How do you calculate friction loss with Hazen-Williams?

General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.

Friction loss with Hazen-Williams is calculated per foot of pipe as p = 4.52 × Q1.85 ÷ (C1.85 × d4.87), where Q is the flow in gallons per minute (gpm), C is the pipe’s friction loss coefficient and d is its actual inside diameter in inches, and the result in pounds per square inch (psi) per foot is multiplied by the pipe length plus the equivalent length of its fittings and valves. For 150 gpm through 50 ft of 2-inch Schedule 40 steel pipe in a wet pipe system, that comes to 0.199 psi per ft, or 9.95 psi for the run.

NFPA 13, the National Fire Protection Association’s standard for sprinkler systems, sets the formula, the C-factors and the equivalent lengths of fittings in its hydraulic calculation chapter. This article covers the inputs, the method for one pipe segment, a worked example, fittings and valves, the Darcy-Weisbach case and the input errors that move the answer most.

At a Glance: Hazen-Williams Friction Loss

  • What is calculated: the pressure, in psi, that water loses to friction flowing through one pipe segment and its fittings and valves at a given flow.
  • Method in one line: p = 4.52 × Q1.85 ÷ (C1.85 × d4.87) psi per ft, multiplied by the pipe length plus the equivalent length of the fittings and valves.
  • Inputs needed: the flow in gpm, the actual inside diameter in inches, the C-factor for the pipe material and system type, the measured length in ft, and the fittings and valves in the run.
  • Code and section: NFPA 13 (2022) Chapter 28, which holds the formula (Section 28.2.2.1.1), the C-value table (Table 28.2.4.8.1) and the equivalent length chart (Table 28.2.3.1.1); the 2025 edition keeps Chapter 28, the 2019 edition uses Chapter 27, and the 2016 edition used in New York City uses Chapter 23.
  • Typical result range (units): psi per ft, then psi for the run. In 1 in. to 4 in. Schedule 40 steel at C = 120, the chart below runs from about 0.004 psi per ft (4 in. pipe at 100 gpm) to 0.5 psi per ft (1 in. pipe at 41 gpm); the worked example is 0.199 psi per ft and 9.95 psi over 50 ft.
  • Most common input error: the wrong inside diameter, either the nominal size or another schedule’s bore. Because d carries the 4.87 power, a 3 percent error in the bore shifts the loss by about 15 percent.

What does the Hazen-Williams formula calculate?

The Hazen-Williams formula calculates the pressure that water loses to friction as it flows through a pipe: drag at the pipe wall and turbulence in the stream, which grow with the flow and shrink as the bore gets larger and smoother. NFPA 13 uses the formula for water in sprinkler piping, and it returns a loss per foot that is multiplied by length to give psi for one segment.

Friction is one of three losses in a sprinkler hydraulic calculation. The other two are elevation, 0.433 psi for every foot the water rises, and the losses through devices such as backflow preventers and alarm valves, which come from listed data rather than the formula. DGA’s article on how sprinkler hydraulic calculations are done adds all three together node by node; this article stays with the friction in one segment.

The formula and its constants are the same in every NFPA 13 edition used in the five states DGA works in, so the chapter citation changes from one jurisdiction to the next but the arithmetic does not. The dry system C-factor can differ, because the 2022 and 2025 editions add allowances for corrosion-protected piping described below. As of November 2026, New York State and New Jersey review sprinklers to NFPA 13 (2022), where the method is in Chapter 28, and the Delaware State Fire Marshal reviews to NFPA 13 (2025), also Chapter 28. Pennsylvania uses NFPA 13 (2019), Chapter 27, and New York City uses NFPA 13 (2016) as modified by Appendix Q of the 2022 New York City Building Code, where the method is in Chapter 23.

In Maryland, the county building permit reviews sprinklers to NFPA 13 (2019) through the 2021 International Building Code (IBC), while the State Fire Prevention Code (NFPA 1, 2024) references NFPA 13 (2022). Under either edition the friction loss arithmetic in this article is the same.

What inputs does Hazen-Williams need: Flow, pipe size, C-factor and length?

Every Hazen-Williams calculation needs four numbers for the pipe and a count of what is in it. The table lists each input, its unit, where it comes from and its value in the worked example below.

