Insights topic · 39 articles

Water Supply

Running and reading hydrant flow tests, sizing fire pumps, and checking storage tanks and standpipes against sprinkler demand.

Every water-based fire protection system depends on its water supply. A hydrant flow test shows what the city main can deliver, and the system demand shows what the sprinklers and standpipes need. When the supply falls short, the answer is usually a fire pump, a storage tank or both. The guides below cover flow tests, fire pumps, standpipes and acceptance testing.

Start here

Do You Need a Fire Pump? How Engineers Decide (NFPA 20)

A building needs a fire pump when a hydrant flow test less than 12 months old cannot meet the sprinkler or standpipe demand plus a 10 percent or 10 psi…

Questions this topic answers

Overview

QuestionCode basisLast reviewed
Water Supply for Fire Protection: The Complete GuideNFPA 13 (2022; 2019 PA/MD; 2025 DE), NFPA 291 (2022), NFPA 20 (2022; 2019 PA/MD; 2025 DE), NFPA 22 (2023), NFPA 24 (2022), NFPA 14 (2019/2024), NFPA 25 (2023), IFC App. B and C (2021/2024)Nov 2026

What it is

QuestionCode basisLast reviewed
What Is a Fire Pump Controller and Transfer Switch?NFPA 20 Ch 3, 4, 9, 10, 11, 12 in the edition referenced by the adopted code; NFPA 20 (2016) as modified by 2022 NYC BC Appendix Q (Q106); NFPA 20 (2025) in DE; NFPA 70 (NEC) Art 430 and 695, 695.4(B)(2)(b); UL 218; UL 1008; 2021 IBC 913; NFPA 25 (2023) Ch 8, 8.3.3; 2022 NYC BC Appendix Q modifications to NFPA 13 (2016); NYC DOB stationary fire pump requirementsNov 2026
What Is Backflow Preventer Pressure Loss in Sprinkler Calcs?NFPA 13 (2022) Ch 16, 28, 29, 30; NFPA 13 (2016) with NYC BC Appendix Q; NFPA 13 (2019) PA and MD; NFPA 13 (2025) DE; NFPA 25 (2023) Ch 13 and 4.3.4; 10 NYCRR 5-1.31; N.J.A.C. 7:10-10; 25 Pa. Code 109.709; COMAR 26.04.01.32; DE Public Drinking Water Regulations 21.0Nov 2026
What Is a Combined Sprinkler and Standpipe System?NFPA 14 (2016 and 2019; edition referenced by the adopted IBC) Ch 3, 6, 7, 9; NFPA 13 (2019 PA and MD, 2022 NYS and NJ, 2025 DE) Ch 5, 16; NFPA 13 (2016, NYC) Ch 8, 24 as modified by Appendix Q; 2021 IBC 403.3, 903.4, 905, 912; 2022 NYC BC Appendix Q (Q102, Q105); NFPA 25 (2023) Ch 5, 6, 15Nov 2026
What Is a Water Supply Safety Margin and How Much Is Enough?NFPA 13 (2022) Ch 5, Ch 19, Ch 20, Ch 28, Sec 4.5.1.1; NFPA 13 (2019) Ch 5, Ch 27; NFPA 13 (2016) with NYC BC Appendix Q; 2021 and 2024 IBC 903.3.5; NFPA 291 (2022) Ch 4; NFPA 20 Ch 4, Ch 6; NFPA 25 (2023) 4.1.6, 4.1.7.1Nov 2026
What Should a Hydrant Flow Test Report Contain?NFPA 291 (2022) Ch 4; NFPA 13 (2022) Ch 4 (water supply information; Section 4.5.1.1 test age), Ch 28 (plans and calculations) and Section 29.4 (hydraulic design information sign); NFPA 13 (2016) Ch 23 (NYC, Appendix Q), NFPA 13 (2019) Ch 27 (PA, MD) and NFPA 13 (2025) Ch 28 (DE) plans chapters; NFPA 25 (2023) Ch 13; 2021 and 2024 IBC Section 903.3.5; AWWA Manual M17Nov 2026
How Current Must a Flow Test Be, and Who Can Perform One?NFPA 13 (2022) 4.5.1.1; NFPA 13 (2019) Ch 4; NFPA 13 (2025) Ch 4; NFPA 13 (2016) Ch 23 via NYC 2022 Building Code Appendix Q; NFPA 291 (2022) Ch 4; NFPA 25 (2023) Ch 13Nov 2026
What Is a Fire Pump Room and What Does NFPA 20 Require?NFPA 20 (2016 as modified by NYC Appendix Q; 2025 in Delaware; edition referenced by the adopted IBC elsewhere) Chapters 4, 6, 7, 9, 10, 11 and 12; 2021 and 2024 IBC Sections 913.2 and 913.2.1; 2022 NYC Building Code Section 913 and Appendix Q Section Q106; NFPA 25 (2023) Chapter 8Nov 2026
What Is a Standpipe System (NFPA 14 Class I, II, III)?NFPA 14 (2016 in NYC via 2022 BC Appendix Q; editions referenced by the 2021 IBC in PA and MD and by the 2024 I-Codes in NJ and NYS; NFPA 1 (2024) in DE); 2021 IBC Section 905; NFPA 25 (2023) Chapter 6Nov 2026
What Is a Private Fire Service Main (NFPA 24)?NFPA 24 (2022); NFPA 13 (2022); 2021 IFC Section 507; NYS 2025 Uniform Code; NYC 2022 Construction Codes; NJ UCC 2024 I-Codes; PA UCC 2021 I-Codes; MD 2021 IBC and NFPA 1 (2024); DE Regulation 701 (2026)Nov 2026

