Sprinkler Systems · Definition
What is an antifreeze sprinkler system, and is it allowed?
General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.
An antifreeze sprinkler system is a wet pipe sprinkler system filled with an antifreeze solution instead of plain water, so its piping can run through space that falls below freezing. It is still allowed, under rules that have tightened: new systems must use a listed antifreeze solution, and the National Fire Protection Association (NFPA) inspection standard, NFPA 25 (2023), now requires listed solutions in existing systems as well, with a narrow allowance for older solutions that still test within set limits.
In commercial buildings an antifreeze system is usually a small section fed from a heated wet system, carrying sprinklers into a loading dock, a vestibule, a canopy or an unheated attic. The sections below cover what the system includes, where the rules sit and what changed, how it compares with a dry pipe system, when it is still a sensible choice, and what owners of existing systems must do in New York, New Jersey, Pennsylvania, Maryland and Delaware as of November 2026.
At a Glance: Antifreeze Sprinkler System
- Definition: a wet pipe sprinkler system, or a section of one, filled with a listed antifreeze solution so the piping can pass through space that freezes; the solution discharges first when a sprinkler opens, and water from the supply follows.
- Governing code and section: NFPA 13 (2022) Chapter 8 for new systems in New York State and New Jersey, with the 2016 edition and Appendix Q in New York City, the 2019 edition in Pennsylvania and through Maryland county permits, and the 2025 edition in Delaware; NFPA 13R and 13D for residential systems; NFPA 25 (2023) Section 5.3.4.4 for the solution in existing systems.
- Who prepares it or who it applies to: the sprinkler designer or fire protection engineer specifies the solution and the arrangement, the sprinkler contractor installs and fills it, and the owner has the solution tested every year.
- When it’s required: never as such; it is one way to protect piping that cannot be kept at 40 F or above (NFPA 13 (2022) Section 16.4.1.1), alongside dry pipe systems, dry sprinklers fed from heated piping and listed heat tracing.
- Typical output: the antifreeze section on the shop drawings with the solution, its volume and the connection details; a Darcy-Weisbach friction check above 40 gal; a sign at the main control valve; and an annual test report.
- Often confused with: a dry pipe system, which keeps water out of cold piping with air or nitrogen pressure and a dry pipe valve instead of filling the pipe with a liquid that will not freeze.
What is an antifreeze sprinkler system?
NFPA 13, the NFPA standard for the installation of sprinkler systems, defines the antifreeze system in Chapter 3 of its 2022 edition as a type of wet pipe system. The piping holds a liquid that will not freeze at the lowest temperature the space reaches, and each sprinkler stays closed until heat operates it, as on any wet system. When a sprinkler opens, the solution discharges first and water from the supply follows.
The solution is the part that has changed. Older systems hold glycerine or propylene glycol solutions that were never listed for sprinkler use, now called legacy solutions. Underwriters Laboratories (UL) reports that its research found certain concentrations of these solutions intensify a fire when a sprinkler discharges them onto it, and NFPA cites the same risk of accelerated fire growth as the reason the rules changed.
Antifreeze is one of several ways NFPA 13 lets sprinkler piping pass through cold space; the others are dry pipe and preaction systems, dry sprinklers fed from heated piping, and listed heat tracing. DGA’s comparison of wet, dry, preaction and deluge sprinkler systems sets the main system types side by side.
What does an antifreeze sprinkler system include?
An antifreeze system adds a few parts to an ordinary wet system. They keep the solution separate from the water supply, absorb its expansion and let it be filled, drained and sampled. NFPA 13 (2022) Chapter 8 sets the arrangement, the listing of the chosen solution adds limits of its own, and NFPA 25 (2023) adds a sign and an annual test.
