Sprinkler Systems · Trigger
Do balconies and decks need sprinklers under NFPA 13R?
General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.
In a building sprinklered to NFPA 13R, the National Fire Protection Association (NFPA) standard for low-rise residential buildings, balconies, decks and ground-floor patios need sprinklers when they serve dwelling or sleeping units in a Type V building with a roof or deck above them, or when a combustible balcony on a Type III, IV or V building skips its fire-resistance rating because sprinklers are extended to it. Both cases come from Section 903.3.1.2.1 of the 2021 International Building Code (IBC), and Section 903.3.1.2.2 adds corridors and egress balconies, the open breezeways of many garden apartment buildings, under five conditions. New York City and Delaware write their own rules, and Delaware’s reaches every porch, balcony and deck of a residential building other than a one- or two-family dwelling.
NFPA 13R lets designers leave sprinklers out of some spaces open to the outside air; the IBC puts many of them back, and where it is stricter, the code governs. The other systems an apartment building needs are covered in DGA’s guide to the fire protection a multifamily building needs.
At a Glance: Balcony and Deck Sprinklers in NFPA 13R Buildings
- Threshold(s) with units: 2021 IBC Section 903.3.1.2.1: any balcony, deck or ground-floor patio of a dwelling or sleeping unit in a Type V building with a roof or deck above, at any size, and any combustible balcony left unrated under Section 705.2.3.1, Exception 3; Section 903.3.1.2.2: corridors and egress balconies meeting one of five conditions, such as a corridor with combustible floor or walls or ends less than 50 percent open; NFPA 13R (2022): a roof, deck or balcony more than 4 ft wide above; NFPA 13: projections more than 4 ft wide.
- Code, edition, section: IBC Sections 903.3.1.2.1, 903.3.1.2.2 and 705.2.3.1 and Table 601 (2021 text; each jurisdiction’s edition is in the state table); NFPA 13R (2022) Section 6.6.5; NFPA 13 (2022) Sections 9.2.3, 9.3.19 and 9.3.20.1; 2022 New York City Building Code Sections 903.3.1.2.1 and 903.3.1.2.2; Delaware Regulation 702, Chapter 4, Section 1.3.1.
- Main exceptions: Type I and II buildings; Type III and IV buildings whose balconies are noncombustible, fire-retardant-treated wood, heavy timber or rated; Type V balconies with open sky above that need no rating. Delaware has none for residential buildings other than one- and two-family dwellings.
- What applies once triggered: listed sprinklers, most often dry sidewall sprinklers fed from the heated unit, with deflectors 1 to 6 inches below the structural members and, under open wood joists, no more than 14 inches below the deck; freeze protection for anything outside the heated envelope.
- Permit or filing: the sprinkler shop drawings show the balcony, deck and breezeway sprinklers, and the architectural drawings show the construction type and how each balcony is built; in Delaware, the State Fire Marshal’s water-based fire suppression system application and Preliminary Sprinkler Form.
- Who decides: the building official approves the construction type and balcony construction; the authority having jurisdiction (AHJ) for sprinkler plans checks coverage: the Department of Buildings (DOB) in New York City, the fire protection subcode official in New Jersey, county reviewers in Maryland, local code officials in New York State and Pennsylvania, and the State Fire Marshal or a city fire marshal in Delaware.
When do balconies and decks need sprinklers in an NFPA 13R building?
IBC Section 903.3.1.2 permits NFPA 13R in Group R occupancies within its story and height limits, and its subsections add protection the standard alone would not provide. Section 903.3.1.2.1 of the 2021 IBC requires sprinklers for exterior balconies, decks and ground-floor patios of dwelling units and sleeping units where the building is Type V construction with a roof or deck above, or where the balcony is built under Section 705.2.3.1, Exception 3. Whether a building may use NFPA 13R at all is a separate question, which DGA’s comparison of NFPA 13, 13R and 13D answers.
