What does NFPA 13D require for a one- or two-family home?

General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.

NFPA 13D, the National Fire Protection Association (NFPA) standard for sprinkler systems in one- and two-family dwellings and manufactured homes, requires listed residential sprinklers throughout the home except in the spaces it lets designers leave out, such as small bathrooms and closets, garages, attics and crawl spaces, and a water supply that can run up to 2 sprinklers in the most demanding compartment, for at least 10 minutes, or 7 minutes in a one-story home under 2,000 sq ft, where stored water is the only source. NFPA 13D does not decide whether a home must have a sprinkler system. The residential code each jurisdiction adopts makes that call, in Section R313 of the International Residential Code (IRC), which the 2024 edition renumbers R309.

As of November 2026 the answer differs across the region. Maryland requires sprinklers in new one- and two-family dwellings and townhouses; New Jersey (for applications submitted on or after July 10, 2024), Pennsylvania and New York State (on a municipal water supply) require them in new townhouses; New York City (NYC) exempts homes of 3 stories or fewer above grade plane that have separate means of egress; and no Delaware county requires them in new one- and two-family homes.

At a Glance: NFPA 13D Home Sprinkler Requirements

  • Threshold(s) with units: the residential code sets the trigger, not NFPA 13D. As of November 2026, new townhouses need sprinklers in Maryland, Pennsylvania, New Jersey (applications submitted on or after July 10, 2024) and New York State (units on a municipal water supply); new one- and two-family dwellings need them in Maryland, in New York State only in the cases the Department of State (DOS) lists, including homes 3 stories or more above grade plane, and in New York City when taller than 3 stories above grade plane or without separate means of egress.
  • Code, edition, section: IRC Section R313 in the 2018 and 2021 editions (Pennsylvania, Maryland, Delaware counties) and R309 in the 2024 edition (New Jersey) and the 2025 Residential Code of New York State (RCNYS); 2022 NYC Building Code Sections 903.2.8 and 903.3.1.3; NFPA 13D in the edition each code references, including 2016 as modified by Appendix Q in New York City and 2025 in Delaware’s State Fire Prevention Regulations.
  • Main exceptions: Pennsylvania excludes Section R313.2 by statute and New Jersey did not adopt the matching 2024 IRC rule, so new one- and two-family dwellings need no sprinklers there; no Delaware county requires them; manufactured homes built to the federal Department of Housing and Urban Development (HUD) code sit outside the Maryland and New York State requirements.
  • What applies once triggered: an NFPA 13D or IRC Section P2904 system with listed residential sprinklers, a design for up to 2 sprinklers flowing, under NFPA 13D a 10-minute supply (7 minutes in a one-story home under 2,000 sq ft) where stored water is the only source, stand-alone or multipurpose piping and no required fire department connection.
  • Permit or filing: the home’s building permit, with a separate sprinkler permit in some Maryland counties; the fire protection subcode section of the construction permit in New Jersey; a Department of Buildings (DOB) filing in New York City.
  • Who decides: the local building official under the adopted residential code, with the fire protection subcode official in New Jersey, DOB in New York City and, in Maryland, the State Fire Marshal’s enforcement duty for new one- and two-family dwellings.

What is NFPA 13D, and which homes does it cover?

NFPA 13D is an installation standard: it sets how a sprinkler system in a one- or two-family dwelling or a manufactured home is designed, installed and tested. Its goal is life safety rather than property protection. A 13D system is meant to keep a fire from reaching flashover in the room where it starts and to give the people inside time to escape, which is why the standard puts sprinklers where people live and sleep and lets some low-risk spaces go without them.

The IRC gives builders two design paths for a dwelling system: NFPA 13D or IRC Section P2904, the residential code’s own sprinkler section. Section P2904.1 treats P2904 as equivalent to NFPA 13D and applies it to both stand-alone and multipurpose wet-pipe systems. New Jersey, Pennsylvania, Maryland and New York State all keep both options.

Homes outside the residential code’s scope, and all other residential buildings, follow the International Building Code (IBC), whose Section 903.3.1 names the NFPA standard each building may use; DGA’s comparison of NFPA 13, 13R and 13D sets out those limits, and its guide to when a building needs fire sprinklers covers the building code triggers. New York City has no residential code, and Section 903.3.1.3 of the 2022 NYC Building Code lets NFPA 13D serve one- and two-family dwellings and townhouses up to 6 stories.

