Sprinkler Systems · Trigger
Do elevator machine rooms and hoistways need sprinklers?
General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.
Elevator machine rooms and hoistways need sprinklers whenever the building is sprinklered throughout to NFPA 13, the sprinkler standard of the National Fire Protection Association (NFPA), unless one of the standard’s elevator omissions applies. New York City (NYC) is the exception: its Building Code does not permit sprinklers in elevator machine rooms, machinery spaces, control rooms or control spaces at all.
Outside NYC, the answer turns on the elevator and the materials around it. A hydraulic elevator keeps a sprinkler in its machine room and a sidewall sprinkler in its pit, while a traction elevator in a noncombustible hoistway can usually go without pit and top-of-hoistway sprinklers, and without machine room sprinklers when the room meets the standard’s conditions. Every sprinkler that stays brings a power shutdown: the International Building Code (IBC) requires a means, installed under NFPA 72, that disconnects the elevator’s main line power before water is applied (Section 3005.5).
At a Glance: Sprinklers in Elevator Machine Rooms and Hoistways
- Threshold(s) with units: every machine room, machinery space, control room, control space and hoistway in a building sprinklered throughout to NFPA 13, unless an omission applies; a pit sprinkler of the sidewall type no more than 2 ft above the pit floor; standard-response sprinklers in machine rooms, machinery spaces and control spaces; shutdown heat detectors within 2 ft of each sprinkler.
- Code, edition, section: NFPA 13 (2022) Section 9.3.6 (Sections 9.2.14 and 9.3.6 in the 2025 edition), with each jurisdiction applying its adopted edition (2016 in NYC as modified by Appendix Q, 2019 in Pennsylvania and the Maryland county permits, 2022 in New York State and New Jersey, 2025 in Delaware); IBC Sections 3005.5, 3005.4 and 903.3.1.1.1; NFPA 72 Chapter 21 (Section 21.4 in the 2022 edition); ASME A17.1/CSA B44, the elevator safety code of the American Society of Mechanical Engineers (ASME) and CSA Group; 2022 NYC Building Code Sections 903.2 and 3005.5.
- Main exceptions: traction elevator machine rooms, machinery and control spaces and hoistways that are dedicated to elevator equipment, protected by smoke detection, enclosed in the rated construction the building code requires and free of unrelated storage; the pit of an enclosed noncombustible hoistway with no combustible hydraulic fluid; the top of a passenger elevator hoistway that is noncombustible or limited-combustible with a car enclosure that meets ASME A17.1; machine rooms of fire service access and occupant evacuation elevators protected by automatic fire detection (IBC Section 903.3.1.1.1).
- What applies once triggered: a shunt trip that disconnects main line power automatically before water flows, set off by heat detectors rated lower and more sensitive than the sprinklers or by a waterflow switch with no time delay; the means does not reset itself, and sprinklers outside the elevator spaces must not trip it (IBC Section 3005.5; NFPA 72 Chapter 21).
- Permit or filing: the elevator sprinklers go on the sprinkler drawings filed with the sprinkler permit (a sprinkler (SP) filing with the NYC Department of Buildings (DOB); the building permit, a suppression permit, a county fire protection permit or a State Fire Marshal submittal elsewhere), and the heat detectors and shutdown circuit go on the fire alarm drawings.
- Who decides: the official reviewing the sprinkler drawings accepts or rejects each omission and the shutdown design: DOB in NYC, the local code enforcement official in New York State, the fire protection subcode official in New Jersey, the code official or third-party agency in Pennsylvania, the county in Maryland, and the State Fire Marshal or a city fire marshal in Delaware.
When does NFPA 13 require sprinklers in elevator machine rooms and hoistways?
NFPA 13 reaches elevator spaces through the building code. Where the IBC requires a building to be sprinklered throughout, Section 903.3.1.1 sends the design to NFPA 13, and the standard covers every room and shaft unless its own text or IBC Section 903.3.1.1.1 lets a space go without. Whether the building needs sprinklers in the first place is a separate question, answered by the occupancy thresholds in IBC Section 903.2 and explained in DGA’s guide to when a building needs fire sprinklers.
NFPA 13 (2022) handles elevators in Chapter 9, the chapter on where sprinklers go and where they may be left out. Its starting point is sprinklers in the machine room and at the top and bottom of the hoistway, and its omissions then remove them where the elevator and its enclosure carry little fuel. In Maryland, the county building permit reviews sprinklers to NFPA 13 (2019) through the 2021 IBC, while the State Fire Prevention Code (NFPA 1, 2024) references NFPA 13 (2022).
The conditions track the fire risk. Machine rooms hold motors, controllers and, with a hydraulic elevator, oil, and they can end up holding spare parts and other stored material; pits collect debris and, under a hydraulic elevator, hydraulic fluid. NFPA 13 ties its omissions to exactly those points: no hydraulic machinery, no unrelated storage, a rated enclosure and automatic detection.