NFPA 13R (2022) has its own rule in Section 6.6.5.1: in Type V construction, attached balconies, decks and ground-floor patios directly serving dwelling units get sprinklers where a roof, deck or balcony more than 4 ft wide is above them, and the 2019 edition used in Pennsylvania and the Maryland county permits sets no width for the roof or deck above. The IBC test is broader, with no width for the roof or deck above, sleeping units included and a second condition that reaches Types III and IV. The table lists each case, as of November 2026.
| Space or condition in a building on NFPA 13R | Sprinklers required? | Section |
|---|---|---|
| Balcony, deck or ground-floor patio of a dwelling or sleeping unit, Type V building, roof or deck above | Yes, at any size and of any material | 2021 IBC 903.3.1.2.1, item 1 |
| Combustible balcony on a Type III, IV or V building left unrated under the projection exception | Yes | 2021 IBC 903.3.1.2.1, item 2; 705.2.3.1, Exception 3 |
| Combustible balconies longer in total than 50 percent of the perimeter on a floor | Yes, to exceed the length limit | 2021 IBC 705.2.3.1, Exception 4 |
| Type V balcony with open sky above that needs no rating (Type VB) | Not under the IBC | 2021 IBC 903.3.1.2.1 |
| Balcony on a Type I or II building, or a noncombustible, fire-retardant-treated wood, heavy timber or rated balcony on a Type III or IV building | Not under the IBC | 2021 IBC 903.3.1.2.1; 705.2.3.1 |
| Corridor or egress balcony (breezeway) meeting any of five conditions | Yes | 2021 IBC 903.3.1.2.2 |
| Type V, attached balcony, deck or ground-floor patio of a dwelling unit, with a roof, deck or balcony more than 4 ft wide above | Yes | NFPA 13R (2022) Section 6.6.5.1 |
| New York City: dwelling unit balcony, deck or ground-floor patio, Type V building | Yes, with no roof-above condition | 2022 New York City Building Code 903.3.1.2.1 |
| Delaware: porch, balcony, deck, corridor or stair of a residential building other than a one- or two-family dwelling | Yes, open or not | Regulation 702, Chapter 4, Section 1.3.1.3 |
Paraphrased by DGA from the 2021 IBC, NFPA 13R (2022), the 2022 New York City Building Code and Delaware Regulation 702, not code text. The state table below shows which edition applies in each jurisdiction.
Which construction types trigger the balcony rule?
Construction type decides the first condition. Type V is the construction type of most wood-frame apartment buildings, and on a Type V building every balcony, deck and ground-floor patio of a dwelling or sleeping unit with a roof or deck above gets sprinklers, whatever its size or material. On a podium building under IBC Section 510.2, the building above the podium counts as a separate building for type of construction, so a Type V structure over a Type IA podium follows the Type V rule.
The second condition comes from the rules for combustible projections. Under 2021 IBC Section 705.2.3.1, a combustible balcony other than fire-retardant-treated wood must carry the rating Table 601 sets for the building’s floors or be heavy timber, and such balconies may run no more than 50 percent of the perimeter on each floor. Exception 3 lets a balcony on a Type III, IV or V building be unrated Type V construction where sprinklers are extended to it, and Exception 4 lifts the length limit where sprinklers extend to the balconies.
Table 601 rates floors at 1 hour in Types IIIA and VA, 2 hours in Types IV-A to IV-C and heavy timber in Type IV-HT, with no rating in Types IIIB and VB. An untreated wood balcony on a Type IIIA or VA building that is neither rated nor heavy timber therefore relies on Exception 3 and needs sprinklers even on a top floor with open sky above, while a combustible balcony on a Type VB building needs no rating and answers only to item 1, and one on a Type IIIB building answers to neither. Type I and II buildings fall outside both conditions.
Figure 1: Does the balcony need sprinklers under the 2021 IBC?
How are balconies, decks, patios and breezeways measured and sorted?