When it is required

QuestionCode basisLast reviewed
Do You Need a Fire Pump? How Engineers Decide (NFPA 20)NFPA 13 (2022) Ch. 28 and 4.5.1.1; NFPA 291 (2022); NFPA 20 (2022); NFPA 25 (2023); NFPA 22Oct 2026
When Can a Well or Private Source Supply Fire Protection?NFPA 13 (2022) Ch 5 and 19; NFPA 20 Ch 4 and 7; NFPA 22 Ch 4; NFPA 13D Ch 6; NFPA 13R; NFPA 25 (2023) Ch 8, 9 and 14; N.J.A.C. 7:9D and 7:19; 25 Pa. Code Ch 110; COMAR 26.04.04 and 26.17.06; 7 Del. Admin. Code 7301 and 7303Nov 2026
When Does a Fire Pump Need a Generator or Alternate Power?NFPA 20 Ch 9 and 10 in the edition referenced by the adopted IBC; NFPA 20 (2016) via 2022 NYC BC Appendix Q; NFPA 20 (2025) in DE; 2021 IBC 403.4.8, 913 and 202; 2022 NYC BC 403.4.8.4; NFPA 70 Articles 695 and 700 (2020 NYC Electrical Code basis, 2023 NJ and DE)Nov 2026
When Do Standpipes Need Pressure-Reducing Valves?NFPA 14 Ch. 3, 4, 7 and 11 (edition referenced by the adopted building code); NFPA 14 (2016) as modified by 2022 NYC Building Code Appendix Q; NFPA 25 (2023) Ch. 4 and 13; NFPA 20 Ch. 10Nov 2026
When Is a Jockey Pump, Bypass or Test Header Required?NFPA 20 Ch 4 and Ch 14 (2016 as modified by 2022 NYC BC Appendix Q Q106; 2025 in DE; IBC-referenced edition elsewhere); NFPA 25 (2023) Ch 8Nov 2026
When Does a Standpipe Need a Fire Pump or a Second Zone?NFPA 14 Chapters 5, 7 and 9 as numbered in the 2016 edition (edition referenced by the adopted IBC; system pressure limit 350 psi in NFPA 14 (2016), higher in later editions); NFPA 14 (2016) as modified by 2022 NYC Building Code Appendix Q (Q105.1; 5.4.1.2, 7.2.1, 7.2.3.2 reserved, 7.2.4, 7.7.2, 7.8.1, 7.9.1, 7.9.2, 7.9.3, 7.9.3.1); NFPA 20 Chapter 4 (2025 in DE); NFPA 25 (2023) Chapters 6 and 13; 2021 and 2024 IBC Section 202; 2021 IBC Sections 403 and 403.4.8Nov 2026
Can a Fire Pump Take Suction From a City Main?NFPA 20 Chapter 4; NFPA 13 (2022) 4.5.1.1; NFPA 291 (2022) Chapter 4; NFPA 14 9.1.4(2) as modified by 2022 NYC Building Code Appendix Q; NFPA 20 (2025) in DelawareNov 2026
Do You Need a Standpipe During Construction (IFC 3314)?2021 IFC Sections 104 and 3314.1 to 3314.3 (3313 in the 2018 IFC; 3307.5 in the 2024 IFC); 2021 IBC Sections 905.3.1 and 3311.1 to 3311.3; 2022 NYC Building Code Sections 3303.8, 3303.8.1 and 3303.8.2; 2022 NYC Fire Code Section 3313; NFPA 14 (buildings under construction chapter); NFPA 241 (2022) Chapter 4Nov 2026
How Many Fire Hydrants Does a Site Need (IFC Appendix C)?2021 IFC Section 507.5.1; 2021 IFC Appendix C (C102, Table C102.1, C103, C104); NFPA 24 Chapter 7; NFPA 25 (2023) Chapter 7; NFPA 1 (2024) Chapter 18; 1 Del. Admin. Code 702 Chapter 6; N.J.A.C. 5:21 and 5:70-3.2; 2022 NYC Fire CodeNov 2026
When Is a Fire Protection Water Tank Required?NFPA 13 (2022) Ch 4 (4.5.1.1), Ch 5 and Ch 19; NFPA 20 Ch 4; NFPA 22; NFPA 25 (2023); 2021 and 2024 IBC 903.3.5 and 403.3.3; NYC 2022 BC Appendix Q (NFPA 14 (2016) 9.1.4, NFPA 20 (2016)); purveyor rulesNov 2026
When Does a Building Need a Standpipe (IBC 905.3)?2021 IBC Sections 905.3 and 905.4; 2024 IBC Section 905.3 (NYS, NJ); 2022 NYC Building Code Section 905.3.1; 2021 IFC Section 3314; NFPA 14 (edition per adopted code); NFPA 25 (2023) Chapter 6; NFPA 101 (2024)Nov 2026

