Storage and Commodities · Trigger

What Does the Fire Code Require for Records Storage?

Reviewed by a licensed Professional Engineer · NY, NJ, PA, MD, DE · Last reviewed · Code basis: NFPA 13 (2016 NYC App. Q; 2019 PA, MD; 2022 NYS, NJ; 2025 DE) Ch. 4, 9, 20, 21, 24, 26; IFC Ch. 2 and 32 (2021; 2024 NYS; 2018 NJ UFC; 2022 NYC FC); IBC 311.2 and 903.2.9 (2021; 2024 NYS, NJ); NFPA 1 (2024) Ch. 34 (MD, DE); NFPA 232 (2022); 36 CFR 1234.12

General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.

A records storage warehouse almost always needs automatic sprinklers designed under National Fire Protection Association (NFPA) 13 for cartoned paper records, which are a Class III commodity, and it falls under the high-piled storage rules of International Fire Code (IFC) Chapter 32 once the top of the records is more than 12 ft above the floor. Under the International Building Code (IBC), a records center is a Group S-1 storage occupancy that must be sprinklered throughout once a fire area exceeds 12,000 sq ft, a line nearly every records warehouse crosses.

Records storage also has design criteria of its own. NFPA 13 has criteria written for cartoned records on multilevel shelving with catwalk access and for compact mobile shelving of paper files up to 8 ft high, and NFPA 232, Standard for the Protection of Records, governs records an owner is required to protect. The sections below set out the thresholds, how they are measured, the alternatives and what applies once a records building crosses them.

At a Glance: Records Storage and the Fire Code

  • Thresholds: top of storage over 12 ft for cartoned paper records, or over 6 ft for records in Group A plastic totes where the fire code official applies the high-hazard line; a high-piled storage area over 500 sq ft for the operational permit; a Group S-1 fire area over 12,000 sq ft, or all S-1 fire areas combined over 24,000 sq ft, for sprinklers throughout; compact mobile shelving criteria limited to 8 ft and 5 percent plastics.
  • Code, edition, section: 2021 IFC Chapter 2 definitions and Sections 3203.4, 3207.2.1 and 3210.1; 2021 IBC Sections 311.2 and 903.2.9; NFPA 13 (2022) Chapters 20, 21 and 26; NFPA 232 (2022). Editions by state are in the jurisdiction table.
  • Main exceptions: storage held at 12 ft or less, which NFPA 13 protects as an occupancy hazard rather than as high-piled storage; a high-piled area of 500 sq ft or less, which needs no IFC operational permit; an S-1 fire area of 12,000 sq ft or less with no other sprinkler trigger.
  • What applies once triggered: the IFC Chapter 32 features that Table 3206.2 assigns to Class III storage, a high-piled storage plan, an NFPA 13 design matched to the arrangement (the cartoned records criteria, the compact storage criteria or the general shelf and rack criteria), sprinklers under catwalks and solid shelves, and NFPA 232 where records protection is required.
  • Permit or filing: a sprinkler permit through the building department, and a high-piled storage operational permit where the fire code requires one, issued in New York City by the Fire Department of the City of New York (FDNY); New Jersey approves the storage through the construction permit instead.
  • Who decides: the fire code official decides whether the storage is high-piled and how its height is measured; the building official sets the occupancy and the sprinkler requirement; the fire protection engineer sets the NFPA 13 design basis; the records owner or a regulator decides whether NFPA 232 applies.

What Thresholds Apply to a Records Storage Building?

Records storage meets nine thresholds drawn from three documents: the fire code for the storage, the building code for the occupancy and NFPA 13 for the sprinkler design. The table gives each threshold with its number and its section in the 2021 IFC, the 2021 IBC and the 2022 edition of NFPA 13. The jurisdiction table further down gives the edition each state enforces.

