Sprinkler Systems · Definition
What is a fire department connection and where does it go?
General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.
A fire department connection (FDC) is the inlet on the outside of a building through which a fire engine pumps water into the building’s sprinkler or standpipe system. It goes on the street side of the building or the side facing the fire apparatus access road, fully visible and kept clear, at a spot the fire code official approves under Section 912 of the International Building Code (IBC) and International Fire Code (IFC).
The fitting is small, but three sets of rules meet at it. NFPA 13, the National Fire Protection Association’s sprinkler installation standard, decides when a sprinkler system needs an FDC and how it is piped; Section 912 decides where it goes and how it is marked and kept reachable; and the local fire department decides the details that have to match its own engines and hose. In New York City (NYC) the same fitting is usually called a siamese.
At a Glance: Fire Department Connection (FDC)
- Definition: the exterior inlet, with its check valve, drain, piping and sign, through which a fire engine pumps water into a sprinkler or standpipe system.
- Governing code and section: NFPA 13 (2022) Chapter 16 for sprinkler FDCs, the edition New York State and New Jersey use (Pennsylvania and Maryland county permits use 2019, Delaware 2025, and New York City 2016 as modified by Appendix Q); NFPA 14 for standpipe and combined connections; IBC and IFC Section 912 for location, access, caps and signs.
- Who prepares it or who it applies to: the sprinkler designer shows it on the site plan and riser details, the fire code official or fire department approves its location and hardware, and the owner keeps it clear, capped and tested.
- When it’s required: on most NFPA 13 sprinkler systems and on fire department standpipes. NFPA 13 exempts a few cases, New York City rewrites those exemptions around small systems, and NFPA 13D home systems need none.
- Typical output: a wall-mounted or freestanding connection with two 2 1/2 in. threaded inlets or one large Storz inlet, shown on the site plan and riser detail with its sign, check valve and drain.
- Often confused with: the hydrant that supplies the engine, the standpipe hose valve inside the building, and a fire pump test header, which can look similar on an outside wall but discharges water during pump tests instead of taking it in.
What is a fire department connection?
An FDC lets the fire department add water to a fixed fire protection system from outside the building. The engine draws water from a hydrant, raises its pressure with the engine’s pump and sends it through supply hose into the FDC, which carries it into the system piping.
For a sprinkler system, the FDC backs up the building’s automatic water supply. That matters when more sprinklers open than the design assumed, or when the public main or a fire pump cannot deliver the flow and pressure the system needs. For a manual standpipe, the FDC is the water supply itself, because the piping has no supply able to deliver the standpipe demand on its own.
The FDC is part of the system it serves, so it is drawn, reviewed, tested and maintained with that system. Its inspection, testing and maintenance follow NFPA 25, which the 2021 IFC names for fire department connections in Section 912.7.
What does an FDC assembly include?
An FDC is more than the fitting on the wall. Behind it sit a check valve, a drain, the pipe to the system and a sign that tells the arriving engine company what the connection feeds. The table lists each part, what it does and where the codes address it, with NFPA 13 cited at chapter level in its 2022 edition.
| Component | What it does | Where the code covers it |
|---|---|---|
| Inlet body | Receives the supply hose from the engine. Commonly a two-way body with two 2 1/2 in. threaded swivel inlets, the siamese, or a single large-diameter Storz inlet, on the wall or on a freestanding post. | NFPA 13 (2022) Chapter 16; local fire department rules |
| Threads or Storz coupling | Must mate with the hose the local fire department carries. NFPA 13 defaults to national standard hose threads and lets the authority having jurisdiction name another connection where local hose differs. | NFPA 13 (2022) Chapter 16; IFC 912.3 for standpipe threads |
| Caps or plugs | Keep debris out of the inlets. Locking caps go on where the fire code official requires them and the fire department carries the key wrench. | IFC 912.4.1; 2022 NYC Fire Code (FC) 912.3.1 |
| Check valve | Lets water from the engine into the system and stops system water from flowing back out through an open inlet. | NFPA 13 (2022) Chapter 16 |
| Automatic drain | Empties the short pipe between the check valve and the inlet so trapped water cannot freeze; required where that pipe is subject to freezing. | NFPA 13 (2022) Chapter 16 |
| Pipe to the system | Carries the water to the riser or main and joins the system on the system side of its check valve, with no shutoff valve in the FDC line. | NFPA 13 (2022) Chapter 16 |
| Sign | Names the system the connection serves and the buildings or portions served and, under the 2024 IBC and IFC, gives the standpipe pumping pressure where it is over 150 pounds per square inch (psi). | IFC 912.5 (2024 edition: 912.5.1 to 912.5.4); FC 912.4 |
| Clear space and protection | A working space 36 in. wide, 36 in. deep and 78 in. high in front of and beside the connection, plus impact protection where vehicles could strike it. | IFC 912.4.2 and 912.4.3; FC 912.3.2 and 912.3.3 |
The check valve and the automatic drain work as a pair, keeping the short pipe behind the inlet empty so it cannot freeze. The FDC line is one of several components that meet at the base of the system; DGA’s explainer on what has to be on a sprinkler riser covers the control valve, alarm valve, gauges and drains around it.