How the process works

QuestionCode basisLast reviewed
How Are Underground Fire Mains Flushed and Tested (NFPA 24)?NFPA 24 (2022) Ch 10; NFPA 13 (2022) Ch 29, (2019) Ch 28, (2016) Ch 10 as modified by NYC 2022 BC Appendix Q; NFPA 14 (2016) 11.4.1 as modified (NYC); NFPA 25 (2023) 4.3.4, Ch 7, 14.3; 15 RCNY 20-01Nov 2026
How Does an Electric Fire Pump Acceptance Test Differ?NFPA 20 Chapters 9, 10 and 14 (edition referenced by the adopted code: 2016 via 2022 NYC BC Appendix Q, 2025 in Delaware); NFPA 25 (2023) Chapter 8, Section 8.3.3; NYC DOB Construction Advisory 2025-001; UL 218; UL 1008; NFPA 110Nov 2026
How Is a Dry Hydrant or Drafting Site Approved?NFPA 1142 (2022; the 2021 IFC references an earlier edition); IFC Appendix B Section B103.3 (2021 and 2024, where adopted); NFPA 1 (2024) Chapter 18 (MD); 1 Del. Admin. Code 702 Chapter 6 Sections 2 and 7, Regulation 703 Chapter 1 (DE); N.J.A.C. 5:70-3.2; 25 Pa. Code Chapter 105 (GP-4); MDSPGP-7; USDA NRCS Conservation Practice Standard 432 (2021)Nov 2026
How Is a Hydrant Flow Test Run and Read (NFPA 291)?NFPA 291 (2022) Ch. 4; NFPA 13 (2022) Ch. 4, 5 and 28; AWWA M17; NYS 2025 Uniform Code; NYC 2022 Building Code; NJ UCC 2024 I-Codes; PA UCC 2021 I-Codes; MD 2021 IBC, NFPA 1 and 101 (2024); DE Reg. 701 (2026), NFPA 13 (2025)Nov 2026
What Happens at a Diesel Fire Pump Acceptance Test?NFPA 20 (2022); NFPA 22; NFPA 25 for the annual test that followsOct 2026

How the options compare

QuestionCode basisLast reviewed
Split-Case vs In-Line vs Vertical Turbine: Which Fire Pump?NFPA 20 Chapters 4, 6, 7, 9, 11 and 14 (2016 as modified by NYC Appendix Q, 2025 in Delaware, edition referenced by the 2021 or 2024 IBC elsewhere); NFPA 25 (2023) Chapter 8; 2022 NYC Building Code Appendix Q, Section BC Q106Nov 2026
Wet vs Dry vs Manual Standpipes: Which Does the Code Allow?NFPA 14 Chapters 3 and 5 (2016, 2019); 2021 IBC Sections 202, 905.2, 905.3.1, 905.3.2, 905.3.5, 905.8, 912; 2024 IBC Section 905 (NJ, NYS); NYC 2022 Building Code Section 905 and Appendix Q; NFPA 25 (2023) Chapters 6 and 8Nov 2026
Electric vs Diesel Fire Pump: How Do Engineers Choose?NFPA 20 (2016 NYC via 2022 BC Appendix Q; 2025 DE; edition referenced by the 2021 or 2024 IBC elsewhere) Chapters 9 to 12 and 14; NFPA 25 (2023) Chapter 8; 2021 IBC Section 403.4.8; NYC Fire Code and Mechanical Code (fuel storage); FM Global DS 3-7Nov 2026

Calculations

QuestionCode basisLast reviewed
How Do You Calculate Standpipe Demand and Pressure?NFPA 14 Chapter 7 and Chapter 9 (edition referenced by the adopted building code); NFPA 13 (2022) Chapter 28; 2022 NYC Building Code Appendix Q (NFPA 14 (2016) as modified); IBC Section 905Nov 2026
How Do You Size a Fire Protection Water Storage Tank?NFPA 13 (2022) Ch. 19 and 20 to 25; NFPA 14 Ch. 7 and 9; NFPA 20 Ch. 4; NFPA 22 (2023) Ch. 4; NFPA 72; FM Global DS 3-2; 2021 and 2024 IBC; NFPA 1 (2024)Nov 2026
How Do You Read a Fire Pump Test Curve (Speed Corrected)?NFPA 20 Chapter 14 and Chapter 6 (DE: 2025 edition; elsewhere the edition referenced by the adopted building code); NFPA 25 (2023) Chapter 8, Section 8.3.3; SFPE Handbook, 5th ed.Nov 2026
How Do You Calculate Available Fire Flow at 20 psi?NFPA 291 (2022) Ch 4; NFPA 13 (2022) Ch 28; AWWA Manual M17Nov 2026
How Do You Calculate Required Fire Flow (IFC Appendix B)?2021 IFC Appendix B (B102, B103, B104, B105, Tables B105.1(1), B105.1(2), B105.2); 2021 IBC Section 602; NFPA 1 (2024) Chapter 18; 1 Del. Admin. Code 702 Chapter 6; N.J.A.C. 5:70-3; 19 NYCRR Part 1225; 2022 NYC Fire Code and Building CodeNov 2026
How Do You Size a Fire Pump (Rated Flow and Pressure)?NFPA 20 Ch 4, 6 and 7 (2016 NYC via 2022 BC Appendix Q; 2025 DE; editions referenced by the 2024 I-Codes for NYS and NJ and by the 2021 IBC for PA and MD); NFPA 13 (2022) Ch 4, 19 and 28; NFPA 14 Ch 7Nov 2026
How Do You Plot Sprinkler Demand Against the Supply Curve?NFPA 13 (2022) Ch 28, Ch 5, 4.5.1.1 and Ch 19; NFPA 13 (2019) Ch 27 (PA, MD); NFPA 13 (2016) Ch 23 (NYC, Appendix Q); NFPA 13 (2025) Ch 28 (DE); NFPA 291 (2022) Ch 4Nov 2026