Figure 1: Which standard covers which home

Larger buildings and more stories NFPA 13 Any building at any height, and an option wherever 13R or 13D is allowed Life safety and property protection (IBC 903.3.1.1) NFPA 13R Group R buildings up to 4 stories above grade plane (IBC 903.3.1.2) 2021 IBC: highest floor 30 ft or less above fire department vehicle access 2024 IBC, Group R-2: roof up to 45 ft. New York City: 6 stories and 60 ft NFPA 13D in New York City Homes and townhouses up to 6 stories (NYC Building Code 903.3.1.3) Sprinklers required above 3 stories or without separate egress (903.2.8) NFPA 13D or IRC Section P2904 One- and two-family dwellings and townhouses under the residential code Up to 3 stories above grade plane, separate means of egress (IRC R101.2) Whether sprinklers are required: IRC R313 (2018, 2021) or R309 (2024)
Under the residential code, one- and two-family dwellings and townhouses up to 3 stories above grade plane with separate means of egress use NFPA 13D or IRC Section P2904, and IRC Section R313 (R309 in the 2024 edition) decides whether they must be sprinklered. New York City allows NFPA 13D in homes and townhouses up to 6 stories, NFPA 13R covers Group R buildings up to 4 stories within the IBC 903.3.1.2 height tests (6 stories and 60 ft in New York City), and NFPA 13 covers any building.

When does a new home or townhouse need sprinklers in each state?

The residential code sets the trigger, and each jurisdiction in the region has edited the model rule. The 2021 IRC requires an automatic sprinkler system in townhouses (Section R313.1) and in one- and two-family dwellings (Section R313.2), and the 2024 IRC moved the same rules to Section R309 without changing their content. The table gives the status for new construction in each jurisdiction as of November 2026.

JurisdictionResidential code and editionNew one- and two-family dwellingsNew townhousesNFPA 13D edition
New York State (outside NYC)2025 RCNYS, Title 19 of the New York Codes, Rules and Regulations (NYCRR) Part 1220, on the 2024 IRC; sprinkler section R309Required only in the cases DOS lists: live/work units, owner-occupied lodging houses, and dwellings 3 stories or more above grade planeRequired in every new unit served by a municipal water supply system, at any number of stories; DOS also lists units 3 stories or more above grade plane on any supplyThe edition the 2025 RCNYS references
New York City2022 NYC Building Code (no residential code)Exempt when detached, not more than 3 stories above grade plane and with separate means of egress (Section 903.2.8); otherwise requiredExempt when not more than 3 stories above grade plane and with separate means of egress (Section 903.2.8); otherwise required2016, as modified by Building Code Appendix Q, Q103; permitted up to 6 stories (Section 903.3.1.3)
New JerseyOne- and two-family dwelling subcode, New Jersey Administrative Code (N.J.A.C.) 5:23-3.21, on the 2024 IRC since August 17, 2026; sprinkler section R309Not required: the Department of Community Affairs (DCA) did not adopt the IRC requirementRequired where the construction permit or development application was submitted on or after July 10, 2024The edition the 2024 IRC references
Pennsylvania2021 IRC through the Uniform Construction Code (UCC), since January 1, 2026; sprinkler section R313Not required: Act 45 section 901(g) excludes R313.2; the builder must offer a system at the buyer’s costRequired under R313.1The edition the 2021 IRC references
Maryland2021 IRC through the Maryland Building Performance Standards, Code of Maryland Regulations (COMAR) 09.12.51; sprinkler section R313Required (R313.2); counties may not weaken the rule (Public Safety Article 12-504)Required (R313.1)The edition the 2021 IRC references; Montgomery County adopts NFPA 13D (2019)
DelawareIRC adopted county by county: 2021 in Sussex, 2018 in Kent and Wilmington; sprinkler section R313Not required in any county; the builder must inform the buyer and install a system on request (Title 6, sections 3681 to 3683)Exempt in Sussex County (Ordinance 2851); optional in Kent County (County Code Chapter 105)2025 in the State Fire Prevention Regulations (Regulation 701 section 3.1.8)

Status for new construction as of November 2026. Municipal codes and local amendments are not shown, and a home outside the residential code’s scope follows the building code.