| Component | What it does | Where the rule sits |
|---|---|---|
| Listed antifreeze solution | Keeps the piping from freezing down to the lowest temperature the space reaches; it arrives premixed from the factory and is not diluted on site | NFPA 13 (2022) Chapter 8; NFPA 25 (2023) Section 5.3.4.4; UL 2901 for the listing |
| Control valve with a check valve or backflow preventer | Isolates the antifreeze section and keeps the solution from moving into the wet system and the public water supply | NFPA 13 (2022) Chapter 8; the state’s cross-connection rule for the device |
| Expansion chamber | Absorbs the expansion of the solution trapped behind the check valve or backflow preventer as it warms, so pressure stays within the rating of the system’s components | NFPA 13 (2022) Chapter 8; the product’s installation instructions |
| Fill, drain and test connections | Let the solution be filled, drained and sampled, with sample points near the top and the bottom of the antifreeze section | NFPA 13 (2022) Chapter 8; NFPA 25 (2023) Chapter 5 |
| Antifreeze information sign | Hangs at the main control valve and records the solution’s type and brand, its concentration by volume and the volume in the system | NFPA 25 (2023) Chapter 4 |
Where the system connects to a public water main, the water purveyor’s cross-connection program chooses the backflow device, and a reduced pressure zone (RPZ) assembly is commonly required on fire services that carry antifreeze or other additives. DGA’s article on backflow preventer pressure loss in sprinkler calculations lists each state’s cross-connection rule and shows what the device costs in pressure.
Figure 1: An antifreeze loop fed from a wet system
Where do NFPA 13 and NFPA 25 set the antifreeze rules, and what changed?
For new systems the rules sit in NFPA 13 (2022). Chapter 8 governs antifreeze systems and accepts only listed solutions in new ones, Chapter 16 requires water-filled piping to be kept at 40 F or above (Section 16.4.1.1), and Chapter 28 requires an antifreeze system holding more than 40 gal to be calculated with the Darcy-Weisbach formula as well as Hazen-Williams. NFPA 13R and NFPA 13D, the standards for low-rise residential buildings and for one- and two-family dwellings, carry their own antifreeze provisions and also require listed solutions in new systems.
The Darcy-Weisbach check matters because an antifreeze solution is denser and more viscous than water, and its viscosity rises as it cools, which the Hazen-Williams formula does not account for. DGA’s Darcy-Weisbach friction loss calculator works the formula for water or an antifreeze solution and shows the Hazen-Williams result beside it. A listed product’s installation instructions can add calculation rules of their own, such as using the fluid’s properties at the lowest temperature the system will see.
For existing systems the rules sit in NFPA 25 (2023). Section 5.3.4.4 requires antifreeze systems to use listed solutions, with exceptions that let some older systems keep their solution under conditions; Chapter 5 requires the solution to be tested every year, and Chapter 4 requires a sign at the system’s main control valve.
The history explains the current wording. NFPA notes that its installation standards have not allowed unlisted solutions in new systems since 2012, yet the first listed solution did not reach the market until late 2018. UL tests and certifies these products under UL 2901, its outline of investigation for antifreeze in sprinkler systems, which covers stability, effects on system materials, health and environmental impact, fire performance and hydraulic characteristics, and the solutions arrive premixed from the factory.
NFPA 25 has also changed course on existing systems. In February 2019, UL described NFPA 25 as requiring glycerine and propylene glycol solutions in installed systems to be replaced with a listed solution by September 30, 2022. The 2023 edition carries no such date. Instead it lets an existing system keep a premixed legacy solution of up to 30 percent propylene glycol or 38 percent glycerine by volume (Section 5.3.4.4.2), while the solution still protects to the temperature the space requires; a legacy solution above those limits, or any solution that has to be replaced, gives way to a listed one.
| When | Document | Rule, paraphrased | Source |
|---|---|---|---|
| Since 2012 | NFPA 13, 13R and 13D | New antifreeze systems may use listed solutions only | NFPA Journal (Fall 2023) |
| Late 2018 | UL 2901 | The first listed solution becomes available; listed solutions are premixed at the factory and not diluted or mixed in the field | NFPA Journal (Fall 2023); UL (February 2019) |
| As described in 2019 | NFPA 25, edition then in force | Glycerine and propylene glycol solutions in installed systems to be replaced with a listed solution by September 30, 2022 | UL (February 2019) |
| 2023 | NFPA 25 (2023) | Listed solutions in all antifreeze systems; an existing system may keep a premixed legacy solution of up to 30 percent propylene glycol or 38 percent glycerine; no September 30, 2022 date | Sections 5.3.4.4 and 5.3.4.4.2 |
| Current | NFPA 25 (2023) | A sign at the main control valve gives the solution’s type and brand, concentration and volume | Chapter 4 |
Figure 2: How the antifreeze rules tightened
- 42023: NFPA 25 requires listed solutions in all antifreeze systemsAn existing system may keep a premixed legacy solution of up to 30 percent propylene glycol or 38 percent glycerine (Section 5.3.4.4.2)
- 3Late 2018: the first listed antifreeze solution reaches the marketListed under UL 2901 and premixed at the factory
- 22012: new systems limited to listed solutionsNFPA 13, 13R and 13D
- 1Before 2012: unlisted glycerine and propylene glycol solutionsNow called legacy solutions
DGA designs antifreeze, dry pipe and wet pipe sprinkler systems and prepares their shop drawings and hydraulic calculations across New York, New Jersey, Pennsylvania, Maryland, Delaware, Washington, Oregon and Florida. Project briefs get confirmation and preliminary code feedback within one business day. See where DGA works →
How is an antifreeze system different from a dry pipe system?
