Storage and Commodities · Trigger
What Storage Rules Apply to Tires, Rolled Paper and Cotton?
Reviewed by a licensed Professional Engineer · NY, NJ, PA, MD, DE · Last reviewed · Code basis: NFPA 13 (2016 NYC App. Q, 2019, 2022, 2025); IFC 2018, 2021, 2024 Ch. 32, 34 and 37; IBC 2021 Sec. 903.2.9.2; NFPA 1 (2024) Ch. 33 and 34
General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.
Rubber tires, roll paper and baled cotton are special commodities: NFPA 13, the National Fire Protection Association’s sprinkler installation standard, does not protect them with the Class I to IV or plastics criteria, and gives each one its own design rules driven by how it is stored. Tire designs turn on orientation (on-side, on-tread or laced) and pile type; roll paper designs turn on weight class, vertical or horizontal storage, banding and wrapping; baled cotton designs turn on bale type and arrangement. The International Fire Code (IFC) adds a second layer: tire piles can count as high-piled storage above 6 ft, indoor tire piles have size limits in IFC Chapter 34, and the International Building Code (IBC) requires sprinklers throughout a building once its tire storage space exceeds 20,000 cu ft.
The three commodities share one problem. Each burns in a way the standard test commodities do not represent: tires give off heavy smoke and pyrolysis oil and shelter fire inside their wheel holes, roll paper peels and burns up the gaps between rolls, and a cotton bale can smolder deep inside before it flames. Tire distributors, paper converting plants and cotton warehouses are typical of the industrial and high-hazard facilities where this question decides the sprinkler design.
At a Glance: Tire, Roll Paper and Baled Cotton Storage
- Threshold(s) with units: tire piles over 6 ft can be high-piled storage at the fire code official’s call, and roll paper and baled cotton over 12 ft are high-piled storage; a building with more than 20,000 cu ft of tire storage space must be sprinklered throughout; tire storage over 2,000 sq ft, or above the NFPA 13 miscellaneous tire storage height limits (12 ft for on-side floor piles and single-row racks, 5 ft for on-tread floor piles, double-row or multiple-row racks and laced tires in racks), leaves that allowance.
- Code, edition, section: NFPA 13 (2019, 2022 and 2025) Chapter 3 definitions, Chapter 4 for miscellaneous tire storage, Chapter 20, the storage design Chapters 21, 22 and 23, and, in the 2022 and 2025 editions, Chapter 26 for baled cotton; 2021 IFC Section 202, Chapter 32, Sections 3401.1 and 3409.1 for tires and Chapter 37 for baled cotton; 2021 IBC Section 903.2.9.2; NFPA 1 (2024) Chapter 33 for outdoor tires in Maryland and Delaware.
- Main exceptions: NFPA 13 miscellaneous tire storage (2,000 sq ft or less within its pile height limits); the fire code official’s discretion at the 6 ft tire line; reduced requirements for small high-piled areas under IFC Table 3206.2.
- What applies once triggered: the commodity’s own sprinkler criteria under control mode density/area (CMDA), control mode specific application (CMSA) or early suppression fast response (ESFR) design, NFPA 13 column protection and clearance rules, IFC Chapter 32 high-piled requirements and Chapter 34 tire pile limits.
- Permit or filing: a construction permit for the sprinkler work; an IFC operational permit for high-piled storage over 500 sq ft (Section 105.5 in the 2021 and 2024 IFC, Section 105.6 in the 2018 IFC); in New York City, Fire Department of the City of New York (FDNY) permits for tire storage and high-piled storage.
- Who decides: the fire code official on commodity classification and the 6 ft tire line, the building official on the sprinkler permit, with the fire protection engineer documenting the commodity, the arrangement and the design basis.
Why NFPA 13 Treats These Three as Special Commodities
NFPA 13 sorts most stored goods into Class I to IV commodities and Group A, B and C plastics, then protects them from shared design tables; DGA’s guide to commodity classification under NFPA 13 explains that scheme. Rubber tires, roll paper and baled cotton sit outside it. NFPA 13 defines each one in Chapter 3 and gives each a separate set of criteria, because each was fire tested on its own and burns differently from the commodities behind the Class I to IV tables.