ThresholdNumberWhat it decidesCode and section
Storage height, cartoned paper recordsTop of storage over 12 ftThe records are high-piled combustible storage; records on racks or shelves over 12 ft follow the general and rack storage sections of Chapter 322021 IFC Chapter 2, definition of high-piled combustible storage; Section 3210.1
Storage height, high-hazard commoditiesTop of storage over 6 ftRecords in Group A plastic totes can be high-piled at the lower line where the fire code official requires it2021 IFC Chapter 2, same definition
High-piled storage areaOver 500 sq ftOperational permit; the larger area bands of Table 3206.2 begin above 500 sq ft2021 IFC Section 105.5; Table 3206.2
Shelf depth and spacingShelves less than 30 in. deep and not more than 3 ft apart verticallyShelving inside these limits is shelf storage; deeper or more widely spaced shelving is rack storage2021 IFC Chapter 2, definition of shelf storage
Shelf storage heightOver 12 ft and under 15 ft; 15 ft or moreNFPA 13 protection below 15 ft; special protection such as in-rack sprinklers at 15 ft or more2021 IFC Section 3207.2.1
Group S-1 fire areaOver 12,000 sq ft; more than 3 stories above grade plane; all S-1 fire areas combined over 24,000 sq ftAutomatic sprinklers throughout the building2021 IBC Section 903.2.9
NFPA 13 storage designClass III storage over 12 ftThe NFPA 13 storage criteria replace the occupancy hazard criteriaNFPA 13 (2022) Chapters 4 and 20
Compact mobile shelvingUp to 8 ft high, 5 percent plastics or lessThe compact storage criteria for paper files, books and similar documents apply; above either limit they do notNFPA 13 (2022) Section 26.7
Solid shelves in racksOver 20 sq ftIn-rack sprinklers below the shelvesNFPA 13 (2022) Chapter 20

The first six rows decide whether the codes reach the building at all, and multilevel records shelving with catwalks routinely crosses the height, area and fire area lines. The last three rows decide which NFPA 13 criteria the sprinkler design uses, and the decision tree further down sorts the arrangements.

How Are Cartoned Paper Records Classified?

NFPA 13 Chapter 20 classifies a commodity by everything that burns: the product, its packaging and the pallet or container under it. Paper records in corrugated cardboard cartons are a Class III commodity, the class NFPA 13 uses for products of wood, paper and natural fiber with or without cartons. The 2021 IFC uses the same class in Section 3203.4, so the fire code and the sprinkler standard start from the same answer.

The class changes when plastic enters the package. Records in plastic boxes or totes, files in plastic binders and stored media such as tapes and discs are classified by their plastic content under the mixed-commodity rules in NFPA 13 Chapter 20, which can move the load to Class IV or to Group A plastics. Empty totes kept in a records building are a plastic commodity in their own right, and open-top totes on racks bring the NFPA 13 open-top container rules with them.

DGA’s article on how commodity classification works under NFPA 13 walks through the class definitions and the plastic percentages. For records storage the practical point is narrow: the special records criteria in NFPA 13 were written for paper in corrugated cartons, and a records program that moves to plastic totes has left them.

How Is Storage Height Measured in a Records Center?

Records storage height is measured from the main floor to the top of the highest carton, not from each catwalk. Multilevel records shelving is one structure: the shelving uprights run through every catwalk level, and open-grated catwalks let heat and burning debris pass between tiers. Three tiers of shelving served by catwalks therefore form one array for both the fire code and NFPA 13.

A records center with catwalks at 8 ft and 16 ft and cartons to 24 ft has 24 ft of storage, twice the 12 ft line. The ceiling sprinklers see that whole array, and the catwalks need sprinklers of their own: the cartoned records criteria place sprinklers beneath each catwalk level, and NFPA 13 (2022) Section 9.5.5.3 separately requires sprinklers below any fixed obstruction wider than 4 ft.

Clearance is measured the same way as in any warehouse, from the top of the highest carton to the deflectors of the ceiling sprinklers, and standard spray sprinklers need at least 18 in. DGA’s guide to how high storage can go under ceiling-only sprinklers explains how the ceiling height and the sprinkler type cap the array.

Figure 1: Where Sprinklers Go in Catwalk Records Shelving

Ceiling sprinklers: designed for the full 24 ft array 12 ft above the main floor: IFC high-piled line Clearance to deflectors: 18 in. minimum, standard spray Storage height: 24 ft, measured from the main floor Catwalk level at 16 ft Sprinklers beneath the catwalk Catwalk level at 8 ft Sprinklers beneath the catwalk One array: open-grated catwalks at 8 ft and 16 ft, cartons to 24 ft, measured from the main floor. Above 12 ft the records are high-piled; sprinklers go at the ceiling and beneath every catwalk level. Cartoned paper records, Class III Sprinkler Example: 3 tiers in 2 aisles
Multilevel records shelving is one storage array measured from the main floor to the top of the highest carton, so catwalks at 8 ft and 16 ft with cartons to 24 ft make 24 ft of Class III storage, twice the 12 ft high-piled line in the 2021 IFC. The NFPA 13 cartoned records criteria design the ceiling sprinklers for that full height and add sprinklers beneath each catwalk level, with at least 18 in. of clearance below standard spray ceiling sprinklers.