Both systems protect piping that runs through cold space, but they work in opposite ways. An antifreeze system keeps the pipe full of a liquid that will not freeze, so it behaves like a wet system; a dry pipe system keeps water out of the cold pipe, holding it back at a dry pipe valve in heated space with air or nitrogen pressure in the piping. The table compares the two.
| Point | Antifreeze system | Dry pipe system |
|---|---|---|
| What fills the piping | A listed antifreeze solution, so the system is a wet system | Air or nitrogen under pressure, held behind a dry pipe valve in heated space |
| When a sprinkler opens | The solution discharges at once, and water from the supply follows | The air escapes, the valve trips, and water travels through empty pipe before it discharges |
| Size limit | Set by the listing; under NFPA 13 one listed product allows up to 200 gal for light hazard and 40 gal for ordinary hazard or storage, or up to 500 gal for light or ordinary hazard designed to the dry system hydraulic criteria, and up to 500 gal under NFPA 13R and 13D | Up to 500 gal, or 750 gal with a quick-opening device, without a water delivery time limit; larger systems must meet one (NFPA 13 (2022) Chapter 8) |
| Design area | No increase for the system type | 30 percent larger where the density/area method is used (NFPA 13 (2022) Section 19.2.3.2.5) |
| Friction loss | Darcy-Weisbach as well as Hazen-Williams above 40 gal (NFPA 13 (2022) Chapter 28) | Hazen-Williams (NFPA 13 (2022) Chapter 28) |
| Upkeep under NFPA 25 (2023) | Annual solution test (Chapter 5) and the information sign (Chapter 4) | Annual trip test, a full flow trip test every 3 years (Section 13.4.5.2.2), an air supply and low point drains |
The delay is the main practical difference. Water in a dry pipe system has to travel through empty pipe before it reaches the fire, and NFPA 13 (2022) accounts for that delay with the 30 percent larger design area of Section 19.2.3.2.5 and the size limits of Chapter 8. DGA’s article on when a dry pipe system needs a quick-opening device covers the delivery time rules.
When is an antifreeze system still a reasonable choice?
An antifreeze system fits best where a small unheated area adjoins a heated building that already has a wet system: a loading dock, an entrance vestibule, a canopy, an unheated attic section or a short run of pipe through a cold space. For a handful of sprinklers, a dry pipe valve, its air supply and the 30 percent larger design area can be more than the area warrants, and dry sprinklers cannot always reach far enough from heated piping.
The listed product decides as much as NFPA 13 does. One listed product’s installation instructions, for example, set a lowest use temperature, cap the system volume separately for NFPA 13, 13R and 13D, exclude extra hazard occupancies, flammable liquids and early suppression fast response (ESFR) sprinklers, and require samples from the top and bottom of the system at least once a year. The design has to stay inside every limit of the chosen product, and a different product may set different ones.
Large cold spaces usually rule antifreeze out. An open or partly heated parking garage usually holds more pipe than a listing like the one above allows on the normal NFPA 13 design basis, and above that size the listing calls for the dry system hydraulic criteria, so garages generally take dry pipe systems. DGA’s article on whether parking garage sprinklers need freeze protection compares the garage options, and DGA’s work on parking garages and transit facilities covers the building type.
In one- and two-family homes, antifreeze is an option only for a stand-alone NFPA 13D system with its own piping. A multipurpose system, whose piping also feeds the plumbing fixtures, carries drinking water and cannot hold antifreeze. Antifreeze is also a poor fit where the owner cannot commit to the annual test or where the space gets colder than any listed product allows.
What must owners of existing antifreeze systems do now?