The definitions are narrower than the everyday words. Rubber tires in NFPA 13 are pneumatic tires for cars, trucks, buses, trailers, aircraft, and farm and off-road construction equipment. Roll paper is paper wound on a core and stored in rolls, from linerboard to tissue. Baled cotton is natural seed fiber pressed and wrapped into bales, and the definition also takes in linters and motes, the short fibers and residue left from ginning.
The Thresholds for Tires, Roll Paper and Baled Cotton
Two codes set the numbers. NFPA 13 decides which sprinkler criteria apply, and the fire and building codes decide when high-piled rules, pile limits, sprinklers and permits apply. The table lists the thresholds a design team checks first, using the 2021 I-Code numbering; the jurisdiction table further down shows the edition each state enforces.
| Trigger | Threshold | Code and section | What it brings |
|---|---|---|---|
| High-piled storage, tires | Top of storage over 6 ft, where the fire code official requires it | 2021 IFC Section 202, definition of high-piled combustible storage; Chapter 32 | IFC Chapter 32 requirements, permit and storage plan |
| High-piled storage, roll paper and baled cotton | Top of storage over 12 ft; over 6 ft if the official treats the stock as a high-hazard commodity | 2021 IFC Section 202; Chapter 32 | IFC Chapter 32 requirements, permit and storage plan |
| High-piled storage permit | High-piled storage area over 500 sq ft | 2021 and 2024 IFC Section 105.5; 2018 IFC Section 105.6 | Operational permit from the fire code official |
| Sprinklers for bulk tire storage | Area available for tire storage over 20,000 cu ft | 2021 IBC and IFC Section 903.2.9.2 | NFPA 13 sprinklers throughout the building |
| Indoor tire pile size | On-tread piles 50 ft max in the wheel-hole direction; piles along a wall 25 ft max out from the wall; other piles 50 ft max wide | 2021 IFC Section 3409.1 | Pile layout shown on the storage plan |
| Baled cotton blocks | Each block or pile 25,000 cu ft max, with 5 ft aisles or a flash-fire barrier between blocks; top of piles at least 3 ft below sprinklers | 2021 IFC Sections 3705.1 and 3703.3 (Chapter 37, combustible fibers) | Block sizes and aisles shown on the storage plan; combustible fibers operational permit under Section 105.5 |
| NFPA 13 miscellaneous tire storage | 2,000 sq ft max storage area; on-side floor piles and single-row racks to 12 ft; on-tread floor piles, double-row or multiple-row racks and laced tires in racks to 5 ft; on-tread piles 25 ft max in the wheel-hole direction | NFPA 13 (2022) Section 4.3.1.6 | Within the limits, miscellaneous storage criteria; beyond them, the tire criteria |
| Roll paper class | Heavyweight 20 lb or more per 1,000 sq ft; mediumweight 10 to 20 lb; lightweight under 10 lb; tissue at any basis weight | NFPA 13 (2019, 2022) Chapter 3 definitions | Selects the roll paper criteria in Chapters 20 to 23 |
None of these numbers depends on the size of the building. A 15,000 sq ft tire shop and a 400,000 sq ft distribution center meet the same 6 ft, 20,000 cu ft and 500 sq ft lines.
How Each Trigger Is Measured
Storage height. The IFC measures high-piled storage to the top of the stored material, not to the top of a rack or shelf, so a 7 ft tire pile crosses the 6 ft line whatever the rack around it measures. NFPA 13 also needs the ceiling height and the clearance from the top of storage to the sprinkler deflectors. The tire and roll paper criteria are written for set combinations of storage height and building height, so all three numbers go on the drawings.
Tire orientation and pile type. NFPA 13 recognizes tires stored on-side (lying flat, with the wheel holes stacked into a vertical column), on-tread (standing upright, with the wheel holes lined up as a horizontal tunnel) and laced (on their sides but overlapped and interlocked). The pile type matters as much as the orientation: floor piles, palletized portable racks and fixed racks in single-, double- or multiple-row form each have their own lines in the tire criteria. The design team records the most demanding arrangement the operation will use, because a warehouse that moves from on-tread racks to laced floor piles has changed its design basis.