InputUnitWhere it comes fromWorked example
Flow, QGallons per minute (gpm)The hydraulic calculation at that point in the system, or the flow being checked150 gpm
Inside diameter, dInchesThe pipe manufacturer’s published dimensions for the material and schedule, not the nominal size2.067 in. (2 in. Schedule 40 steel)
C-factor, CNone (a coefficient)The C-value table in NFPA 13 (2022) Chapter 28, by pipe material and system type120 (steel in a wet pipe system)
Pipe length, LFeetMeasured along the pipe on the layout drawing50 ft
Fittings and valves, LeFeet of equivalent pipeThe equivalent length chart in NFPA 13 (2022) Chapter 28, adjusted for C-factor and bore; listed devices from the manufacturer’s dataNone in the base case; 20 ft in the fittings example

The inside diameter is the input most often taken from the wrong place. Pipe is named by a nominal size, but the formula needs the bore, which depends on the wall thickness: 2-inch Schedule 40 steel has a 2.067-inch bore and 2-inch Schedule 10 a 2.157-inch bore, from the pipe manufacturer’s published dimensions.

The C-factor measures how smooth the pipe wall is, and NFPA 13 assigns it by material and by system type. The table groups the values that matter in sprinkler work and shows how much each one changes the loss compared with C = 120 pipe of the same bore.

Pipe and where it is usedC-factorLoss compared with C = 120 pipe of the same bore
Black or galvanized steel in a wet pipe or deluge system120Baseline
Black or galvanized steel in a dry pipe or preaction system1001.40 times
Unlined cast or ductile iron1001.40 times
Cement-lined ductile iron, common for underground mains1400.75 times
Listed plastic pipe such as chlorinated polyvinyl chloride (CPVC), copper tube or stainless steel1500.66 times

C-factors paraphrased from the C-value table in NFPA 13 (2022) Chapter 28. The last column is DGA’s arithmetic, (120 ÷ C)1.85. In New York City, Appendix Q allows nonmetallic pipe such as CPVC only in Group R occupancies six stories or less.

The lower value for steel in dry pipe and preaction systems reflects how those systems age: their piping holds air and some trapped water, and the inside of the pipe corrodes faster than pipe kept full of water. NFPA 13 (2022) lets black or galvanized steel in a new dry pipe or preaction system use C = 120 where the piping is kept under nitrogen supplied as the standard’s Chapter 8 requires (an existing system converted to nitrogen stays at C = 100), and the 2025 edition extends that value to piping protected by vacuum or a vapor corrosion inhibitor. DGA’s guide to wet, dry, preaction and deluge sprinkler systems explains how each type holds water or air until it operates.

How is friction loss calculated for one pipe segment, step by step?

A segment is a run of one pipe size carrying one flow, usually from one node of the calculation to the next. The loss for that segment takes six steps, and the formula card below defines each term.

  1. Set the flow. Q is the flow in the segment in gpm, taken from the hydraulic calculation at that point or from the flow being checked.
  2. Look up the bore. Use the actual inside diameter for the pipe’s material and schedule, never the nominal size.
  3. Pick the C-factor. Read it from the NFPA 13 C-value table for the material and system type: 120 for steel in a wet pipe system, 100 for steel in a dry pipe or preaction system.
  4. Solve for the loss per foot. Raise Q to the 1.85 power, C to the 1.85 power and d to the 4.87 power, then compute p = 4.52 × Q1.85 ÷ (C1.85 × d4.87).
  5. Total the length. Add the equivalent length of every counted fitting and valve to the measured pipe length.
  6. Multiply. The friction loss for the segment is p times the total length, in psi; elevation and device losses are added separately.

Figure 1: The Hazen-Williams formula, term by term

Friction loss per foot: p = 4.52 × Q1.85 ÷ (C1.85 × d4.87)

p is the friction loss in psi per foot of pipe. Q is the flow in gpm. C is the C-factor for the pipe material and system type. d is the actual inside diameter in inches, not the nominal size.

Loss for the run: Pf = p × (L + Le), where L is the measured pipe length in ft and Le is the equivalent length of the counted fittings and valves in ft.

Fitting lengths for other pipe: chart length × 0.713 at C = 100 (1.16 at C = 130, 1.33 at C = 140, 1.51 at C = 150) × (actual bore ÷ Schedule 40 bore)4.87.

Friction loss rises with the 1.85 power of flow and falls with the 4.87 power of the bore, so doubling the flow multiplies the loss by about 3.6, and dropping the C-factor from 120 to 100 multiplies it by 1.40.