Maryland is the strictest. The Maryland Building Performance Standards adopt Section R313 unchanged, Public Safety Article 12-504 has barred local amendments that weaken it since October 1, 2012, and Public Safety Article 6-305(a)(3) makes the State Fire Marshal enforce the installation rules in new one- and two-family dwellings. DGA’s article on Maryland’s sprinkler law for new homes covers the history and the county process.

New Jersey and Pennsylvania split the rule. New Jersey’s townhouse requirement comes from P.L.2023, c.265 and P.L.2024, c.42, which DCA wrote into the one- and two-family dwelling subcode in R.2025 d.111, and it covers townhouses whose construction permit or development application was submitted on or after July 10, 2024. Pennsylvania’s Construction Code Act (Act 45 of 1999, section 901(g)) removes Section R313.2 but leaves R313.1 in force, so new townhouses built under the IRC are sprinklered while the builder of a one- or two-family dwelling only has to offer a system at the buyer’s cost, with information on its cost and benefits.

The 2025 RCNYS requires sprinklers in every new townhouse unit served by a municipal water supply system, whatever its number of stories. For one- and two-family dwellings it keeps the 2020 provisions, which DOS describes as requiring sprinklers only in live/work units, owner-occupied lodging houses, and new dwellings and townhouse units 3 stories or more above grade plane. In New York City, Section 903.2.8 of the Building Code exempts homes and townhouses of 3 stories or fewer above grade plane with separate means of egress, so taller homes need sprinklers.

No Delaware county requires sprinklers in new one- and two-family homes. Sussex County’s Ordinance 2851 exempts one- and two-family dwellings and townhouses, and Kent County Code Chapter 105 makes a residential system optional in both. Delaware’s New Home Buyers Fire Protection Act (Title 6 of the Delaware Code, sections 3681 to 3683) requires the builder of a new one- or two-family dwelling to give the buyer State Fire Marshal information on sprinkler benefits and costs and to install a system at the buyer’s expense on request.

How is a home’s sprinkler status determined, and what are the exceptions?

Four facts settle a home’s sprinkler status on a given lot. The first is the code path: a detached one- or two-family dwelling or townhouse stays under the residential code only while it is not more than 3 stories above grade plane and each unit has a separate means of egress (IRC Section R101.2; in New York State, 19 NYCRR 1220.2(a)), and a larger home goes to the building code. The second is the filing date, which decides the New Jersey townhouse rule and which code edition applies wherever a new edition has just taken effect.

The third fact is the water supply. New York State’s 2025 townhouse rule applies only where a municipal water supply system serves the units, and DOS declined to extend it to townhouses without one, citing the cost of on-site tanks and pumps. The fourth is whether the work is new: the requirements in the table cover new dwellings, and RCNYS Appendix BO (formerly Appendix J) adds sprinklers, for townhouses on municipal water, where new units are added to an existing townhouse or an addition increases a townhouse unit’s floor area by more than 50 percent.

Exceptions follow the dwelling type and the state. Manufactured (HUD-code) homes sit outside Maryland’s requirement, and DOS added a manufactured home exception to the 2025 RCNYS so it would not conflict with HUD standards. Maryland also lets a county relax the rule for a property not connected to an electrical utility (Public Safety Article 12-504), the only local weakening State law still allows.

The design alternatives all meet or exceed the residential minimum. New Jersey’s DCA confirmed in adopting its townhouse rule that an NFPA 13R or NFPA 13 system may replace a 13D or P2904 system, because the code sets a minimum. A home outside the mandate can still be sprinklered voluntarily, and in Pennsylvania and Delaware the builder must give the buyer that choice.

Opens the Project Desk with your sentence. Our licensed PEs review every brief and reply within one business day.

What does a 13D system have to deliver: Design sprinklers, flow and duration?

NFPA 13D sizes a home system for a small, early fire rather than for the whole house. The hydraulic design assumes up to 2 sprinklers flowing in the most demanding compartment, each at the greater of its listed flow and a density of 0.05 gallons per minute per sq ft (NFPA 13D (2025) Sections 10.2.1 and 10.1.1), and where stored water is the only source, the supply has to hold that flow for at least 10 minutes, or 7 minutes in a one-story dwelling under 2,000 sq ft (Sections 6.1.2 and 6.1.3). The sprinklers must be listed residential sprinklers installed within the spacing and coverage limits of their listing (Chapters 7 and 8).