The IBC sorts these spaces by whom they serve. Section 903.3.1.2.1 covers balconies, decks and ground-floor patios of dwelling and sleeping units, the private outdoor space of an apartment or room, while a breezeway or open walkway that several units use to reach the exits is part of the means of egress and falls under Section 903.3.1.2.2. For a balcony, the drawings need to show the construction type, whether a roof or deck sits above and whether the balcony relies on Exception 3.
The IBC sets no minimum size for the roof or deck above, so a balcony under another balcony qualifies, and so does a ground-floor patio once a deck projects over it. NFPA 13R (2022) applies its own rule only where the roof, deck or balcony above is more than 4 ft wide.
Section 903.3.1.2.2 of the 2021 IBC requires sprinklers in corridors that have combustible floor or walls, an interior change of direction of more than 45 degrees or ends less than 50 percent open to the outside, in open-ended corridors with exterior stairways and ramps under Section 1027.6, Exception 3, and on egress balconies that do not comply with Sections 1021.2 and 1021.3. In a Type V building the first condition usually settles it, because a wood-framed breezeway has combustible floors and walls. The International Code Council (ICC) added this scoping in 2021 because NFPA 13R lets sprinklers be left out of many spaces open to the outside; NFPA 13R (2022) also calls for protection of balconies and corridors that are part of the means of egress (Section 6.6.5.2).
New York City’s Section 903.3.1.2.2 is narrower, requiring sprinkler and freeze protection in open-ended corridors and their exterior stairways and ramps under Section 1027.6, Exception 3. Delaware requires sprinklers in the corridors and stairs of residential buildings other than one- and two-family dwellings, open or not (Regulation 702, Chapter 4, Section 1.3.1.3).
DGA prepares NFPA 13R and NFPA 13 sprinkler shop drawings for apartment buildings, including the balcony, deck and breezeway protection the code adds, across New York, New Jersey, Pennsylvania, Maryland, Delaware, Washington, Oregon and Florida. Project briefs get confirmation and preliminary code feedback within one business day. See where DGA works →
Which exceptions apply to balcony sprinklers in a 13R building?
Noncombustible balconies are the most common point of confusion. Item 1 of Section 903.3.1.2.1 turns on the building’s construction type, not the balcony’s material, so a steel or concrete balcony on a Type V building with a roof or deck above is covered as written, while a noncombustible balcony on a Type III or IV building does not rely on Exception 3 and falls outside the section. The section has no size exception either.
Roof overhangs raise the opposite question on the top floor. The IBC names no width for the roof above, so an eave over a top-floor balcony can count as a roof, and the AHJ decides how much coverage is enough; NFPA 13R (2022) looks for a roof more than 4 ft wide. New York City and Delaware apply no roof-above condition at all.
Storage closets on a balcony are a related trap. Delaware requires sprinklers in closets on exterior balconies, whether or not they open directly into the dwelling unit (Regulation 702, Chapter 4, Section 1.3.1.4), and DGA’s guide to closet, bathroom and small room sprinklers covers the size allowances for closets inside dwelling units.
The ways around balcony sprinklers each change the building. Rated, heavy timber, fire-retardant-treated wood or noncombustible balconies remove item 2 but not item 1 on a Type V building, and an NFPA 13 design brings that standard’s projection rules instead. In Delaware, the Fire Marshal also evaluates every NFPA 13R omission and may disapprove one that, in the Fire Marshal’s opinion, leaves an inadequate level of fire safety (Regulation 702, Chapter 4, Section 1.3.1, Exception 2).
Which sprinklers and piping protect a balcony once the rule applies?
Every exterior balcony in New York, New Jersey, Pennsylvania, Maryland and Delaware sees freezing weather, so water-filled piping cannot simply run out onto it. The usual answer is a dry sidewall sprinkler on the exterior wall, whose sealed barrel passes through the wall to the wet branch line inside the heated unit, so no water stands in the cold section. The sprinkler must be listed for the use and installed within its listing, which sets its coverage and how far it throws across the balcony.