By state and city

QuestionCode basisLast reviewed
What Are NYC’s Standpipe Requirements (BC 905, FC 912)?2022 NYC Building Code 905, 912, Chapter 17, Appendix Q (NFPA 14, 2016, as modified); 2022 NYC Fire Code 901, 905, 912; 3 RCNY 912-01; 2021 IBC 905.3.1Nov 2026

Problems and how to fix them

QuestionCode basisLast reviewed
Why Did the AHJ Reject the Hydrant Flow Test?NFPA 13 (2022) Ch 4 (Sec 4.5.1.1), Ch 28, Sec 29.4; NFPA 13 (2016, NYC Appendix Q), (2019), (2025); NFPA 291 (2022) Ch 4; AWWA Manual M17; IBC (2021, 2024) Sec 903.3.5, 105.3.2, 105.5Nov 2026
Why Is the Water Supply Weaker Than the Old Flow Test Said?NFPA 291 (2022) Ch. 4; NFPA 13 (2022) 4.5.1.1, 29.4, Ch. 30; NFPA 25 (2023) 4.1.6, 4.1.7.1, 4.3.4, Ch. 8, 13, 14; 2021 IBC 903.3.5Nov 2026

A fire protection water supply is the source, piping and equipment that deliver water to a building's sprinklers, standpipes and hydrants at the flow, pressure and duration the design needs. Every sprinkler system in the region is designed to a demand point, a number of gallons per minute (gpm) at a pressure in pounds per square inch (psi) that must be sustained for a set time, and the supply has to meet that point with a margin. When the public main cannot, the project adds a fire pump, a storage tank or a larger service, and each of those carries its own standard, its own acceptance test and its own place in the permit sequence.

This guide is written for owners, developers, architects and construction managers who need to understand how a water supply is measured, how engineers decide whether it is enough, and what happens when it is not. It covers New York State, New York City, New Jersey, Pennsylvania, Maryland and Delaware. It stays at the level of the whole topic and points to the article that owns each individual question.

At a Glance: Water Supply for Fire Protection

  • What this topic covers: hydrant flow tests, the supply versus demand comparison, fire pumps, water storage tanks, private fire service mains, standpipes and the fire flow and hydrant rules in the fire code.
  • Governing codes and editions: National Fire Protection Association (NFPA) 13 (2022 edition; 2019 under the 2021 International Building Code in Pennsylvania and Maryland; 2025 in Delaware) Chapter 5 for water supplies and Chapter 28 for plans and calculations (Chapter 27 in the 2019 edition); NFPA 291 (2022) for flow testing; NFPA 20 (2022; 2019 under the 2021 IBC; 2025 in Delaware) for fire pumps; NFPA 22 (2023) for tanks; NFPA 24 (2022) for private fire service mains; NFPA 14 (2019 under the 2021 IBC; 2024 under the 2024 I-Codes) for standpipes; International Fire Code (IFC) Appendix B and Appendix C (2021 or 2024, adopted locally) for fire flow and hydrants; NFPA 25 (2023) Chapter 8 for pump testing after acceptance.
  • Who it applies to: every sprinklered or standpipe-equipped building, every new building that needs a fire flow determination at site plan, and every owner who inherits a fire pump or tank that must be tested each year.
  • The 3 decisions that drive cost: whether the city main can carry the sprinkler demand without a pump; whether a storage tank is needed because the main cannot supply the duration or the water purveyor limits the draw; and whether the building height or standpipe class pushes the pump pressure high enough to require pressure-reducing valves and a second power source.
  • Where to start: a current hydrant flow test on the main that will serve the site, read against the sprinkler and standpipe demand before the design is set.
  • Related services and tools: DGA's fire pump design and standpipe design services, the Hydrant Flow Test Calculator, the Sprinkler Water Supply Analysis tool, the Fire Pump Test Curve Plotter and the IFC Appendix B Fire Flow Calculator, all linked below.

What a Water Supply Has to Deliver: Flow, Pressure and Duration

A fire protection water supply is judged on three numbers at once. Flow is the volume per minute the system discharges, in gpm. Pressure is what pushes that flow through the pipe network and out of the most remote sprinkler, in psi. Duration is how long the supply must hold that flow, in minutes, and NFPA 13 (2022) Chapter 19 sets the duration and the hose stream allowance by hazard class.

The sprinkler demand is a single point: for example, 720 gpm at 58 psi at the base of the riser for 90 minutes, including 250 gpm of hose stream for the fire department. NFPA 13 (2022) Chapter 5 lists the acceptable sources (a public waterworks, a tank, a pump drawing from a reliable source, or a combination) and Chapter 28 sets what the hydraulic calculation has to show about them. A supply is adequate when the available pressure at the demand flow is above the required pressure, and NFPA 13 (2022) Chapter 28 requires the calculation to show the supply curve, the demand point and the margin between them.

Standpipes add a second demand that is usually larger than the sprinkler demand. Under NFPA 14 (2019) a Class I or Class III standpipe must deliver 100 psi residual at the most remote hose outlet, with 500 gpm for the first standpipe and 250 gpm for each additional standpipe, capped at 1,000 gpm where the building is sprinklered throughout and 1,250 gpm otherwise (Chapter 7). In a high-rise the pressure to reach the roof outlet, plus friction, is the number that decides whether a fire pump is required and how large it is.