When do NFPA 13 and the fire code require an FDC, and which systems are exempt?
NFPA 13 (2022) Chapter 16 makes a fire department connection the default for sprinkler systems and excuses only a few cases: a building in a remote area the fire department cannot reach, a large deluge system that needs more water than the fire department can pump, and a single-story building of 2,000 sq ft or less. Section 912.1 of the IBC and IFC then has each connection installed under the NFPA standard for the system and adds the location, access, cap and sign rules.
New York City rewrites the exemptions. Section Q102 of Appendix Q to the 2022 NYC Building Code replaces the three NFPA 13 (2016) cases in Section 8.17.2.2 with two: a system whose sprinklered area is 2,000 sq ft or less, and a system with 36 or fewer sprinklers unless another section of the standard requires a connection. The remote-area and large-deluge cases do not apply in the city.
The residential standards differ. NFPA 13R, used for low-rise residential buildings, carries its own FDC provision, which New York City rewrites in Section Q104: at least one single 3-inch inlet, two-way connections in Group R-1 buildings, and none in one- and two-family dwellings. NFPA 13D, the standard for one- and two-family dwellings and manufactured homes, does not require an FDC at all.
Standpipe connections follow NFPA 14 and the same Section 912 rules, which IFC Section 905.2 applies to standpipe FDCs. New Jersey adds one FDC requirement for existing buildings: under the Rehabilitation Subcode, a windowless basement of 3,000 to 10,000 sq ft sprinklered from the existing domestic water supply needs an FDC marked “Basement Area Sprinkler Water Supply” and a supervised automatic fire alarm system (New Jersey Administrative Code (N.J.A.C.) 5:23-6.30(c)7).
| Case | Where the rule sits | Notes |
|---|---|---|
| Building in a remote area the fire department cannot reach | NFPA 13 (2022) Chapter 16 | Not an exemption in New York City |
| Large deluge system needing more water than the fire department can pump | NFPA 13 (2022) Chapter 16 | Not an exemption in New York City |
| Single-story building of 2,000 sq ft or less | NFPA 13 (2022) Chapter 16 | New York City uses its own area test (next row) |
| System with a sprinklered area of 2,000 sq ft or less | 2022 NYC Building Code Appendix Q, Section Q102 (NFPA 13 (2016) Section 8.17.2.2 as modified) | New York City only |
| System with 36 or fewer sprinklers | Same Appendix Q entry | New York City only, and not where another section of the standard requires a connection |
| NFPA 13D system in a one- or two-family dwelling | NFPA 13D | No FDC required |
| NFPA 13R system in a one- or two-family dwelling | Appendix Q, Section Q104 (NFPA 13R (2016) Section 6.11 as modified) | New York City; other 13R buildings in the city need at least one 3 in. inlet, and Group R-1 buildings a two-way connection |
Paraphrased by DGA, not NFPA text. NFPA 13 cases are cited at chapter level; Pennsylvania and Maryland county permits apply the 2019 edition and Delaware the 2025 edition.
How is a sprinkler FDC different from a standpipe or combined FDC?
A sprinkler-only FDC feeds one sprinkler system and backs up its automatic supply, so the engine pumps at the pressure the sprinkler demand calls for. A standpipe FDC feeds the risers that serve the 2 1/2 inch hose valves firefighters use inside the building, and NFPA 14 governs it rather than NFPA 13.
A combined FDC serves a combined system, in which the standpipe risers also feed the sprinklers through a floor control valve assembly on each floor. Pumping into it supplies the hose valves and the sprinklers together, so the connection is designed with the standpipe under NFPA 14 and marked for both services; the 2024 IFC has its sign show every service the connection feeds (Section 912.5.3). DGA’s explainer on how a combined sprinkler and standpipe system works covers the riser side.