Worked example: What is the loss for 150 gpm through 50 ft of 2 in. Schedule 40 steel?

The segment is 50 ft of 2-inch Schedule 40 black steel pipe in a wet pipe system, carrying 150 gpm, with no fittings in the run. The inputs are Q = 150 gpm, C = 120 for steel in a wet system, and d = 2.067 inches, the bore of 2-inch Schedule 40 pipe.

Raised to their powers, the terms are Q1.85 = 10,611, C1.85 = 7,022 and d4.87 = 34.33. The loss per foot is 4.52 × 10,611 ÷ (7,022 × 34.33) = 0.199 psi, and the 50 ft run loses 0.199 × 50 = 9.95 psi. DGA’s Hazen-Williams friction loss calculator runs the same arithmetic for any single run, with the fitting, C-factor and pipe schedule adjustments built in.

Changing one input at a time shows which inputs matter. The table keeps the run at 50 ft with no fittings.

Case (50 ft, no fittings)Input that changesLoss per ft, psiLoss in 50 ft, psiCompared with the base case
Base case: 2 in. Schedule 40, wet pipe system, 150 gpmNone0.1999.951.00
Dry pipe or preaction systemC drops from 120 to 1000.27913.941.40 times
2 in. Schedule 10 piped rises from 2.067 to 2.157 in.0.1628.080.81 times
2-1/2 in. Schedule 40 piped rises to 2.469 in.0.0844.190.42 times
Flow doubled to 300 gpmQ doubles0.71735.863.61 times

Run totals and ratios are computed before the per-foot values are rounded.

Flow and bore dominate the result. Doubling the flow multiplies the loss by 3.6, and one pipe size up cuts it by 58 percent, which is why a calculation that comes up short is usually fixed by enlarging the pipe that loses the most.

Figure 2: Friction loss against flow, Schedule 40 steel at C = 120

00.10.20.30.40.5 0100200300400500 Friction loss, psi per ft Flow, gpm 1 in. 1-1/4 in. 1-1/2 in. 2 in. 2-1/2 in. 3 in. 4 in. 2 in. pipe Other Schedule 40 sizes, labeled at the line ends Worked example: 150 gpm in 2 in. pipe loses 0.199 psi per ft
In Schedule 40 steel at C = 120, 150 gpm loses 0.199 psi per ft in 2 in. pipe but only 0.084 psi per ft in 2-1/2 in. pipe. Every curve steepens with flow because loss rises with the 1.85 power of flow: 1 in. pipe reaches 0.5 psi per ft at 41 gpm, while 4 in. pipe loses 0.072 psi per ft at 500 gpm.

Opens the Project Desk with your sentence. Our licensed PEs review every brief and reply within one business day.

How are fittings and valves converted to equivalent length?

Elbows, tees and valves lose pressure by turning and squeezing the flow, and NFPA 13 counts that loss as extra feet of straight pipe. The equivalent length chart in NFPA 13 (2022) Chapter 28 gives each common fitting and valve, by size, as feet of Schedule 40 steel pipe at C = 120, and those feet are added to the measured length before the loss per foot is applied.

What counts matters as much as the chart. Each elbow, each tee or cross where the flow turns 90 degrees, and each valve in the run is counted, while a tee or cross with straight-through flow is left out and the fitting connected directly to a sprinkler may be left out. Alarm, dry pipe and deluge valves, strainers and backflow preventers are not on the chart, so their losses come from the manufacturers’ listed data, as DGA’s article on backflow preventer pressure loss in sprinkler calculations explains.

Two adjustments carry the chart to other pipe. For a C-factor other than 120, the chart lengths are multiplied by 0.713 for C = 100, 1.16 for C = 130, 1.33 for C = 140 or 1.51 for C = 150. For a bore other than Schedule 40, they are multiplied by the actual inside diameter divided by the Schedule 40 inside diameter, raised to the 4.87 power.

Adding fittings to the worked example shows both rules at work. Two 2-inch standard elbows at 5 ft each and one 2-inch tee with the flow turned at 10 ft add 20 ft, so the wet pipe run counts as 70 ft and loses 13.93 psi.