The IBC helps with placement: sidewall sprinklers protecting these balconies and decks may sit with their deflectors 1 to 6 inches below the structural members and, under open wood joists, no more than 14 inches below the deck (2021 IBC Section 903.3.1.2.1, with the same allowance in the 2022 New York City Building Code). Dry sprinklers are made to length, and the length has to suit the wall and the manufacturer’s minimum exposed length, so the wall section should be settled before ordering.
Figure 2: Dry sidewall sprinkler under a balcony above
A closed soffit under the balcony framing creates a concealed space, and DGA’s guide to when concealed spaces and attics need sprinklers explains how NFPA 13 and 13R treat it. An antifreeze loop is the other way to protect a cold balcony from a wet system: NFPA 25 (2023), the edition Delaware and the Maryland State Fire Prevention Code use, requires listed antifreeze solutions with narrow exceptions, and New York City’s Appendix Q allows only glycerin-type antifreeze in NFPA 13R systems with nonmetallic pipe or fittings (Section Q104).
How does NFPA 13 treat the same balcony?
Section 903.3.1.2.1 sits under the IBC’s NFPA 13R provisions, so in an NFPA 13 building the standard’s own rules decide. Under NFPA 13 (2022) Section 9.3.19.1, sprinklers go under exterior roofs, canopies, balconies, decks and similar projections more than 4 ft wide unless the projection is noncombustible, limited-combustible or fire-retardant-treated wood with nothing combustible stored below, or is wood framed with a qualifying finish and concealed spaces. Combustibles stored under a projection more than 4 ft wide cancel those omissions, whatever the projection is built of (Sections 9.2.3.4 and 9.3.19.2).
The 2022 edition added a rule similar to NFPA 13R’s for balconies serving dwelling units in Type V construction (NFPA 13 (2022) Section 9.3.20.1), while the 2016 edition used in New York City and the 2019 edition in Pennsylvania and the Maryland county permits rely on the projection rule alone. Choosing NFPA 13 for a wood-frame building therefore swaps one set of balcony rules for another; it does not by itself take sprinklers off the balconies. The table compares the two paths.
| Question | NFPA 13 building | NFPA 13R building, with IBC Section 903.3.1.2 |
|---|---|---|
| What sets the rule | Chapter 9 exterior projection rule (Section 9.3.19.1), plus a 2022 rule for Type V dwelling unit balconies (Section 9.3.20.1) | IBC Sections 903.3.1.2.1 and 903.3.1.2.2, plus NFPA 13R’s own rule (2022, Section 6.6.5.1) |
| Width test | Projection more than 4 ft wide | None in the IBC; NFPA 13R (2022): roof, deck or balcony above more than 4 ft wide |
| Type V dwelling unit balcony | Falls under the 2022 rule; under the 2016 and 2019 editions, sprinklered when more than 4 ft wide and not exempt | Covered with a roof or deck above, or under Exception 3 |
| Noncombustible balcony, nothing stored below | May be omitted under the projection rule, the 2022 Type V rule aside | Covered on a Type V building with a roof or deck above |
| Combustibles stored below | Sprinklered under a projection more than 4 ft wide, whatever it is built of | Not a factor in the IBC text |
| Closed soffit under the balcony | Concealed space under the Chapter 9 rules | May stay unsprinklered under NFPA 13R if not used for living or storage |
Paraphrased by DGA from NFPA 13 (2022), NFPA 13R (2022) and the 2021 IBC, not standard or code text. Each omission carries further conditions in the standard.
How do New York, New Jersey, Pennsylvania, Maryland and Delaware apply the balcony rules?