In New York City the cap color tells the engine company what it is looking at. The 2022 NYC Fire Code assigns red caps marked STANDPIPE to standpipe connections, green caps marked SPRINKLER to automatic sprinkler connections, silver caps marked SPRINKLER to non-automatic sprinkler connections and yellow caps marked COMBINATION STANDPIPE AND SPRINKLER SYSTEMS to combined connections, with the words cast into the cap in letters 1 inch high or shown on a durable non-ferrous metal plate (FC 912.4.1 and 912.4.2). The city’s standpipe FDC rules, including Appendix Q’s sizes and mounting heights, are covered in DGA’s guide to New York City’s standpipe requirements.
Figure 1: Sprinkler-only FDC vs combined sprinkler and standpipe FDC
- Feeds one NFPA 13 sprinkler system
- Backs up the system’s automatic water supply
- Check valve in the FDC line, an automatic drain where the line can freeze, and no shutoff valve
- Sign names the sprinkler service (IFC 912.5); green caps marked SPRINKLER in New York City
- New York City size: two-way, at least 5 in., or 4 in. for one system with a riser under 5 in.
- Feeds standpipe risers that also feed each floor’s sprinklers
- Designed with the standpipe system under NFPA 14
- One hookup supplies the hose valves and the sprinklers together
- Sign lists every service fed (2024 IFC 912.5.3); yellow caps marked COMBINATION STANDPIPE AND SPRINKLER SYSTEMS in New York City
- Pumping pressure on the sign where it exceeds 150 psi (2024 IFC 912.5.4)
DGA designs sprinkler and standpipe systems, including the FDC location and the piping to the riser, across New York, New Jersey, Pennsylvania, Maryland, Delaware, Washington, Oregon and Florida. Project briefs get confirmation and preliminary code feedback within one business day. See where DGA works →
Where does the FDC go on the building, and who decides?
The fire code official decides. Section 912.2 of the IBC and IFC makes the FDC location subject to the fire code official’s approval and requires that an engine and hose connected to it not block access to the building for other fire apparatus. Section 912.2.1 then places the connection on the street side of the building or facing an approved fire apparatus access road, in plain view and easy to identify from the street, the access road or the closest point a fire engine can reach, unless the fire code official approves another location.
On an existing building where the FDC cannot be seen from the approach, Section 912.2.2 calls for an approved sign with the letters FDC at least 6 inches high to show where it is. Section 912.4 keeps the connection reachable at all times, with no fences, plantings or stored items in the way. It also requires a clear working space 36 inches wide, 36 inches deep and 78 inches high in front of and beside the connection (Section 912.4.2) and impact protection where vehicles could strike it (Section 912.4.3).
The hydrant distance is mostly a local rule. Where the IFC is the fire code, a building with a standpipe needs a hydrant within 100 ft of its FDC unless the fire code official approves a longer distance (IFC Section 507.5.1.1). For sprinkler-only FDCs, Montgomery County, Maryland, asks for a hydrant within 100 ft and Prince George’s County within 200 ft, while the NYC Fire Code sends the distance to the city’s Building Code (FC 912.2.2).
The FDC and the riser are planned together. The FDC pipe has to run from the outside wall to the system and join it on the system side of the check valve, with no shutoff valve in the line (NFPA 13 (2022) Chapter 16), so the approved FDC location and the riser room location affect each other.
Figure 2: Where the FDC sits: Street side, hydrant, entrance and riser
Who approves the location differs by state. In Delaware, the fire department’s chief officer sets the FDC location in writing within 5 working days, and the State Fire Marshal decides if the chief does not (Regulation 702, Chapter 4, Section 1.3). In New York City, the Fire Department of the City of New York (FDNY) can approve a location other than the street side (FC 912.2.1), and in New Jersey the fire protection subcode official in the municipal construction office reviews the FDC with the sprinkler plans under the Uniform Construction Code (UCC).
What do local fire departments add: Threads, Storz couplings, signs and locks?
Local fire departments shape the FDC hardware because the connection has to fit their hose. NFPA 13 (2022) Chapter 16 defaults to inlets with national standard hose threads and lets the authority having jurisdiction (AHJ) name a different connection where local hose does not match. Delaware writes the same idea into its own rules: FDC threads must be compatible with the local fire company (Regulation 702, Chapter 4, Section 1.3).
Some departments require a Storz inlet, a threadless quick-connect coupling, in place of threaded inlets. The Syracuse Fire Department in New York requires a 4-inch Storz connection on all new FDC installations and on systems undergoing major renovation, mounted 18 to 48 inches above grade (Fire Department Connection Bulletin, October 2022). Upper Dublin Township in Montgomery County, Pennsylvania, requires 5-inch Storz fittings on sprinkler intake connections (Township Code Section 117-7).