Which NFPA 13 Criteria Apply to Shelving, Mobile Shelving, Racks and Plastic Boxes?

NFPA 13 offers a records building four routes, and the storage arrangement on the floor picks the route. DGA’s comparison of rack, palletized and shelf storage under NFPA 13 covers the general arrangements; the records-specific routes follow.

Cartoned records on shelving with catwalk access. NFPA 13 has control mode density/area (CMDA) criteria written for cartoned records storage on multilevel shelving reached by catwalks, in Section 26.6 of the 2022 edition. The criteria pair ceiling sprinklers designed for the full height of the array with sprinklers at each catwalk level, catwalks no more than 12 ft apart vertically, shelving at least 50 percent open and 6 in. transverse flues at each upright, and they apply only when the commodity is paper records in corrugated cartons and the shelving, catwalks and aisles match the arrangement the criteria describe. New York City applies the corresponding provisions of NFPA 13 (2016) as modified by Appendix Q of the 2022 NYC Building Code.

Compact mobile shelving. High-density mobile shelving rolls the units together on rails and opens one aisle at a time, so a fire inside a closed bank is shielded from the ceiling sprinklers. NFPA 13 (2022) Section 26.7 covers compact storage of paper files, magazines, books and similar documents in folders, with no more than 5 percent plastics, up to 8 ft high, and protects it as light hazard. Compact shelving taller than 8 ft, or holding plastic media, is outside those criteria and needs an engineered design accepted by the authority having jurisdiction (AHJ).

Records on racks. Cartoned records on pallet racks, or on shelving deeper than 30 in., are Class III rack storage under the general CMDA, control mode specific application (CMSA) or early suppression fast response (ESFR) criteria in NFPA 13 Chapters 21 to 23. High bay records storage has its own criteria in NFPA 13 (2022) Section 26.8. Solid shelves over 20 sq ft need in-rack sprinklers under NFPA 13 Chapter 20, and 2021 IFC Section 3208.2.2 sends racks of paper records with solid shelving to NFPA 13 for their protection. DGA’s article on why solid shelves in racks change the sprinkler design covers the shelf-area limits and the in-rack levels.

Records in plastic boxes or totes. A records program that moves to plastic totes leaves the cartoned records criteria behind. The design is then built for the class the totes produce, usually Class IV or Group A plastics, under the general storage chapters, and at Group A the 6 ft high-piled line in the IFC can apply.

Figure 2: Which NFPA 13 Criteria Fit the Records?

Records stored in a warehouse, records center or file room
Are the records paper, in corrugated cartons or folders, with 5 percent plastics or less?
Yes: paper records, Class III
Fixed shelving with catwalk accessCartoned records criteriaNFPA 13 (2022) Section 26.6: ceiling sprinklers for the full height, sprinklers beneath each catwalk level
Compact mobile shelving up to 8 ftCompact storage criteriaNFPA 13 (2022) Section 26.7: paper files, books and documents in folders
Racks, deep shelving or mobile units over 8 ftGeneral criteria or engineered designNFPA 13 Chapters 21 to 24; in-rack sprinklers under solid shelves over 20 sq ft
No: plastic boxes, totes or mediaReclassify the loadClass IV or Group A plastics under NFPA 13 Chapter 20; the 6 ft IFC line can apply
NFPA 13 gives records storage four routes: the cartoned records criteria for paper in corrugated cartons on shelving with catwalk access, the compact storage criteria for mobile shelving up to 8 ft with 5 percent plastics or less, the general shelf and rack criteria or an engineered design for other arrangements, and a reclassification to Class IV or Group A plastics once records move into plastic boxes or totes.

Red flag: a switch from cardboard cartons to plastic totes changes the commodity class without moving a single shelf. A records center that makes the switch has left the criteria its sprinklers were designed to, and the hydraulic design information sign at the riser will no longer match the storage.

Opens the Project Desk with your sentence. Our licensed PEs review every brief and reply within one business day.

What Exceptions and Alternatives Apply to Records Storage?