Roll paper class and arrangement. NFPA 13 sets the roll paper class by basis weight, the weight of 1,000 sq ft of the sheet, and the mill specification gives that number. Roll diameter and roll weight do not change the class: a 2,000 lb parent roll of tissue is still tissue. The criteria then depend on whether rolls stand on end (vertical) or lie on their side (horizontal), on the array for vertical storage (closed, standard or open, set by the gaps between columns), on banding (straps around each end of the roll) and on wrapping (a heavy kraft covering over the sides and ends).
Baled cotton type and arrangement. Cotton bales vary in size and density with how they were pressed, and NFPA 13 recognizes the common bale types. The baled cotton criteria depend on how the bales are arranged, tiered in blocks on the floor or held in racks, and on storage height. NFPA 13 also defines a fire-packed bale, one with fire sealed inside during ginning, because such a bale can smolder for a long time before it shows flame.
Tire storage volume. The IBC sprinkler trigger for tires is a volume, the area available for tire storage in cubic feet. DGA’s practice is to multiply the floor area that can hold tires by the height they can be stacked to, and to confirm that method with the building official. A 3,500 sq ft tire room with 6 ft piles gives 21,000 cu ft, which exceeds 20,000 cu ft and requires sprinklers throughout the building under Section 903.2.9.2, even where the Group S-1 fire area limits would not.
Figure 1: How Tires and Roll Paper Are Stored
Exceptions and Alternatives
Miscellaneous tire storage. NFPA 13 lets small tire storage that is incidental to the main use of a building be protected under the miscellaneous storage rules in Chapter 4 instead of the tire criteria. The allowance is capped at 2,000 sq ft of storage area, with on-side floor piles and single-row racks up to 12 ft high, on-tread floor piles, double-row or multiple-row racks and laced tires in racks up to 5 ft high, and on-tread piles no more than 25 ft long in the wheel-hole direction. An auto dealer’s parts room or a fleet garage’s spare tire rack often fits; a tire distribution warehouse does not.
The fire code official’s call at 6 ft. The IFC definition of high-piled combustible storage reaches tires above 6 ft only where the fire code official requires it. Many officials apply it as a matter of course, so a tire project should plan for IFC Chapter 32 unless the official confirms otherwise in writing.
Choosing the sprinkler type. For tires and roll paper, NFPA 13 offers CMDA, CMSA and ESFR criteria, each limited by storage height, building height and arrangement; DGA’s comparison of ESFR and CMSA sprinklers for warehouses covers the trade-offs. Baled cotton has only CMDA criteria in NFPA 13, so a cotton warehouse that wants ESFR sprinklers needs a basis outside the prescriptive tables, such as insurer criteria accepted by the authority having jurisdiction (AHJ) as an alternative. Rack tire storage can also use in-rack sprinklers under NFPA 13 Chapter 25 where the ceiling-only criteria run out.
Changing the arrangement. The least expensive alternative is often operational. Keeping tire piles at or below 6 ft, holding tire storage space under 20,000 cu ft, ordering roll paper banded, or keeping tissue out of a bay designed for mediumweight rolls can move the design to a less demanding line. Each choice has to be written into the storage plan and kept, because the next inspection measures what is on the floor.
Outdoor tire piles. Tires stored outside follow separate limits: 2021 IFC Section 3405.1 caps an individual pile at 5,000 sq ft, 50,000 cu ft and 10 ft high, Section 3405.2 requires 40 ft between piles, and NFPA 1 (2024), the Fire Code adopted in Maryland and Delaware, carries the outdoor tire rules in Chapter 33. Outdoor storage in general is a separate topic and is not covered here.
What Applies Once the Trigger Is Met
Crossing a special commodity threshold brings requirements from the sprinkler standard and the fire code together. A design and permit package for tire, roll paper or baled cotton storage has to show each of these items.
- Commodity-specific sprinkler design: the tire criteria in NFPA 13 (2022) Sections 21.7 (CMDA), 22.6 (CMSA) and 23.5 (ESFR), or the roll paper criteria in Sections 21.8, 22.7 and 23.6, selected for the arrangement, storage height and building height, or the baled cotton CMDA criteria, which sit in Section 26.5 of the 2022 edition and in Chapter 26 of the 2025 edition used in Delaware.
- NFPA 13 Chapter 20 storage rules: protection of steel building columns (2022 Section 20.18), the general roll paper criteria (2022 Section 20.6), clearance to sprinklers, and the hose stream allowance and water supply duration.