Montgomery County, Maryland, writes its FDC rules into the Department of Permitting Services (DPS) submittal requirements for NFPA 13 systems, a 2016 document DPS still posts as of November 2026. The FDC sits within 100 ft of a hydrant with inlet centerlines 18 to 48 inches above grade, and the number of 2 1/2 inch inlets follows the system demand: 2 up to 749 gallons per minute (gpm), 3 from 750 to 999 gpm and 4 at 1,000 gpm or more. Multiple FDCs serving one building are interconnected, and each FDC is at least the size of the main riser or the fire pump discharge, whichever is larger.
Locks and signs are the other common additions. Syracuse requires Knox keyed locking caps, which the IFC lets the fire code official require (Section 912.4.1). The 2024 IBC and IFC sign rules (Sections 912.5.1 to 912.5.4) cover lettering, the buildings or portions served, every service on a combined connection and the standpipe pumping pressure where it exceeds 150 psi; New Jersey adopted them effective August 17, 2026, as DGA’s summary of what New Jersey’s 2024 code adoption changed for fire protection explains. Delaware requires a raised-letter sign at least 1 inch high giving the required pressure, except where the system demand is under 150 psi (Regulation 702, Chapter 4, Section 1.3).
Which FDC rules apply in New York, New Jersey, Pennsylvania, Maryland and Delaware?
Every jurisdiction in the region builds on the same NFPA 13 and Section 912 framework, with different editions and different local additions. The table lists each one’s code and NFPA 13 edition, local FDC rules, reviewer and filing, as of November 2026.
| Jurisdiction | Code and NFPA 13 edition | FDC rules added locally | Who reviews | Filing |
|---|---|---|---|---|
| New York State (outside NYC) | 2025 Uniform Code: Building Code and Fire Code of New York State, based on the 2024 IBC and IFC; NFPA 13 (2022) | No New York amendment to Section 912 in the 2025 rule text. Local fire departments set the hardware: the Syracuse Fire Department requires 4 in. Storz inlets, Knox locking caps and an 18 to 48 in. mounting height (bulletin, October 2022). | Local code enforcement official; in Syracuse, the Fire Department approves the FDC location | Building permit with sealed sprinkler drawings under New York Codes, Rules and Regulations (NYCRR) Title 19, Part 1203 |
| New York City | 2022 NYC Building Code and Fire Code; NFPA 13 (2016) as modified by Appendix Q | Two-way FDC of at least 5 in. (4 in. for one system with a riser under 5 in.); no FDC for systems of 2,000 sq ft or less or with 36 or fewer sprinklers unless another section requires one; FC 912: street side, with red, green, silver or yellow caps by system type and 1 in. cast letters | Department of Buildings (DOB) for plans and permit; FDNY on FDC location and caps under the Fire Code | DOB NOW: Build, sprinkler (SP) work type |
| New Jersey | UCC on the 2024 International Codes since August 17, 2026; NFPA 13 (2022) | Section 912.1A: connections arranged so pumping into any one sprinkler connection serves all sprinklers, with a connection per zone allowed in a high-rise designed with low and high zones; 2024 IBC sign rules; Rehabilitation Subcode basement FDC (N.J.A.C. 5:23-6.30(c)7) | Fire protection subcode official in the municipal construction office; Department of Community Affairs (DCA) for state projects | Construction permit: Form F100 with the F140 fire protection technical section |
| Pennsylvania | Pennsylvania Uniform Construction Code on the 2021 International Codes since January 1, 2026; NFPA 13 (2019); IFC only by local ordinance | No statewide FDC rule beyond IBC Section 912. Municipalities set the hardware: Upper Dublin Township requires 5 in. Storz fittings on sprinkler intake connections (Township Code Section 117-7). | Municipal code official or third-party agency; the Department of Labor and Industry where it is the code official; Philadelphia’s Department of Licenses and Inspections; Pittsburgh’s Department of Permits, Licenses, and Inspections | Building permit with fire protection plans; FDCs are within the scope of Philadelphia’s Fire Suppression Systems Permit and Pittsburgh’s Suppression Systems Permit |
| Maryland | Maryland Building Performance Standards on the 2021 IBC, with no amendment to Section 912; NFPA 13 (2019) through the county permit | Montgomery County: hydrant within 100 ft, inlets 18 to 48 in. above grade, 2 to 4 inlets of 2 1/2 in. by system demand. Prince George’s County: hydrant within 200 ft (Subtitle 4, Section 4-164). Baltimore County: 15 ft kept clear around the FDC. Baltimore City: 2021 IFC Section 912 as published. | Montgomery DPS; Prince George’s Department of Permitting, Inspections and Enforcement (DPIE); Baltimore City Fire Department; Baltimore County Department of Permits, Approvals and Inspections; the Office of the State Fire Marshal where the county does not review | County fire protection system permit |
| Delaware | Regulation 701 (2026) with NFPA 1 (2024) and NFPA 13 (2025); IBC by county (2021 in New Castle and Sussex, 2018 in Kent and Wilmington) | Regulation 702, Chapter 4, Section 1.3: threads compatible with the local fire company; location set in writing by the fire department’s chief officer within 5 working days, or by the State Fire Marshal; raised-letter pressure sign at least 1 in. high unless the system demand is under 150 psi | Office of the State Fire Marshal; city fire marshals in Wilmington, Dover, Newark and New Castle | State Fire Marshal water-based suppression system plan submittal with the Preliminary Sprinkler Form |
Adoptions as of November 2026. Local rules are examples from published agency documents, not a complete list for each state.