DemandWhat sets itTypical rangeStandard
Light and ordinary hazard sprinklersDensity over a remote area, plus hose stream, for the listed durationAbout 250 to 1,000 gpm at 40 to 80 psi for 30 to 90 minutesNFPA 13 (2022) Chapters 19 and 28
Storage sprinklers (early suppression fast response (ESFR), control mode specific application (CMSA) and in-rack)Number of operating sprinklers at a minimum pressure, plus hose stream, for 60 to 120 minutesAbout 1,200 to 3,000 gpm at 50 to 100 psiNFPA 13 (2022) Chapters 20 to 25 and 28
Class I or III standpipe100 psi residual at the most remote outlet, 500 gpm first standpipe plus 250 gpm each additional500 to 1,250 gpm; pressure set by building heightNFPA 14 (2019) Chapter 7
Site fire flow for hydrantsBuilding area and construction type, reduced for sprinklers1,000 to 4,000 gpm for 2 to 4 hours (varies by jurisdiction)IFC Appendix B, where adopted, or NFPA 1 Chapter 18

The fire flow in the last row is a different question from the sprinkler demand. Fire flow is the water the fire department needs from hydrants to fight a fire in the building from outside, and the fire code sets it by floor area and construction type in IFC Appendix B, reduced where the building is sprinklered. New York City does not use Appendix B; its water supply and hydrant rules sit in the NYC Fire Code and in the Department of Environmental Protection's standards. This guide only places that arithmetic in the sequence.

The Water Supply Train: Main to Hose Outlet

Public main (water purveyor) Tap and private main NFPA 24 (2022) Backflow FIRE PUMP NFPA 20 bypass Roof outlet: 100 psi NFPA 14 (2019) Ch. 7 Floor control valve Sprinkler branch Riser and standpipe NFPA 13 and 14 Hydrant: flow test here NFPA 291 (2022) test header Each element has its own standard and its own acceptance test. The pressure the pump must add is the roof outlet requirement plus elevation and friction, minus what the main delivers at the demand flow.
Water reaches a sprinkler or hose outlet through five governed elements: the public main, tested under NFPA 291 (2022); the private fire service main, built and flushed under NFPA 24 (2022); the fire pump, sized and accepted under NFPA 20 (2022 or 2019); the sprinkler riser under NFPA 13; and the standpipe, which under NFPA 14 (2019) Chapter 7 must deliver 100 psi at the most remote hose outlet.

How the Supply Is Measured and Plotted

The supply side of the comparison comes from a hydrant flow test. A gauge on one hydrant records the static pressure with nothing flowing and the residual pressure while a second hydrant on the same main flows water through a pitot gauge. NFPA 291 (2022) Chapter 4 sets the procedure, and the 2022 edition recommends enough hydrants be flowed to drop the residual pressure by at least 10 percent from static; the 2019 edition asked for 25 percent. The same chapter sets 20 psi as the residual pressure that the available flow is projected to.

Two readings define a curve. Water flow through a pipe network follows a 1.85-power relationship between flow and pressure loss, so when static and residual pressures are plotted on paper whose horizontal axis is scaled to the 1.85 power, the supply becomes a straight line. The engineer then plots the sprinkler demand point on the same graph and reads the distance between the two. The Process article on how a hydrant flow test is run and read covers the field procedure.

A supply that barely clears the demand is not a safe design. Public mains lose pressure as the system ages and as new customers connect, and a test taken on a cool morning reads higher than the same main on a summer afternoon. Most engineers in the region design to a margin of about 10 percent or 10 psi at the demand flow, and some AHJs (authorities having jurisdiction) write a minimum margin into their review standards.

Supply Curve Against the Sprinkler Demand Point

020406080 Pressure, psi 05001,0001,5002,000 Flow, gpm (axis scaled to the 1.85 power) 20 psi residual (NFPA 291 projection) Static 72 psi, 0 gpm Test point: 1,150 gpm at 52 psi About 2,200 gpm available at 20 psi Demand: 720 gpm at 58 psi Supply 65 psi at 720 gpm: margin 7 psi Numbers are an example for a 2-story office; each project plots its own test.
Two hydrant readings, a static of 72 psi and a residual of 52 psi while 1,150 gpm flows, define the whole supply line on 1.85-power graph paper and project to about 2,200 gpm at 20 psi. A sprinkler demand of 720 gpm at 58 psi falls 7 psi below the line, which is a margin most reviewers in the region accept; NFPA 13 (2022) Chapter 28 requires the calculation to show the supply curve, the demand point and that margin.

Three Formulas Behind Every Water Supply Analysis

Pitot flow (NFPA 291, 2022, Chapter 4): Q = 29.84 × c × d² × √p, where Q is flow in gpm, c is the outlet coefficient (0.90 for a smooth rounded hydrant outlet, 0.80 for a square outlet, 0.70 for an outlet projecting into the barrel), d is the outlet diameter in inches and p is the pitot pressure in psi.

Projection to 20 psi (NFPA 291, 2022, Chapter 4): QR = QF × ((PS − PR) / (PS − PF))0.54, where QF is the flow measured, PS is static pressure, PF is the residual pressure at the test flow and PR is the residual pressure of interest, normally 20 psi.