Records storage has five ways to stay under a threshold or to meet it another way, and each one changes an input rather than the definition. The table lists them with the point where each stops working.

AlternativeHow it worksWhere it stops working
Keep storage at 12 ft or lessThe records are not high-piled, and NFPA 13 protects them as an occupancy hazard; the Ordinary Hazard Group 2 definition in NFPA 13 Chapter 4 caps stockpiles of moderate heat release at 12 ftCatwalk shelving exists to use the building’s height, and the limit is enforced to the top of the carton, not the shelf
Hold the high-piled area to 500 sq ft or lessNo IFC operational permit, and the smallest Table 3206.2 bandRecords on open catwalk levels count with the storage below them
Keep each S-1 fire area at 12,000 sq ft or lessNo IBC Section 903.2.9 trigger by fire areaAll S-1 fire areas combined over 24,000 sq ft, or a fire area more than 3 stories above grade plane, still triggers sprinklers, and IFC Chapter 32 can require them anyway
Fire-rated vaults and file roomsNFPA 232 construction and equipment for the records that matter most, inside a sprinklered buildingA vault or file room protects its contents; it does not replace sprinklers in the storage areas
Engineered alternative designNFPA 13 Chapter 24 alternative designs, full-scale fire test data or insurer criteria, approved by the AHJ under the alternative methods section of IFC Chapter 1Needs test data that matches the arrangement, and review takes longer

The 12 ft limit is the alternative records operators reach for first and the one they lose first, because a records center earns its keep by storing upward. In practice the question is rarely whether to sprinkler a records center but which NFPA 13 criteria the sprinklers follow, and the arrangement chosen at layout fixes that answer for the life of the shelving.

What Applies Once a Records Building Is Triggered?

Once storage passes 12 ft, IFC Chapter 32 applies to the high-piled storage area. Table 3206.2 sets the building features for Class III storage by area band: automatic sprinklers, fire detection or building access in some bands, fire department access doors, smoke and heat removal in larger areas, and the aisle and pile limits of Section 3206. Section 3210.1 adds that records on racks or shelves over 12 ft follow the general and rack storage sections, so tall records shelving is held to the rack rules for aisles and flue spaces.

The fire code official also expects a high-piled storage plan under 2021 IFC Section 3201.3 that shows the shelving layout, each catwalk level, the commodity, the storage height and the sprinkler design criteria. The building official applies IBC Section 903.2.9 to the Group S-1 occupancy, and records storage fits the S-1 list in IBC Section 311.2, which names books and paper in rolls or packs.

On the sprinkler side, the hydraulic calculation has to account for the ceiling sprinklers and the sprinklers beneath the catwalks as the records criteria direct, so the water supply and any fire pump are sized for that combined system. The hydraulic design information sign records the criteria used, and any later change in container, shelving height or catwalk layout is a change to the design basis. The industrial and high-hazard sector page describes how DGA handles warehouse sprinkler and storage approvals across the region.

Where Does NFPA 232 Come In?

NFPA 232, Standard for the Protection of Records (2022 edition), protects the records themselves rather than the building. NFPA 232 covers records vaults (Chapter 6), archives (Chapter 7), file rooms (Chapter 8) and records centers (Chapter 9), and the records protection equipment inside them, such as fire-rated safes and file containers, and it starts from an evaluation of how valuable the records are and how much loss the owner can accept.

NFPA 232 is not the sprinkler trigger. The sprinkler requirement and the sprinkler design still come from the building code and NFPA 13; NFPA 232 applies when a regulation, a contract, an insurer, the AHJ or the records owner’s own program calls for it, and it then adds construction, separation and equipment requirements around the most important records.

Records centers that store federal records add a third layer. The National Archives and Records Administration (NARA) facility standards in Title 36 of the Code of Federal Regulations (CFR), Part 1234, set fire-safety requirements for those facilities in Section 1234.12, and the operator meets them in addition to the local code.

Which Codes Apply to Records Storage in Each State?

The 12 ft line and the Class III classification hold across the region. What changes is the fire code that carries the storage rules, the building code edition behind the S-1 sprinkler trigger and the NFPA 13 edition for the design, and the table lists each as adopted in October 2026.