Case (50 ft of 2 in. Schedule 40 at 150 gpm)Fitting length usedTotal lengthPipe loss, psiFitting loss, psiTotal loss, psi
Wet pipe system, C = 12020 ft70 ft9.953.9813.93
Dry pipe system, C = 100, chart lengths × 0.71314.26 ft64.26 ft13.943.9717.91
Dry pipe system with the 0.713 multiplier left out20 ft70 ft13.945.5719.51

Fittings: two 2 in. standard elbows at 5 ft each and one 2 in. tee with the flow turned at 10 ft, from the NFPA 13 (2022) Chapter 28 equivalent length chart.

The fittings cost about 4 psi whether the system is wet or dry, because a fitting’s loss comes from its shape, not from the roughness of the pipe beside it; only the straight pipe loses more at C = 100. Leaving the chart lengths unadjusted in a C = 100 calculation charges the fittings 5.57 psi instead of 3.97 psi, a 40 percent overstatement.

When does NFPA 13 require the Darcy-Weisbach formula?

Hazen-Williams is an empirical formula fitted to water at ordinary temperatures in turbulent flow, and it has no term for the fluid’s density or viscosity. That suits water in sprinkler pipe, and NFPA 13 uses it as the standard method, but it does not suit a fluid that is thicker than water.

NFPA 13 draws the line at antifreeze. For antifreeze systems holding more than 40 gal, NFPA 13 (2022) Section 28.2.2.1.3 requires the friction loss to be calculated with the Darcy-Weisbach formula as well as with Hazen-Williams. Antifreeze solutions are denser and more viscous than water, and their viscosity climbs as they cool, so Hazen-Williams alone can understate the loss in the cold piping an antifreeze system exists to protect.

Darcy-Weisbach works from the fluid’s properties. In inch-pound units the loss is ΔP = 0.000216 × f × L × ρ × Q2 ÷ d5 psi, with L in ft, ρ the fluid density in lb per cubic ft, Q in gpm, d in inches, and f a friction factor found from the Reynolds number and the pipe’s roughness. Because f depends on viscosity, the answer changes with temperature. Both formulas are set out in the hydraulics chapter of the SFPE Handbook of Fire Protection Engineering (5th edition), published by the Society of Fire Protection Engineers (SFPE).

Listed antifreeze products can add requirements of their own to the standard’s. Installation instructions for some listed solutions call for friction loss by both formulas regardless of system size, and some require the solution’s viscosity at the lowest temperature the system will see.

Which Hazen-Williams input errors are most common?

Hazen-Williams arithmetic is simple enough that errors almost always come from the inputs rather than the math. The table lists the input errors that change a friction loss result most, with their size in the worked example’s terms and how to catch each one.

Input errorEffect on the calculated lossHow to catch it
Nominal size used as the inside diameterUsually overstates the loss, by 62 percent in 1-1/4 in. Schedule 40 pipe, but understates it by 6 percent in 2-1/2 in. pipeTake the bore from the manufacturer’s dimensions for the material and schedule
Schedule 10 bore used for Schedule 40 pipeUnderstates the loss by 19 percent in 2 in. pipeMatch the schedule on the layout drawing to the one in the calculation
C = 120 used for steel in a dry pipe or preaction systemUnderstates the loss by 29 percentUse C = 100 for steel in dry pipe and preaction systems unless the adopted edition’s nitrogen or corrosion protection allowance applies
Fittings left out of the runUnderstates the loss; in the worked example, by 3.98 psi of 13.93 psiCount every elbow, every tee or cross where the flow turns, and every valve
Straight-through tees or the fittings at sprinklers countedOverstates the loss, which can lead to oversized pipeLeave out straight-through flow and the fitting connected to each sprinkler
Chart lengths not adjusted for C-factor or boreOverstates fitting losses by 40 percent at C = 100Apply the C-factor multiplier and the 4.87-power bore factor
Hazen-Williams alone on an antifreeze system over 40 galCan understate the loss in cold pipingRun Darcy-Weisbach as well, with fluid properties at the lowest expected temperature

The diameter errors are the ones that hide, because a nominal size looks conservative. Using the nominal size does overstate the loss in most sizes, but it understates the loss in 2-1/2-inch pipe, whose 2.469-inch bore is smaller than its name.

When is a Hazen-Williams hand check not enough?