Owners of existing antifreeze systems face no fixed replacement date under NFPA 25 (2023), but the solution has to pass a test every year. The steps below follow the 2023 edition, which Delaware adopts in Regulation 701 and which NFPA 1 (2024) references in Maryland. New York City applies NFPA 25 (2014), and elsewhere the edition is the one the adopted fire code references, so the wording that applies can differ.
- Read the sign and the records. NFPA 25 (2023) Chapter 4 calls for a sign at the main control valve giving the solution’s type and brand, its concentration by volume and the volume in the system. Where no sign exists, the last test report and the installing contractor’s records are the place to start.
- Test the solution every year. NFPA 25 (2023) Chapter 5 requires an annual test, with samples drawn near the top and the bottom of the system, and the result decides what happens next.
- Keep a listed solution inside its listing. A system already on a listed solution stays in order while the annual result falls within the range the manufacturer publishes.
- Check a legacy solution against the 2023 limits. A glycerine or propylene glycol solution in an existing system may stay only while it is a premixed solution of no more than 38 percent glycerine or 30 percent propylene glycol by volume (Section 5.3.4.4.2) and still protects to the lowest temperature the space reaches.
- Replace a failing solution with a listed one, or change the system. When a listed solution replaces a nonlisted one, NFPA 25 (2023) Section 5.3.4.4.1 lets it be used outside its listing limits as long as it stays within its temperature range. The other route is to convert the area to a dry pipe system, dry sprinklers or heat, which is a design change.
Creating, extending or converting an antifreeze section is a change to the sprinkler system and is filed with the reviewing authority. Delaware’s Office of the State Fire Marshal (SFM), for example, requires a formal plan submission to create an antifreeze loop or to convert a system from wet to dry, and Montgomery County, Maryland, requires a Fire Protection System permit for any addition or modification, including repair.
Which antifreeze rules apply in New York, New Jersey, Pennsylvania, Maryland and Delaware?
The NFPA antifreeze rules reach each jurisdiction through the edition it adopts, and several jurisdictions add rules of their own. The table lists, as of November 2026, the edition for new systems, the maintenance basis for existing systems, any local rule that touches antifreeze, and who reviews the work.
| Jurisdiction | New systems | Existing systems | Local rule on antifreeze | Reviewer and filing |
|---|---|---|---|---|
| New York State (outside New York City) | 2025 Building Code of New York State, based on the 2024 International Building Code (IBC); NFPA 13 (2022) | 2025 Fire Code of New York State, which applies NFPA 25 through its Chapter 9 | No New York change to the referenced NFPA standards appears in the 2025 rule text | City, town or village code enforcement program under Title 19 of the New York Codes, Rules and Regulations (NYCRR), Part 1203; its permit exemption for repairs excludes work on fire protection systems |
| New York City | 2022 New York City Building Code; NFPA 13, 13R and 13D (2016) as modified by Appendix Q | 2022 New York City Fire Code; NFPA 25 (2014) | Appendix Q allows only glycerin-type antifreeze in NFPA 13R systems with nonmetallic pipe or fittings (Q104) and requires NFPA 13D antifreeze supply piping to follow NFPA 13 (2016) as modified for New York City (Q103) | Department of Buildings (DOB), sprinkler work filed in DOB NOW: Build; the Fire Department (FDNY) enforces inspection, testing and maintenance under the Fire Code |
| New Jersey | Uniform Construction Code (UCC) on the 2024 International Codes, effective August 17, 2026; NFPA 13 (2022), or NFPA 13 (2019) for complete applications under the prior codes through February 17, 2027 | Uniform Fire Code on a 2018 International Fire Code (IFC) basis, which sends sprinkler maintenance to NFPA 25 | The Department of Community Affairs (DCA) withdrew Bulletin 11-3, Antifreeze in New Residential and Commercial Fire Sprinkler Systems, in its Fall 2026 newsletter, so the referenced NFPA editions govern | Fire protection subcode official; installing or altering a sprinkler system needs a construction permit (New Jersey Administrative Code (N.J.A.C.) 5:23-2.14) |
| Pennsylvania | Pennsylvania UCC on the 2021 International Codes since January 1, 2026; NFPA 13 (2019) and NFPA 13R (2019) | No statewide fire code; NFPA 25 applies where a municipality adopts a fire code, as Philadelphia does | No state change found to the NFPA editions the 2021 IBC references | Municipal code official, third-party agency or the Department of Labor and Industry; Philadelphia’s Fire Suppression Systems Permit; Pittsburgh’s Suppression Systems Permit |