The IBC sections apply in the edition each jurisdiction adopts, and NFPA 13R follows the local edition, as of November 2026. New York City and Delaware add text of their own, and the table gives the code path, the local rule worth knowing and the reviewer for each.
| Jurisdiction | Code path | Local rule worth knowing | Reviewer and filing |
|---|---|---|---|
| New York State (outside New York City) | 2025 Building Code of New York State (BCNYS), based on the 2024 IBC, in effect since December 31, 2025; NFPA 13R in the edition the BCNYS references | No Chapter 9 amendment in the 2025 rule text (Title 19 of the New York Codes, Rules and Regulations (NYCRR), Part 1221), so the 2024 IBC rules under Section 903.3.1.2 apply | Local code enforcement official; building permit with construction documents sealed by a New York licensed architect or engineer (19 NYCRR 1203.3(a)) |
| New York City | 2022 New York City Building Code; NFPA 13R (2016) as modified by Appendix Q; NFPA 13R allowed in Group R buildings up to six stories (Section 903.3.1.2) | Section 903.3.1.2.1: dwelling unit balconies, decks and ground-floor patios of Type V buildings, no roof-above condition, same sidewall allowance; Section 903.3.1.2.2: sprinkler and freeze protection in open-ended corridors and their exterior stairways and ramps | DOB; sprinkler (SP) work type in DOB NOW: Build |
| New Jersey | Uniform Construction Code (UCC) on the 2024 IBC since August 17, 2026, with complete applications under the 2021-based codes accepted through February 17, 2027; NFPA 13R in the edition the 2024 IBC references | No amendment to Section 903.3.1.2 or its subsections; Section 903.1.2 gives NFPA 13R systems no code reduction unless the code names them, so check it before using 13R balcony sprinklers to drop a Section 705 rating | Fire protection subcode official; construction permit with the fire protection technical section (New Jersey Administrative Code (N.J.A.C.) 5:23) |
| Pennsylvania | Pennsylvania Uniform Construction Code on the 2021 IBC since January 1, 2026; NFPA 13R (2019) | Sections 903.3.1.2.1 and 903.3.1.2.2 as published; the only statewide Chapter 9 change, to Section 903.3.1.2, holds Group R-2 buildings on NFPA 13R to a roof assembly under 45 ft | Municipal building code official, third-party agency or the state Department of Labor and Industry (L&I); in Philadelphia, the Department of Licenses and Inspections Fire Suppression Systems Permit; in Pittsburgh, the Department of Permits, Licenses, and Inspections Suppression Systems Permit |
| Maryland | 2021 IBC through the Maryland Building Performance Standards (Code of Maryland Regulations (COMAR) 09.12.51) and the county permit; NFPA 13R (2019); NFPA 1 (2024) references the 2022 edition | No state amendment to Section 903; the Montgomery County Department of Permitting Services (DPS) NFPA 13 submittal requirements call for sprinklers under attached balconies and porches unless at least 50 percent of the longest exterior side is open (item D.10) | County reviewer, such as Montgomery County DPS or the Prince George’s County Department of Permitting, Inspections and Enforcement; the Office of the State Fire Marshal where the county does not review; county fire protection system permit |
| Delaware | IBC by local adoption: 2021 in New Castle County and Sussex County, 2018 in Kent County and Wilmington, 2024 in the City of New Castle; the State Fire Marshal reviews to NFPA 13 and 13R (2025) under Regulation 701 | Regulation 702, Chapter 4: porches, balconies, decks, corridors and stairs of residential occupancies other than one- and two-family dwellings, open or not (Section 1.3.1.3); closets on exterior balconies (Section 1.3.1.4); the Fire Marshal may disapprove an NFPA 13R omission (Section 1.3.1, Exception 2) | Office of the State Fire Marshal, or the city fire marshal in Dover, Newark, the City of New Castle and Wilmington; water-based fire suppression system application with the Preliminary Sprinkler Form |
As of November 2026. Other local amendments are not shown.
In Maryland, the county building permit reviews sprinklers to NFPA 13 and 13R (2019) through the 2021 IBC, while the State Fire Prevention Code (NFPA 1, 2024) references the 2022 editions. In Delaware, the State Fire Marshal reviews sprinkler plans to NFPA 13 and 13R (2025) under Regulation 701.