- Sprinklers throughout: a building with more than 20,000 cu ft of tire storage space is sprinklered throughout under 2021 IBC Section 903.2.9.2, not only over the tire area.
- IFC Chapter 32 high-piled requirements: Table 3206.2 scales sprinklers, fire detection, building access, smoke and heat removal and maximum pile dimensions with the size of the high-piled area, and tires fall in its high-hazard column. DGA’s article on when IFC Chapter 32 applies to high-piled storage walks through that table.
- IFC Chapter 34 tire rules: 2021 IFC Section 3401.1 sends indoor tire storage to Chapter 32 as well, and Section 3409.1 limits indoor pile dimensions.
- Operational permit and storage plan: a high-piled storage permit above 500 sq ft, with a plan that shows the commodity, arrangement, heights, pile sizes and aisles.
Storage height and ceiling height still drive the sprinkler type and the water demand, as they do for any commodity; DGA’s article on how high storage can go under ceiling-only sprinklers explains the clearance and ceiling limits. Tire and roll paper systems often carry large water demands, so the water supply analysis belongs early in design.
Figure 2: Which Criteria Each Commodity Goes To
DGA designs and reviews sprinkler protection for tire, roll paper and baled cotton storage across New York, New Jersey, Pennsylvania, Maryland and Delaware. Project briefs get confirmation and preliminary code feedback within one business day. See where DGA works →
Code Minimum vs What Insurers Expect
Many tire, paper and cotton warehouses are insured on FM Global data sheets, which set their own criteria: Data Sheet 8-3 for rubber tire storage, Data Sheet 8-21 for roll paper storage and Data Sheet 8-7 for baled fiber storage, including cotton (paraphrased). Those criteria can call for different sprinklers, densities, clearances or arrangement limits than NFPA 13. Where an insurer is involved, the design basis should be agreed with the carrier before the sprinkler layout is fixed, because meeting the code does not guarantee meeting the policy.
Which Codes Apply in New York, New Jersey, Pennsylvania, Maryland and Delaware
The commodity rules are the same wherever NFPA 13 applies, but the edition, the fire code and the permit differ by jurisdiction. The table lists what applies as of October 2026.
| Jurisdiction | Adopted codes and NFPA 13 edition | Tire and high-piled storage rules | AHJ | Permit or filing |
|---|---|---|---|---|
| New York State (outside NYC) | 2025 Uniform Code: Building Code and Fire Code of New York State on the 2024 I-Codes; NFPA 13 (2022) | Fire Code of New York State Chapters 32 and 34; Building Code Section 903.2.9.2 | Local code enforcement official | Building permit for the sprinkler work; operating permit where the local enforcement program requires one |
| New York City | 2022 NYC Building Code and 2022 NYC Fire Code; NFPA 13 (2016) as modified by Appendix Q of the Building Code | NYC Fire Code chapters on high-piled combustible storage and on tire storage | Department of Buildings (DOB) for sprinklers; FDNY for storage | DOB sprinkler filing; FDNY Tires, Scrap Tires and Tire Byproducts permit above 1,000 tires or 2,500 cu ft (outdoors or in fully sprinklered noncombustible buildings) or above 100 tires or 250 cu ft (other indoor storage); FDNY high-piled storage permit |
| New Jersey | Uniform Construction Code (UCC) on the 2024 I-Codes, effective August 17, 2026; NFPA 13 (2022) | Uniform Fire Code (UFC) on a 2018 IFC basis, Chapters 32 and 34; building subcode Section 903.2.9.2 | Construction official and fire protection subcode official; local fire official for the UFC | UCC construction permit; no separate fire permit for indoor high-piled storage; a UFC permit from the fire official for outdoor used tire storage under New Jersey Administrative Code Title 5, Chapter 70 |
| Pennsylvania | UCC on the 2021 I-Codes, effective January 1, 2026; NFPA 13 (2019); no statewide fire code | 2021 IBC Section 903.2.9.2; IFC Chapters 32 and 34 only where a municipality adopts a fire code; Philadelphia Fire Code on a 2018 IFC basis | Municipal or third-party code official; Philadelphia Department of Licenses and Inspections (L&I) | UCC building permit; local fire code permits where adopted, including Philadelphia operational permits |
| Maryland | 2021 IBC through the county building code, with NFPA 13 (2019); State Fire Prevention Code with NFPA 1 and NFPA 101 (2024), and NFPA 1 references NFPA 13 (2022) | NFPA 1 (2024) Chapter 34 for indoor storage and Chapter 33 for outdoor tires; IBC Section 903.2.9.2 | County building official; State Fire Marshal or local fire marshal | County building permit; fire marshal plan review |
| Delaware | State Fire Prevention Regulations, Regulation 701 (2026), with NFPA 1 and NFPA 101 (2024) and NFPA 13 (2025); IBC by county (New Castle and Sussex 2021, Kent and Wilmington 2018) | NFPA 1 (2024) Chapters 33 and 34; NFPA 13 (2025) tire and roll paper sections and Chapter 26 for baled cotton | Office of the State Fire Marshal (Wilmington Fire Marshal inside the city); county building official | State Fire Marshal plan review before the building permit; county building permit |
Editions as listed in DGA’s Fire Code Cheat Sheet for NY, NJ, PA, MD and DE. Local amendments are not shown.