A friction loss figure for one segment is a check, not a design. A permit submittal calculates the whole system from the most remote sprinkler to the water supply, and the resulting demand is compared with a flow test on N1.85 graph paper, where the same 1.85 exponent makes the supply curve a straight line. DGA’s guide to plotting sprinkler demand against the supply curve covers that step.

The formula also needs an engineer’s judgment in three situations. Looped and gridded piping splits the flow between paths, and the split has to be solved by iteration before any segment’s loss is known. Existing pipe may have lost bore to corrosion or deposits, so the table’s C-factor may not describe the pipe in the ceiling, and antifreeze systems need the Darcy-Weisbach check described above. The calculation submitted for a permit is then prepared and signed under each state’s rules, which the hydraulic calculation article linked earlier summarizes.

Key Takeaway: Hazen-Williams friction loss is p = 4.52 × Q1.85 ÷ (C1.85 × d4.87) psi per foot, using the actual inside diameter and the NFPA 13 C-factor for the pipe and system type, multiplied by the pipe length plus the equivalent length of the counted fittings and valves. In the worked example, 150 gpm through 50 ft of 2-inch Schedule 40 steel loses 9.95 psi in a wet system, 13.94 psi in a dry system and 13.93 psi once two elbows and a tee are added. Flow and bore drive the answer, and an antifreeze system over 40 gal needs a Darcy-Weisbach calculation as well.

Frequently asked questions

What C-factor should be used for a dry pipe system?

100 for black or galvanized steel pipe in a dry pipe or preaction system, from the C-value table in NFPA 13 (2022) Chapter 28, against 120 for the same pipe in a wet system. At the same flow and bore, C = 100 pipe loses 1.40 times as much pressure per foot, so the worked example’s 50 ft of 2-inch pipe goes from 9.95 psi to 13.94 psi. NFPA 13 (2022) allows 120 in new systems where the dry piping is kept under nitrogen as the standard requires, and the 2025 edition extends the same allowance to vacuum and vapor corrosion inhibitor systems.

Is Hazen-Williams accurate for antifreeze systems?

No, not on its own for larger systems. The formula has no term for viscosity, and antifreeze solutions grow more viscous as they cool, so NFPA 13 (2022) Chapter 28 requires antifreeze systems holding more than 40 gal to be calculated with the Darcy-Weisbach formula as well. Listed antifreeze products can add calculation requirements of their own.

Do fittings count in friction loss?

Yes. Each elbow, each tee or cross where the flow turns 90 degrees, and each valve is converted to an equivalent length of straight pipe and added to the run, while tees and crosses with straight-through flow are left out and the fitting connected directly to a sprinkler may be left out. In the worked example, two elbows and a tee add 20 ft and raise the loss from 9.95 psi to 13.93 psi.

Why does friction loss rise faster than flow?

Because the Hazen-Williams formula raises the flow to the 1.85 power. Doubling the flow through the same pipe multiplies the loss by 2 to the 1.85 power, about 3.6, so the worked example’s 50 ft of 2-inch pipe loses 9.95 psi at 150 gpm and 35.86 psi at 300 gpm.

Does Schedule 10 pipe lose less pressure than Schedule 40?

Yes, at the same nominal size and flow, because its thinner wall leaves a larger bore. Two-inch Schedule 10 steel has a 2.157-inch bore against 2.067 inches for Schedule 40, so at 150 gpm it loses 0.162 psi per ft instead of 0.199, about 19 percent less.

This article is general information, not a substitute for a project-specific hydraulic calculation. Code editions, local amendments and reviewer practice change; confirm the adopted code and the authority having jurisdiction for the project.

Need Friction Losses Checked in a Sprinkler Calculation?

Send the layout, the pipe schedule and system type, the flow test and the jurisdiction. DGA prepares NFPA 13 hydraulic calculations and shop drawings, or checks the flow, bore, C-factor and fitting inputs in a calculation before it goes to the reviewer. Project briefs get confirmation and preliminary code feedback within one business day.

Send a project brief → View related services

Leave a reply

Your email address will not be published. Required fields are marked *

Quick inquiry

Ready when you are.

Your name, a way to reach you, and where the project is. A licensed PE replies within one business day. Every inquiry is confidential.

Prefer to describe it first? Open the Project Desk

FirmDGA Fire Protection Engineering
SheetFP-5202
OfficesNew York · Harrisburg · Seattle
LicensedNY NJ PA MD DE WA OR FL
Rev11.2026
Sheet index