Fire pump curve (NFPA 20, 2022, Chapter 4): the pump must deliver at least 150 percent of rated flow at not less than 65 percent of rated pressure, and its no-flow (churn) pressure may not exceed 140 percent of rated pressure (Chapter 4, Fire Pump Unit Performance).

A hydrant flow test is reduced to gpm with the pitot equation, projected to 20 psi with the 0.54-power relationship, and the pump that makes up any shortfall is checked against three points: churn at or below 140 percent of rated pressure, 100 percent of rated flow at rated pressure, and 150 percent of rated flow at 65 percent or more of rated pressure.

When the City Main Is Not Enough: Pumps, Tanks and Mains

When the supply line falls below the demand point, the engineer works through a fixed order of fixes, cheapest first. The first move is to redesign the system to lower the demand: smaller remote area through a quick-response sprinkler reduction, larger pipe, a gridded layout or a different sprinkler. The second is a larger or second service from the main, which the water purveyor must approve and which NFPA 24 (2022) governs once it leaves the public right of way. Only when those fail does the project add a pump, and only when the main cannot supply the flow at all, or the purveyor caps the draw, does it add a tank.

A fire pump adds pressure, not water. NFPA 20 (2022) requires the suction source to deliver the pump's full 150 percent flow, and the pressure at the suction flange may not drop below 0 psi gauge, with 20 psi the common purveyor and AHJ limit for a pump drawing from a public main (Chapter 4). The live Trigger article on whether a building needs a fire pump covers the decision in detail, and the live Process article on the diesel fire pump acceptance test covers how NFPA 20 Chapter 14 proves the installed pump; both are linked in the questions table below.

A tank adds water, and sometimes pressure. NFPA 22 (2023) covers the tank itself: gravity tanks, suction tanks, pressure tanks and break tanks, their capacity, their heating and their fill. A break tank is the usual answer when the main has enough pressure for domestic use but the purveyor will not allow a direct pump draw; it holds a fraction of the duration and refills from the main while the pump runs. A suction tank holds the full demand for the full duration when the site has no reliable main, which is common in Pennsylvania and Maryland industrial parks served by small systems.

The private fire service main is the piping that ties all of this together outside the building. NFPA 24 (2022) sets its materials, depth of cover, thrust restraint, flushing rate and the 2-hour hydrostatic test at 200 psi or 50 psi above working pressure (Chapter 10). The Definition article on the private fire service main, linked in the table below, defines it and separates it from the public main and the domestic service.

Supply Short? The Fix Order Engineers Follow

Does the flow test clear the demand point with margin (about 10 percent or 10 psi)? Yes: show the curve in the NFPA 13 Ch. 28 calculation No. Can redesign lower the demand (pipe size, layout, sprinkler type)? Yes: redesign first. Lowest cost, no new equipment No. Will a larger or second service from the main reach the demand? Yes: new service, NFPA 24, purveyor approval needed No. Does the main give enough flow but not enough pressure? Yes: fire pump, NFPA 20, Ch. 14 acceptance test No: tank, NFPA 22, plus pump under NFPA 20
The fix order runs from cheapest to most expensive: redesign the system, enlarge the service under NFPA 24 (2022), add a fire pump under NFPA 20 (2022) when the main has flow but not pressure, and add a tank under NFPA 22 (2023) only when the main cannot supply the flow or the purveyor limits the draw. Each step down the tree adds equipment that NFPA 25 (2023) requires the owner to test for the life of the building.

Standpipes and High-Rise Pressure

A standpipe is a vertical pipe with hose outlets on each floor that lets firefighters connect hose inside the building instead of dragging it up the stairs. The IBC (2021) Section 905.3.1 requires a Class III standpipe where the floor level of the highest story is more than 30 ft above the lowest level of fire department vehicle access, and allows a Class I standpipe instead where the building is fully sprinklered; other triggers in Section 905.3 cover assembly, covered malls, stages and buildings under construction. NFPA 14 (2019) sets the design: Class I for fire department use with 2 1/2 in. outlets, Class II for occupant use with 1 1/2 in. hose, and Class III with both.

Pressure is the whole problem in a standpipe design. The 100 psi required at the roof outlet, plus about 0.433 psi for every foot of elevation, plus friction in the riser, sets the pressure the pump must produce at grade. In a 20-story building that number often lands near 250 psi, and NFPA 14 (2019) caps the pressure at any hose outlet at 175 psi and requires pressure-reducing valves where the static pressure would exceed it (Chapter 7). Above a certain height the system is split into zones with separate pumps or a transfer pump.

Most standpipe systems in the region are combined systems that also feed the floor sprinklers from the same riser. NFPA 14 (2019) Chapter 7 sets the combined demand, and NFPA 13 (2022) Chapter 28 requires the sprinkler calculation to account for it. Under NFPA 14 (2019) Chapter 7 the combined standpipe demand is capped at 1,000 gpm where the building is sprinklered throughout and 1,250 gpm otherwise, and the pump is sized to the larger of that figure and the sprinkler demand; DGA's standpipe design work and the commercial high-rise sector page below describe the projects where this governs.

What the AHJ and the Water Purveyor Each Control

Two different authorities decide a water supply, and they do not always agree. The water purveyor (a municipal water department or a private utility such as New Jersey American Water, Aqua Pennsylvania or the Philadelphia Water Department) owns the public main, runs or witnesses the hydrant flow test, approves the size of the tap and the service, and often limits how far a fire pump may draw the main down. The AHJ for the building code (the building department, fire marshal or fire department) reviews the hydraulic calculation, the pump room and the standpipe design, and witnesses the acceptance tests under NFPA 20 Chapter 14 and NFPA 24.