Key Takeaway: Rubber tires, roll paper and baled cotton each have their own NFPA 13 criteria, so the first step is to record exactly how they are stored: tire orientation and pile type, roll paper class, orientation, array, banding and wrapping, bale arrangement, and every height. The fire and building codes then add the 6 ft high-piled line for tires, the Chapter 34 pile limits and the 20,000 cu ft sprinkler trigger, and those numbers, not the size of the building, decide what the project has to build.
Frequently Asked Questions
Are rubber tires protected as Group A plastics under NFPA 13?
No. NFPA 13 treats rubber tires as a separate commodity with their own criteria in the CMDA, CMSA and ESFR chapters, chosen by orientation, pile type, storage height and building height. The only shortcut is miscellaneous tire storage: 2,000 sq ft or less, with floor piles up to 12 ft on-side or 5 ft on-tread and rack storage up to 12 ft in single-row racks or 5 ft in other racks and for laced tires in any rack.
Does a tire shop with 6 ft piles need sprinklers?
Conditional: under 2021 IBC Section 903.2.9.2 the whole building needs sprinklers once the area available for tire storage exceeds 20,000 cu ft, and the fire code official can treat tire piles above 6 ft as high-piled storage under IFC Chapter 32. A shop under both lines may still need sprinklers for other reasons, such as the Group S-1 or Group M fire area limits.
Is tissue protected like other roll paper?
No. Tissue is its own roll paper class in NFPA 13 regardless of basis weight, with its own lines in the roll paper criteria. A building that adds tissue to a bay designed for heavyweight or mediumweight rolls needs the sprinkler design rechecked.
Can ESFR sprinklers protect baled cotton?
No, not from the NFPA 13 tables. NFPA 13 gives baled cotton control mode density/area criteria only, so ESFR protection over cotton needs another basis, such as insurer criteria that the AHJ accepts as an alternative.
Does banding roll paper change the sprinkler design?
Yes, it can. Banding is one of the variables in the NFPA 13 roll paper criteria because straps at each end keep the outer layers from peeling away in a fire, and for some classes and arrays banded rolls get less demanding criteria than unbanded rolls. The storage plan has to state which the operation uses.
More in Storage and Commodities
- When Does IFC Chapter 32 Apply to High-Piled Storage?
- Why Do Freezer Sprinkler Pipes Get Ice Plugs?
- What Fire Protection Does a Warehouse Need?
- What Fire Protection Do Cold Storage and Food Plants Need?
- What Rules Apply to Carpet, Mattress and Furniture Storage?
- What Fire Protection Does a Retail Store Need?
This article is general information, not a substitute for a project-specific code analysis. Code editions, local amendments, insurer requirements and reviewer practice change; confirm the adopted NFPA 13 and fire code editions with the authority having jurisdiction for each project.
Storing Tires, Roll Paper or Baled Cotton?
Send the storage layout, how each commodity is stored and the jurisdiction. DGA identifies the governing criteria, checks the fire and building code triggers, and designs or reviews the sprinkler protection. Project briefs get confirmation and preliminary code feedback within one business day.