NFPA 13D accepts several water supplies: a connection to a public water system with or without a pump, an elevated tank, a pressure tank, stored water with an automatic pump, or a well with a pump that can meet the sprinkler demand (Chapter 6). Many homes on wells pair the well pump with a storage or pressure tank. DGA’s guide to when a well or private source can supply fire protection covers the well side, and the fire sprinkler pressure tank calculator works out the air pressure and water volume a pressure tank needs.

Local reviewers add their own checks on the supply. Montgomery County, Maryland requires a 10 percent safety factor on NFPA 13D calculations unless a pump would then be needed, asks for the Washington Suburban Sanitary Commission (WSSC) low and high hydraulic gradients, and accepts pumps or tanks on public water only after other design options are ruled out. Elsewhere, the authority having jurisdiction (AHJ) or an insurer may require a margin. The table summarizes the standard’s main requirements.

TopicNFPA 13D requirement (paraphrased)Edition and section
Design sprinklersUp to 2 sprinklers flowing in the most demanding compartment, each at the greater of its listed flow and 0.05 gallons per minute per sq ftNFPA 13D (2025) Sections 10.2.1 and 10.1.1
Water supply durationWhere stored water is the only source: at least 10 minutes; 7 minutes for a one-story dwelling under 2,000 sq ftNFPA 13D (2025) Sections 6.1.2 and 6.1.3
Water supply sourcesPublic water with or without a pump, an elevated tank, a pressure tank, stored water with an automatic pump, or a well with a pump that meets the demandNFPA 13D (2025) Chapter 6
SprinklersListed residential sprinklers, within their listed spacing and coverageNFPA 13D (2025) Chapters 7 and 8
Spaces without sprinklersBathrooms of 55 sq ft or less; closets and pantries of 24 sq ft or less with noncombustible or limited-combustible walls and ceilings; garages, carports and open attached porches; attics (with or without storage) and crawl spaces not used for livingNFPA 13D (2022) Section 8.3; in New York City, 2016 Sections 8.3.4 and 8.3.5 as modified by Q103
AntifreezeListed antifreeze solutions only, in new systemsNFPA 13D (2025) Chapter 9
Multipurpose pipingOne piping network may serve the plumbing fixtures and the sprinklersNFPA 13D (2025) Sections 3.3.13.3 and 6.3
Fire department connectionNot requiredNFPA 13D (2025)
Acceptance testsHydrostatic test, pump test where a pump is used, and operational testNFPA 13D (2025) Chapter 11

Paraphrased by DGA, not NFPA text. Chapter numbers are from the 2025 edition, which Delaware adopts; other jurisdictions apply the edition their code references.

Which rooms and spaces may a 13D system leave without sprinklers?

NFPA 13D calls for sprinklers throughout the dwelling except where Chapter 8 allows them to be left out, and that list is short. Chapter 8 lets designers omit sprinklers in bathrooms of 55 sq ft or less; clothes closets, linen closets and pantries of 24 sq ft or less with noncombustible or limited-combustible walls and ceilings; garages, carports and open attached porches; and attics (with or without storage), crawl spaces and other concealed spaces not used for living. Each omission comes with conditions, so a closet holding a washer, dryer, water heater or heating and cooling equipment needs a sprinkler, and an attic finished as a room no longer qualifies.

Local amendments change the list in places. In New York City, Building Code Appendix Q section Q103 changes two of these provisions in NFPA 13D (2016): the attic provision is limited to attics without floors, and the garage provision depends on at least one sprinkler within 3 ft of any opening between the garage and the dwelling. Other local amendments can add requirements of their own.

Stand-alone or multipurpose: How is a 13D system piped and supplied?

A 13D system is piped one of two ways. A stand-alone system has its own piping that serves only the sprinklers, while a multipurpose system uses one network of household water piping to feed both the plumbing fixtures and the sprinklers. NFPA 13D (2025) defines the multipurpose piping system in Section 3.3.13.3 and sets its rules in Section 6.3, and IRC Section P2904 covers both arrangements for wet-pipe systems.

