Standpipe system design
Standpipes give firefighters, and in some buildings occupants, water access throughout a structure, with system class, pipe sizing, and pressure requirements governed by NFPA 14. DGA Fire Protection Engineering designs standpipe systems for commercial, residential, and mixed-use buildings across New York, New Jersey, Pennsylvania, Maryland, Delaware, Washington, Oregon, and Florida, handling everything from system class selection through hydraulic calculations and coordination with sprinkler and fire pump designs.

What’s Included
What standpipe system design includes
DGA provides standpipe system design for commercial, residential, and mixed-use buildings across New York, New Jersey, Pennsylvania, Maryland, Delaware, Washington, Oregon, and Florida. Our licensed Professional Engineers design systems per NFPA 14, from class selection through hydraulic calculations and coordination with the other fire protection trades.
System class selection
Class I, II, or III systems selected based on building height, occupancy, and AHJ requirements.
Hydraulic calculations
Pressure and flow verified at the most remote hose valves, including pressure-regulating valve needs on lower floors.
Hose valve and riser layout
Locations coordinated with stairs, exits, and fire department access.
Combined systems
Standpipes combined with automatic sprinkler systems where permitted, with demand calculations covering both.
Fire pump coordination
Where supply pressure is insufficient, the standpipe design integrates with the fire pump design.
Standpipe flow testing
Witnessed acceptance flow tests and the documentation the AHJ needs to sign off.
When It Applies
When standpipe system design applies
Triggers
When standpipe design applies
- Mid- & High-Rise Buildings: Buildings with a floor more than 30 feet above the lowest level of fire department vehicle access, where the IBC requires standpipes.
- Large-Footprint & Special Occupancies: Warehouses, covered malls, arenas, and stages where hose travel distance or the occupancy triggers standpipes.
- System Classification: Determining whether a Class I, II, or III and a wet, dry, or automatic system is required before permit.
- Additions & Adaptive Reuse: Vertical additions and renovations that need riser extensions, pump upgrades, or new cross-connections.
What We Deliver
Standpipe engineering & hydraulics
- NFPA 14 Hydraulic Calculations: 500 gpm at the most remote standpipe plus 250 gpm per additional standpipe, at 100 psi residual at the topmost outlet.
- Pressure-Regulating Valve (PRV) Schedules: Static and residual pressure calculations to size and set PRVs where outlet pressures exceed NFPA 14 limits.
- PE-Stamped Riser Diagrams: Riser schematics, cross-connections, isolation and drain valves, and fire pump room piping.
- FDC & AHJ Coordination: Fire department connection location, piping and check valve arrangement, and plan review responses.
This work is common on commercial high-rise, residential, and parking garage and transportation projects.
Process
The design process
01
Determine requirements
Building height, occupancy, and jurisdiction define the system class.
02
Lay out and calculate
Riser locations, hose valve placement, and full hydraulic calculations.
03
Coordinate
Coordination with sprinkler, fire pump, and architectural trades.
04
Document and support
Permit drawings plus plan review and construction support.
FAQ
Frequently asked questions
What is the difference between Class I, II, and III standpipes?
Class I is for fire department use with 2-1/2-inch hose connections, Class II provides 1-1/2-inch hose stations for trained personnel or the fire department during initial response, and Class III combines both. The building’s height and occupancy determine which class is required.
Do standpipes always require a fire pump?
Not always. Whether a pump is required depends on whether the water supply can deliver the required pressures at the highest hose valve. Tall buildings usually need one, and the firm’s hydraulic calculations provide the definitive answer.
Can standpipes share piping with the sprinkler system?
Yes. Combined systems are permitted under NFPA 14 and NFPA 13 in many cases, which can reduce cost. The hydraulic calculations must account for both demands.
Which states are you licensed in?
New York, New Jersey, Pennsylvania, Maryland, Delaware, Washington, Oregon, and Florida. Each project is sealed by a Professional Engineer licensed in the state where it is located.
When does a building need a standpipe?
The building code sets the trigger, usually based on how high the top floor is above fire department vehicle access. The code each state enforces, and New York City’s code, can differ, so DGA confirms the trigger before design starts.
From the Technical Library
Related Services
Related services
Also see PE Inspections & Certification Letters for sealed letters supporting DOB and FDNY sign-off.

Fire pump design
Fire pump selection, sizing, and system design for reliable water supply.

Fire protection engineering design
Integrated sprinkler, alarm, and hydraulic design for new and existing buildings.

Sprinkler shop drawings & hydraulic calculations
Sprinkler shop drawings and hydraulic calculations for installation.