JurisdictionStorage rulesS-1 sprinkler triggerNFPA 13 editionAHJ and filing
New York State (outside NYC)2025 Fire Code of New York State (2024 IFC basis), Chapter 322025 Building Code of New York State (2024 IBC basis), Section 903.2.92022Local code enforcement official; building permit with sprinkler plans; operating permit where the local program requires one
New York City2022 NYC Fire Code, Chapter 322022 NYC Building Code Section 903.2.92016, as modified by Appendix Q of the 2022 NYC Building CodeDepartment of Buildings (DOB) sprinkler filing; FDNY permit for high-piled storage over 500 sq ft
New JerseyUniform Fire Code (UFC) on a 2018 IFC basis, Chapter 32Uniform Construction Code (UCC), 2024 IBC Section 903.2.9, effective Aug 17, 20262022Construction official and fire protection subcode official on the UCC permit; no standalone high-piled storage permit; the local fire official enforces Chapter 32
PennsylvaniaNo statewide fire code; municipal fire codes where adopted, such as the Philadelphia Fire CodeUCC, 2021 IBC Section 903.2.9, effective Jan 1, 20262019Municipal or third-party code official, or the Department of Labor & Industry (L&I) where it has jurisdiction
MarylandState Fire Prevention Code, NFPA 1 (2024) Chapter 342021 IBC Section 903.2.9 through the county building code2019 through the 2021 IBC; NFPA 1 (2024) references the 2022 editionCounty building official; State or local fire marshal plan review
DelawareRegulation 701 (2026), NFPA 1 (2024) Chapter 34IBC by county (2021 in New Castle and Sussex, 2018 in Kent and Wilmington), Section 903.2.92025Office of the State Fire Marshal plan review before the county building permit

Editions as listed in DGA’s Fire Code Cheat Sheet for NY, NJ, PA, MD and DE. Section numbers in the 2018 IFC basis used in New Jersey, the 2024 IFC basis used in New York State and the NYC Fire Code can differ from the 2021 IFC numbers cited above, and Maryland and Delaware apply NFPA 1 Chapter 34 instead of IFC Chapter 32. Local amendments are not shown.

Key Takeaway: Cartoned paper records are a Class III commodity, and a records building becomes high-piled storage under IFC Chapter 32 when the top of the records passes 12 ft, measured from the main floor through every catwalk level. A records center is also a Group S-1 occupancy that needs sprinklers throughout above a 12,000 sq ft fire area. The arrangement then picks the NFPA 13 criteria: cartoned records criteria for shelving with catwalks, compact storage criteria for mobile shelving up to 8 ft, general criteria for racks, and Class IV or Group A criteria once records move into plastic totes.

Frequently Asked Questions

Are cartoned paper records a Class III commodity?

Yes. NFPA 13 Chapter 20 and 2021 IFC Section 3203.4 place paper products in corrugated cartons in Class III. Plastic changes the class: records in plastic boxes or totes, plastic binders and stored media are classified by their plastic content and can become Class IV or Group A plastics.

Is a records center with catwalk shelving high-piled storage?

Yes, when the top of the highest carton is more than 12 ft above the main floor. Storage height runs from the main floor through every open catwalk level, so 3 tiers of shelving reaching 24 ft are one 24 ft array under IFC Chapter 32.

Does compact mobile shelving need special sprinkler protection?

Conditional: NFPA 13 has criteria for compact storage of paper files, books and similar documents with no more than 5 percent plastics up to 8 ft high. Mobile shelving taller than 8 ft or holding more plastic is outside those criteria and needs an engineered design accepted by the AHJ.

Do plastic records totes change the sprinkler design?

Yes, in most cases. The NFPA 13 cartoned records criteria assume paper in corrugated cartons, so a move to plastic totes means a new commodity classification, usually Class IV or Group A plastics, and a design under the general storage chapters.

Is NFPA 232 required for a records storage warehouse?

Conditional: NFPA 232 applies when a regulation, a contract, an insurer, the AHJ or the records owner calls for it. The sprinkler requirement and design still come from the building code and NFPA 13; NFPA 232 adds protection for vaults, file rooms, archives, records centers and the records protection equipment inside them.

This article is general information, not a code determination for any project. Code editions, local amendments and reviewer practice change; confirm the adopted code and the authority having jurisdiction for the project.

Planning or Expanding a Records Center?

Send the shelving layout, the catwalk levels, the container type and the existing sprinkler drawings. DGA classifies the records, matches the NFPA 13 criteria to the arrangement and prepares the high-piled storage plan. Project briefs get confirmation and preliminary code feedback within one business day.

Send a Project Brief → View Related Services