Key Takeaway: Under NFPA 13R, balconies, decks and ground-floor patios of dwelling and sleeping units need sprinklers when the building is Type V with a roof or deck above, or when a combustible balcony goes unrated under IBC Section 705.2.3.1, Exception 3, and Section 903.3.1.2.2 adds breezeways under five conditions. Noncombustible materials do not remove the Type V rule, and a roof overhang can trigger it. New York City drops the roof-above condition for Type V buildings, and Delaware requires sprinklers on every residential porch, balcony, deck, corridor and stair except at one- and two-family dwellings. Settle the construction type and balcony framing before the sprinkler layout starts.
Frequently asked questions
Do apartment balconies need sprinklers?
Conditional: in a building on NFPA 13R, 2021 IBC Section 903.3.1.2.1 requires sprinklers on balconies, decks and ground-floor patios of dwelling and sleeping units when the building is Type V with a roof or deck above, or when a combustible balcony goes unrated under Section 705.2.3.1, Exception 3. New York City drops the roof-above condition for Type V buildings, and Delaware requires sprinklers on every porch, balcony and deck of residential buildings other than one- and two-family dwellings.
Do breezeways need sprinklers in a 13R building?
Conditional: 2021 IBC Section 903.3.1.2.2 requires sprinklers in corridors with combustible floor or walls, an interior change of direction of more than 45 degrees or ends less than 50 percent open, in open-ended corridors under Section 1027.6, Exception 3, and on egress balconies not complying with Sections 1021.2 and 1021.3. In a wood-frame building the combustible floor and wall condition usually decides it, and Delaware requires sprinklers in residential corridors and stairs whether or not they are open.
Are dry sidewall sprinklers used on balconies?
Yes, they are the usual choice: the sprinkler sits on the exterior wall and its sealed barrel passes through the wall to the wet piping in the heated unit, so no water stands where it can freeze. The 2021 IBC lets these sidewall sprinklers sit with their deflectors 1 to 6 inches below the structural members and, under open wood joists, no more than 14 inches below the deck.
Do noncombustible balconies need sprinklers?
Conditional: on a Type V building on NFPA 13R with a roof or deck above, yes, because 2021 IBC Section 903.3.1.2.1 turns on the building’s construction type, not the balcony’s material. On Type I to IV buildings a noncombustible balcony falls outside that section, and NFPA 13 lets noncombustible projections with nothing combustible below go without sprinklers, apart from its 2022 rule for Type V dwelling unit balconies.
Does a top-floor balcony need sprinklers?
Conditional: under the 2021 IBC, a Type V top-floor balcony with open sky above needs sprinklers only when it is an unrated combustible balcony relying on Section 705.2.3.1, Exception 3, as an untreated wood balcony on a Type VA building that is neither rated nor heavy timber does. An eave above it can count as a roof, and New York City and Delaware apply no roof-above condition.
More in Sprinkler Systems
- What Is NFPA 13? A Plain-English Guide for Owners
- When Does a Sprinkler System Need Seismic Bracing?
- How Do You Size a Water Supply for a 13R or 13D System?
- When Does a Stage or Exhibit Hall Need Special Sprinklers?
- Do Closets, Bathrooms and Small Rooms Need Sprinklers?
- When Does a Loading Dock or Canopy Need Sprinklers?
This article is general information, not a substitute for a project-specific code analysis. Confirm the adopted code editions, local amendments and the authority having jurisdiction’s position on each balcony, deck and breezeway before the design is fixed.
Sorting Out Balconies and Breezeways on a 13R Building?
Send the architectural plans and sections, the construction type, the balcony and breezeway framing details and the jurisdiction. DGA checks which balconies, decks, patios and breezeways the code and NFPA 13R require to be sprinklered, chooses the freeze protection for each and shows it on the sprinkler shop drawings and hydraulic calculations. Project briefs get confirmation and preliminary code feedback within one business day.