business day.