| Maryland | County building permit under the Maryland Building Performance Standards (MBPS), 2021 IBC; NFPA 13 (2019) | State Fire Prevention Code, NFPA 1 (2024), which references NFPA 25 (2023) | The MBPS delete the International Residential Code (IRC) Section P2904.1 sentence that excused a backflow preventer on a home sprinkler system with drinking-water piping, no antifreeze and no fire department connection (Code of Maryland Regulations (COMAR) 09.12.51.04C(6)) | The county, such as Montgomery County’s Department of Permitting Services, whose Fire Protection System permit covers any addition or modification; the Office of the State Fire Marshal where the county does not review |
| Delaware | Regulation 701 (2026 edition of the State Fire Prevention Regulations) adopts NFPA 13, 13R and 13D (2025) without amendment | NFPA 25 (2023) under Regulation 701; systems inspected under Regulation 703, with an annual Certificate of Inspection filed through a licensed company | SFM guidance for existing systems (Doc. 75-01-24-04-06) requires a formal plan submission to create an antifreeze loop | SFM; city fire marshals in Wilmington, Dover, Newark and the City of New Castle |
In Maryland, the county building permit reviews sprinklers to NFPA 13 (2019) through the 2021 IBC, while the State Fire Prevention Code (NFPA 1, 2024) references NFPA 13 (2022). Either way, a new antifreeze system needs a listed solution.
Key Takeaway: An antifreeze sprinkler system is a wet pipe system filled with a solution that will not freeze, and it is still allowed. New systems under NFPA 13, 13R and 13D must use a listed solution, and NFPA 25 (2023) Section 5.3.4.4 applies the listed-solution rule to existing systems, while a premixed legacy solution of up to 30 percent propylene glycol or 38 percent glycerine may stay only as long as it tests within the standard’s limits. Owners should read the sign at the main control valve, test the solution every year and replace a failing solution with a listed one.
Frequently asked questions
Are antifreeze sprinkler systems still allowed?
Yes. NFPA 13, 13R and 13D still allow antifreeze systems where piping would otherwise freeze, but new systems must use a listed antifreeze solution, and NFPA 25 (2023) Section 5.3.4.4 requires listed solutions in existing systems too, with narrow exceptions, including premixed legacy solutions of up to 30 percent propylene glycol or 38 percent glycerine.
Do existing antifreeze systems have to be replaced?
No, not automatically. NFPA 25 (2023) sets no replacement date: an existing system may keep a premixed legacy solution of up to 30 percent propylene glycol or 38 percent glycerine while it still protects to the required temperature, and a solution above the limits, or one that has to be replaced, gives way to a listed solution. New York City applies NFPA 25 (2014), so that edition’s wording governs there.
How often is antifreeze in a sprinkler system tested?
Every year. NFPA 25 (2023) Chapter 5 requires an annual test of the solution, with samples taken near the top and the bottom of the system, and the result decides whether the solution can stay in service.
Can a 13D home sprinkler system use antifreeze?
Conditional: a stand-alone NFPA 13D system with its own piping can use a listed antifreeze solution, but a multipurpose system whose piping also feeds the plumbing fixtures carries drinking water and cannot. An antifreeze system also needs backflow protection between the sprinkler piping and the drinking water, and in New York City Appendix Q requires the 13D antifreeze supply piping to follow NFPA 13 (2016) as modified for New York City.
More in Sprinkler Systems
- What Is NFPA 13? A Plain-English Guide for Owners
- When Does a Sprinkler System Need Seismic Bracing?
- How Do You Size a Water Supply for a 13R or 13D System?
- Do Balconies and Decks Need Sprinklers Under NFPA 13R?
- When Does a Stage or Exhibit Hall Need Special Sprinklers?
- Do Closets, Bathrooms and Small Rooms Need Sprinklers?
This article is general information, not a substitute for a project-specific sprinkler design. Code editions, local amendments and reviewer practice change; confirm the adopted code and the authority having jurisdiction for the project.
Planning an Antifreeze Loop or Replacing an Old One?
Send the drawings or a description of the cold area, the solution now in the system if there is one, and the jurisdiction. DGA compares antifreeze, dry pipe and the other options against NFPA 13 and the local code, then prepares the shop drawings and hydraulic calculations for the one that fits. Project briefs get confirmation and preliminary code feedback within one business day.