The purveyor's rules frequently govern. Many utilities in the region will not release a flow test older than 6 or 12 months, require their own crew to run it, and require a reduced-pressure backflow preventer on the fire service that costs 10 to 15 psi of the available pressure before the water reaches the riser.

The AHJ controls the sequence after the design is set. In New York City, sprinkler and standpipe work is filed with the Department of Buildings (DOB) and the Fire Department (FDNY) witnesses the standpipe and fire pump tests; outside the city, the local code enforcement official or fire marshal does both. The approvals hub linked at the end covers each jurisdiction's filing path; the table below gives the editions and the names.

From Flow Test to Acceptance: The Water Supply Sequence

Hydrantflow testNFPA 2911 to 4 weeks Hydraulic calcand supply decisionNFPA 13 Ch. 281 to 3 weeks PermitfilingAHJ review2 to 12 weeks Underground mainflushed and testedNFPA 24, 200 psifor 2 hours Pump and tankinstalledNFPA 20, 2212 to 30 weeks lead AcceptancetestNFPA 20 Ch. 14AHJ witnesses Annualflow testNFPA 25 Ch. 8every year Design decisions happen in the first two steps. Everything after them is procurement, installation and proof. Durations are typical ranges for the region as of October 2026; pump lead time is the usual critical path item.
The supply decision is made before the permit is filed: the NFPA 291 flow test and the NFPA 13 Chapter 28 calculation take 2 to 7 weeks together, while a fire pump can take several months of lead time in the region as of October 2026. The underground main is tested at 200 psi for 2 hours under NFPA 24 (2022), the pump is proven at churn, 100 percent and 150 percent under NFPA 20 Chapter 14, and NFPA 25 (2023) Chapter 8 then requires an annual flow test for the life of the building.

Code Editions by State

Water supply requirements come from three places in every jurisdiction: the building code that adopts NFPA 13, 14 and 20 by reference, the fire code that sets fire flow and hydrant rules, and the water purveyor's own standards. The table lists the adopted editions as of October 2026, the AHJ that reviews the design and the name of the filing. Local amendments are not shown.

Water Supply Codes, Reviewers and Filings by Jurisdiction

JurisdictionAdopted code and edition (as of October 2026)Fire flow and hydrantsAHJFiling
New York State (outside NYC)2025 Uniform Code (2024 I-Codes): NFPA 13 (2022), NFPA 14 (2024), NFPA 20 (2022), NFPA 24 (2022)2024 IFC Appendix B and C where the municipality adopts them; purveyor flow testLocal code enforcement official; local fire department for hydrantsBuilding permit with sprinkler and standpipe drawings and hydraulic calculations
New York City2022 NYC Building Code and 2022 NYC Fire Code: NFPA 13 (2016), NFPA 14 and NFPA 20, as amended in Appendix QNo IFC Appendix B; hydrant flow tests through the Department of Environmental Protection; NYC Fire Code Chapter 5Department of Buildings for design; FDNY witnesses standpipe and pump testsDOB NOW sprinkler (SP) and standpipe (SD) work types; FDNY test witnessing
New JerseyUniform Construction Code (UCC) 2024 I-Codes (effective August 17, 2026): NFPA 13 (2022), NFPA 14 (2024), NFPA 20 (2022); Uniform Fire Code on a 2018 IFC basisFire flow per 2018 IFC Section 507 as modified by the UFC; local fire official and purveyorMunicipal fire protection subcode official; local fire official for hydrantsUCC construction permit, fire protection subcode technical section
PennsylvaniaUCC 2021 I-Codes (January 1, 2026): NFPA 13 (2019), NFPA 14 (2019), NFPA 20 (2019); no statewide fire codeIFC Appendix B and C only where a municipality adopts a fire code; Philadelphia Fire CodeMunicipal or third-party code official; Philadelphia Department of Licenses and Inspections (L&I)UCC building permit; Philadelphia fire suppression permit
Maryland2021 IBC: NFPA 13 (2019), NFPA 14 (2019), NFPA 20 (2019); NFPA 1 (2024) for fire preventionNFPA 1 (2024) Chapter 18 water supply and hydrant provisions; county fire marshal standardsCounty building official and county or State Fire MarshalCounty building permit plus fire marshal plan review
DelawareRegulation 701 (2026): NFPA 1 (2024), NFPA 13 (2025), NFPA 20 (2025), NFPA 25 (2023); IBC by county (2021 in New Castle and Sussex, 2018 in Kent and Wilmington)NFPA 1 (2024) Chapter 18 water supply provisions; State Fire Marshal reviewOffice of the State Fire Marshal (Wilmington Fire Marshal inside the city)State Fire Marshal plan review before the county building permit
Two states review fire pumps under NFPA 20 (2019) and three under newer editions: Pennsylvania and Maryland through the 2021 IBC, New York State and New Jersey through the 2024 I-Codes (NFPA 20, 2022), and Delaware through Regulation 701 (NFPA 20, 2025). New York City sets fire flow outside IFC Appendix B, and New Jersey applies IFC Section 507 as modified by the Uniform Fire Code rather than the appendix.

Editions as listed in DGA's Fire Code Cheat Sheet for NY, NJ, PA, MD and DE.