In Maryland, the county building permit reviews sprinklers to NFPA 13 (2019) through the 2021 IBC, while the State Fire Prevention Code (NFPA 1, 2024) references NFPA 13 (2022). In New Jersey, a complete application submitted under the prior codes through February 17, 2027 uses NFPA 13 (2019).
Key Takeaway: A fire department connection is the outside inlet, with its check valve, drain, pipe and sign, through which a fire engine pumps water into a sprinkler or standpipe system. NFPA 13 makes one the default on sprinkler systems with narrow exemptions, which New York City rewrites around small systems, and NFPA 13D homes need none. Section 912 of the IBC and IFC puts the FDC on the street side, fully visible, with a clear space 36 inches wide, 36 inches deep and 78 inches high, at a location the fire code official approves, while local fire departments and counties add their own rules on hydrant distance, couplings, caps and signs.
Frequently asked questions
Does every sprinkler system need a fire department connection?
No. NFPA 13 (2022) Chapter 16 requires one on most systems but exempts buildings in remote areas the fire department cannot reach, large deluge systems that need more water than the fire department can pump, and single-story buildings of 2,000 sq ft or less. New York City replaces those cases with systems covering 2,000 sq ft or less or having 36 or fewer sprinklers, and NFPA 13D home systems need no connection.
How far can an FDC be from a fire hydrant?
Conditional: it depends on the fire code and the local rules. Where the IFC is the fire code, a building with a standpipe needs a hydrant within 100 ft of the FDC unless the fire code official approves more (Section 507.5.1.1). For sprinkler-only connections the distance is set locally, such as 100 ft in Montgomery County, Maryland, and 200 ft in Prince George’s County, and the NYC Fire Code sends it to the city’s Building Code.
Does an FDC need a check valve?
Yes. NFPA 13 (2022) Chapter 16 calls for a check valve in each fire department connection, so water pumped by the engine reaches the system while system water cannot flow back out through an open inlet. Where the pipe between that check valve and the inlet could freeze, an automatic drain keeps it empty.
Can the FDC line pass through a shutoff valve?
No. NFPA 13 (2022) Chapter 16 does not allow a shutoff valve in the fire department connection piping, which joins the system on the system side of the check valve. A valve that could be left closed in that line would cut the engine off from the sprinklers.
Who decides where the FDC goes?
The fire code official, who approves the location under Section 912.2 of the IBC and IFC, with the street side or the side facing an approved fire apparatus access road as the default. In Delaware the fire department’s chief officer sets it in writing within 5 working days, or the State Fire Marshal decides, and in New York City FDNY can approve a location other than the street side.
More in Sprinkler Systems
- What Is NFPA 13? A Plain-English Guide for Owners
- When Does a Sprinkler System Need Seismic Bracing?
- How Do You Size a Water Supply for a 13R or 13D System?
- Do Balconies and Decks Need Sprinklers Under NFPA 13R?
- When Does a Stage or Exhibit Hall Need Special Sprinklers?
- Do Closets, Bathrooms and Small Rooms Need Sprinklers?
This article is general information, not a substitute for a project-specific code analysis. Code editions, local amendments and fire department requirements change; confirm the adopted code and the authority having jurisdiction for the project.
Placing an FDC on a New or Altered Building?
Send the site plan, the system type and the jurisdiction. DGA locates the fire department connection and the riser, coordinates the location and hardware with the fire department and prepares the drawings for review. Project briefs get confirmation and preliminary code feedback within one business day.