Figure 2: Stand-alone vs multipurpose 13D piping

Stand-alone system
  • Its own piping network serves only the sprinklers
  • Connects to the water service and can be separated from the drinking water by a backflow preventer
  • Can hold listed antifreeze where pipes run through unheated space
  • Backflow rules come from the plumbing code and the water purveyor; Maryland deletes the IRC P2904.1 exemption
Multipurpose system
  • One network of household piping feeds the fixtures and the sprinklers (NFPA 13D (2025) 3.3.13.3 and 6.3)
  • No second piping network to install
  • No antifreeze, because the piping carries drinking water
  • Pipe, meter and service sized for sprinkler flow; softeners, filters or shutoff valves added later can restrict it
  • New York City: Appendix Q deletes the NFPA 13D (2016) multipurpose piping section (6.3) and allows a shared supply main only where domestic flow stops when sprinklers operate (Q103)
A stand-alone NFPA 13D system runs separate sprinkler piping that can hold listed antifreeze and be separated from the drinking water by a backflow preventer, while a multipurpose system feeds fixtures and sprinklers through one network of drinking-water piping, defined in NFPA 13D (2025) Section 3.3.13.3 and governed by Section 6.3. In New York City, Appendix Q deletes the NFPA 13D (2016) multipurpose piping section (6.3) and allows a shared supply main only where domestic flow stops when the sprinklers operate.

Backflow protection for a stand-alone system is a plumbing code and water purveyor question. The model IRC Section P2904.1 excuses a backflow preventer for a dwelling system that meets NFPA 13D or P2904, uses Section P2906 piping, holds no antifreeze and has no fire department connection, but Maryland deletes that sentence in COMAR 09.12.51.04C(6). In New York City, Appendix Q allows a common supply main for sprinklers and domestic use only where domestic flow stops when the sprinklers operate.

NFPA 13D does not require a fire department connection on a home system. The standard accepts only listed antifreeze solutions in new systems (Chapter 9), and antifreeze is a stand-alone option, since a multipurpose system’s piping carries drinking water. In New York City, Appendix Q requires 13D antifreeze supply piping to follow NFPA 13 (2016) as modified for New York City.

What happens at permit, inspection and testing for a 13D system?

In most of the region the sprinkler system is part of the home’s building permit, with a separate sprinkler permit in some Maryland counties. NFPA 13D (2025) Chapter 11 sets the acceptance tests for a new system: a hydrostatic test of the piping, a pump test where a pump is used and an operational test of the system. The table shows who reviews and inspects a home sprinkler system in each jurisdiction as of November 2026.

JurisdictionWho reviews and inspectsPermit and sign-offDesigner and installer rules
New York State (outside NYC)The local code enforcement official of the city, town or village, or the county or DOS where a locality opts out (19 NYCRR Part 1203)Building permit; certificate of occupancy or certificate of compliance (19 NYCRR 1203.3(d))Construction documents carry a New York architect’s or engineer’s seal unless an Education Law exemption applies (19 NYCRR 1203.3(a)(3))
New York CityDOBDOB filing in DOB NOW: BuildValve supervision not required on systems protecting one- and two-family dwellings (Building Code Section 903.4)
New JerseyFire protection subcode official for Section R309 work; the construction official issues the permitConstruction permit; certificate of occupancy for a new home; minor work notice for suppression devices in an existing one- or two-family dwelling (N.J.A.C. 5:23-2.17A)Plans sealed by an architect or engineer, with exceptions that include an owner’s plans for the owner’s own detached single-family home (N.J.A.C. 5:23-2.15(f))
PennsylvaniaMunicipal building code official or the municipality’s third-party agency; Department of Licenses and Inspections (L&I) in PhiladelphiaUCC building permit; certificate of occupancy, and in Philadelphia a separate fire suppression permit closed with a Certificate of ApprovalNo statewide sprinkler contractor license; Philadelphia and Pittsburgh license fire suppression contractors
MarylandCounty or municipal permit office; the State Fire Marshal enforces installation rules in new one- and two-family dwellings (Public Safety Article 6-305(a)(3))Residential building permit, plus a separate sprinkler permit where the county issues oneState Fire Marshal contractor license; layout by a National Institute for Certification in Engineering Technologies (NICET) Level II or higher qualified individual or a Maryland professional engineer (PE) (COMAR 29.06.05)
DelawareCounty or municipal building official for the home; State Fire Marshal review of a voluntary system depends on that office’s submittal rulesBuilding permit; certificate of occupancy from the county or cityInstaller holds a State Fire Marshal Class IV license

As of November 2026. County and municipal practice varies, especially in Maryland and Delaware.