Key Concepts

These are the terms the Water Supply articles use. Each is defined once here so the spokes can use the term without re-explaining it.

  • Static pressure: the pressure in the main with no water flowing, read on the gauge hydrant at the start of a flow test.
  • Residual pressure: the pressure remaining in the main while the test flow is discharging, read on the same gauge hydrant.
  • Pitot pressure: the velocity pressure measured in the stream leaving a flowing hydrant outlet, converted to gpm with the pitot equation.
  • Demand point: the flow and pressure the sprinkler or standpipe system requires at the point where the supply is compared, usually the base of the riser.
  • Supply curve: the line through the static and residual readings on 1.85-power graph paper, showing the pressure the main can hold at any flow.
  • Safety margin: the pressure difference between the supply curve and the demand point at the demand flow, held in reserve against main deterioration and seasonal change.
  • Hose stream allowance: the extra flow, typically 100 to 500 gpm, added to the sprinkler demand for fire department hose use under NFPA 13.
  • Rated point: the flow and pressure stamped on a fire pump nameplate, the 100 percent point on its curve.
  • Churn: the pump running with no water flowing, whose pressure NFPA 20 limits to 140 percent of rated pressure.
  • Break tank: a tank that receives water from the public main and holds part of the demand so a pump can draw from it without pulling the main below the purveyor's limit.
  • Private fire service main: the owner-owned underground piping from the public main or private source to the risers, private hydrants and fire department connections, built under NFPA 24.
  • Fire flow: the water the fire code requires to be available from hydrants for exterior firefighting, set by building area and construction type in IFC Appendix B or NFPA 1 Chapter 18.

Working With DGA on Water Supply

DGA's engineers request and witness hydrant flow tests, plot the supply against sprinkler and standpipe demands before a design is committed, size fire pumps and tanks, prepare the sealed hydraulic calculations and pump room drawings for permit, and witness NFPA 20 Chapter 14 acceptance tests for owners. The scope of work and the fee drivers are described on the fire pump design service page and the standpipe design service page, and the kinds of buildings where standpipe pressure governs are described on the commercial high-rise sector page.

Four tools support the first conversation. The Hydrant Flow Test Calculator turns pitot readings into gpm and projects the available flow to 20 psi. The Sprinkler Water Supply Analysis tool plots that test against a sprinkler demand and reports the margin.

The Fire Pump Test Curve Plotter checks an acceptance or annual test against the NFPA 20 churn, rated and 150 percent points. The IFC Appendix B Fire Flow Calculator estimates the site fire flow from building area and construction type where a jurisdiction adopts the appendix.

Key Takeaway: A fire protection water supply is proven, not assumed. A current NFPA 291 flow test defines what the main can deliver; the NFPA 13 Chapter 28 calculation shows whether that clears the sprinkler and standpipe demand with margin; and when it does not, the fix order is redesign, larger service, fire pump and then tank, each under its own standard and each proven by an acceptance test the AHJ witnesses. Settling the supply before the permit is filed is the single largest schedule and cost protection a project has.

Frequently Asked Questions

Does every sprinklered building need a fire pump?

No. A fire pump is required only when the public main, after a current flow test, cannot deliver the sprinkler or standpipe demand at the required pressure with margin, and redesign or a larger service cannot close the gap. Most low-rise buildings on a strong municipal main are designed without a pump; most high-rises need one for the standpipe pressure.

How old can a hydrant flow test be for a sprinkler design?

Conditional: most AHJs and water purveyors in the region accept a test no older than 6 to 12 months at permit, and some require a new test if the main has been worked on since. NFPA 13 (2022) Section 4.5.1.1 limits the test to 12 months before working plan submittal unless the AHJ approves otherwise.

What is the 20 psi residual in a flow test?

The 20 psi residual is the pressure NFPA 291 (2022) uses as the floor when projecting available flow, because fire pumps drawing from a main and hydrants in use are generally kept from pulling the main below that point. The flow available at 20 psi is the standard way to state a main's capacity, and the sprinkler demand is then compared against the full curve.

Is a fire pump the same as a booster pump on the domestic water?

No. A fire pump is a listed pump installed under NFPA 20 with its own controller, power source, test header and acceptance test, dedicated to the fire protection system. A domestic booster pump is a plumbing pump that cannot serve sprinklers or standpipes, and the two are kept on separate services with a backflow preventer on the fire side.

Who pays for and runs the hydrant flow test?

Conditional: the water purveyor runs or witnesses the test in most of New York City, New Jersey and Philadelphia and charges a fee, while in much of Pennsylvania, Maryland and Delaware the sprinkler contractor or engineer runs it with the purveyor's permission. The owner or developer pays in either case, and the test report becomes part of the permit submission.

This guide is general information, not a substitute for a project-specific water supply analysis. Code editions, local amendments, purveyor standards and reviewer practice change; confirm the adopted code and the authority having jurisdiction for each project.

Not Sure the Main Can Carry the Design?

Send the site address, the intended occupancy and any flow test on file. DGA plots the supply against the demand, states whether a pump or tank is needed, and prepares the sealed design and the acceptance test plan. Project briefs get confirmation and preliminary code feedback within one business day.

Send a Project Brief → View Fire Pump Design

Quick inquiry

Ready when you are.

Your name, a way to reach you, and where the project is. One of our licensed PEs replies within one business day. No sales calls.

Prefer to describe it first? Open the Project Desk