New Jersey assigns residential sprinkler work under Section R309 to the fire protection subcode for plan review and inspection, so the fire protection subcode official reviews the sprinkler sheets and the construction official issues the permit and the certificate of occupancy. Installing fire suppression devices in an existing one- or two-family dwelling is minor work under N.J.A.C. 5:23-2.17A: a permit is still required, but work may start after notice to the enforcing agency, with the application following within 5 business days.

Maryland licenses the companies that lay out and install home systems under COMAR 29.06.05, including a Class IId license limited to installing NFPA 13D systems. Residential layouts are supervised by the contractor’s designated qualified individual with NICET Level II or higher in sprinkler layout, or equivalent, or by a Maryland registered PE, and multipurpose piping that carries drinking water also needs a licensed master plumber.

Key Takeaway: NFPA 13D sets how a home sprinkler system is built: listed residential sprinklers everywhere except the few spaces it lets designers omit, a design for up to 2 sprinklers flowing, and, where stored water is the only source, a supply that lasts 10 minutes, or 7 minutes in a one-story home under 2,000 sq ft. The residential code decides whether a home needs one, and as of November 2026 Maryland requires sprinklers in new one- and two-family dwellings and townhouses, New Jersey (applications on or after July 10, 2024), Pennsylvania and New York State (units on a municipal water supply) require them in new townhouses, New York City requires them in homes taller than 3 stories above grade plane or without separate means of egress, and no Delaware county requires them in one- and two-family homes.

Frequently asked questions

Do new single-family homes need sprinklers in New Jersey?

No. New Jersey has not adopted the IRC sprinkler requirement for one- and two-family dwellings, and DCA left it out again when the one- and two-family dwelling subcode moved to the 2024 IRC on August 17, 2026. New townhouses are different: those with a construction permit or development application submitted on or after July 10, 2024 must be sprinklered under IRC Section P2904 or NFPA 13D (Section R309.1 as adopted in New Jersey).

Can a 13D system be fed from a private well?

Yes. NFPA 13D accepts a well with a pump that can meet the sprinkler demand as a water supply, and many homes pair the well pump with a pressure or storage tank. Where stored water is the only source, NFPA 13D requires enough for 10 minutes of flow, or 7 minutes in a one-story home under 2,000 sq ft. The pump and tank then become part of the sprinkler system’s design and acceptance tests.

Does a 13D system need a fire department connection?

No. NFPA 13D does not require a fire department connection on a home system. Under the model IRC, a dwelling system with a fire department connection also loses the Section P2904.1 exemption from a backflow preventer, an exemption Maryland deletes for every home system.

Can a home sprinkler system share the domestic water piping?

Yes. NFPA 13D and IRC Section P2904 both allow a multipurpose system, in which one network of household piping feeds the plumbing fixtures and the sprinklers (NFPA 13D (2025) Sections 3.3.13.3 and 6.3). The piping, meter and service must be sized for the sprinkler flow, and in New York City, Appendix Q deletes the NFPA 13D (2016) multipurpose piping section and allows a shared supply main only where domestic flow stops when the sprinklers operate.

Does an attached garage need sprinklers under NFPA 13D?

No. NFPA 13D lets garages, carports and open attached porches go without sprinklers. In New York City, Appendix Q ties the garage provision to at least one sprinkler within 3 ft of any opening between the garage and the dwelling, and a local amendment can require more.

This article is general information, not a code determination for any project. Code editions, local amendments and reviewer practice change; confirm the adopted code and the reviewing office for each project.

Planning a Sprinklered Home or Townhouse Project?

Send the jurisdiction, the dwelling type, the number of units and the water service or well details. DGA checks whether the residential code requires sprinklers, prepares the sprinkler design and hydraulic calculations, and answers review comments. Project briefs get confirmation and preliminary code feedback within one business day.

Send a project brief → View related services

Leave a reply

Your email address will not be published. Required fields are marked *

Quick inquiry

Ready when you are.

Your name, a way to reach you, and where the project is. A licensed PE replies within one business day. Every inquiry is confidential.

Prefer to describe it first? Open the Project Desk

FirmDGA Fire Protection Engineering
SheetFP-5192
OfficesNew York · Harrisburg · Seattle
LicensedNY NJ PA MD DE WA OR FL
Rev11.2026
Sheet index