Buildings designed to NFPA 13R or NFPA 13D follow those standards’ own lists of where sprinklers may be omitted. The table below covers NFPA 13 systems and sets each elevator space against the model rule and the NYC rule.
| Elevator space | Sprinklers required? | Condition or exception | Code basis | New York City (2022 Building Code) |
|---|---|---|---|---|
| Machine room or control room, traction elevator | Yes, unless omitted | Omit when the room is dedicated to elevator equipment, has smoke or other automatic detection under NFPA 72, has the fire-resistance rating the building code requires and holds no unrelated storage | NFPA 13 (2022) Ch. 9; IBC Section 3005.4 for the enclosure rating | Not permitted (Sections 903.2, exception 2, and 3005.5) |
| Machine room, hydraulic elevator | Yes | The traction elevator omission does not cover hydraulic machinery | NFPA 13 (2022) Ch. 9 | Not permitted (Sections 903.2 and 3005.5) |
| Machinery space or control space, including machine-room-less (MRL) designs | Yes, unless omitted | Same conditions as a traction elevator machine room | NFPA 13 (2022) Ch. 9 | Not permitted (Section 3005.5) |
| Top of hoistway | Yes, unless omitted | Omit for a passenger elevator whose hoistway is noncombustible or limited-combustible and whose car enclosure meets ASME A17.1, or under the traction elevator conditions | NFPA 13 (2022) Ch. 9 | Allowed where required (Section 3002.9), with a shutdown under Section 3005.5 |
| Pit | Yes: sidewall sprinkler no more than 2 ft above the pit floor | Omit in an enclosed noncombustible hoistway with no combustible hydraulic fluid | NFPA 13 (2022) Ch. 9 | NFPA 13 (2016) as modified by Appendix Q, with a shutdown under Section 3005.5 |
| Fire service access or occupant evacuation elevator | No | Machine rooms and control spaces exempt where automatic fire detection protects them; their hoistways get no sprinklers either, and neither elevator gets a shunt trip | IBC Sections 903.3.1.1.1, 3007 and 3008 | Not installed in machine rooms, control spaces or hoistways (Sections 3007.2.1 and 3008.3.1) |
NFPA 13 editions as of November 2026: 2016 in NYC as modified by Appendix Q, 2019 in Pennsylvania and the Maryland county permits, 2022 in New York State and New Jersey, 2025 in Delaware. An omission applies only when all of its conditions are met.
Which hoistway and pit locations need sprinklers?
NFPA 13 looks at the hoistway at two points, the pit and the top. In the pit, the standard calls for a sidewall sprinkler no more than 2 ft above the pit floor, low enough to reach debris and spilled fluid. The pit sprinkler may be left out where the hoistway is enclosed, noncombustible and holds no combustible hydraulic fluid, which in practice means a traction elevator in a noncombustible shaft.
At the top of the hoistway the standard calls for an upright, pendent or sidewall sprinkler. That sprinkler may be left out for a passenger elevator whose hoistway is noncombustible or limited-combustible and whose car enclosure materials meet ASME A17.1. A traction elevator hoistway can also use the same omission as a traction elevator machine room, covered below.
Elevators hung on coated steel belts instead of wire ropes add one more check. NFPA 13 brings sprinklers back to the top and the pit of the hoistway when the belt material does not pass the FT-1 flame test the standard names, so the elevator manufacturer’s data on the suspension belongs in the sprinkler submittal.
The elevator code also limits what piping may run in a hoistway. The NYC Building Code, for example, allows piping in a hoistway only as ASME A17.1/CSA B44 Section 2.8 permits, and it lets sprinklers into the hoistway where the code requires them (Sections 3001.5 and 3002.9). The sprinkler layout and the elevator layout are therefore settled together.
How do the elevator code and the fire alarm code change the design?
Water reaching an energized controller, hoist machine or brake can leave an elevator operating unpredictably, so the codes remove power before the water arrives. IBC Section 3005.5 requires that, wherever the hoistway, machine room, control room or control space holding elevator control equipment is sprinklered, a means installed under Chapter 21 of NFPA 72 disconnects the main line power to the affected elevator automatically before water is applied. The means must not reset itself, and a sprinkler operating outside those spaces must not cut the elevator’s power.
NFPA 72 (2022) Section 21.4 sets how the means works. Heat detectors are the usual trigger: each sits within 2 ft of a sprinkler and has a lower temperature rating and a higher sensitivity than that sprinkler, so it operates first. A waterflow switch may trigger the shutdown instead, but only one with no time delay, and the control circuit that trips the power is monitored so that a loss of voltage shows as a supervisory signal at the fire alarm panel.
The elevator code carries its own side of the same rule. ASME A17.1 Section 2.8 requires sprinklers in elevator spaces to be installed under NFPA 13 and requires the elevator’s main line power to be removed automatically when sprinkler water could affect the elevator. The IBC references ASME A17.1-2016 in its 2018 edition and ASME A17.1-2019 in its 2021 edition (Section 3001.2 among others), and NYC applies the standard as modified by Appendix K of its Building Code (Section 3001.2).
Smoke detectors play a different part. They start the elevator recall that sends the cars to the designated level, a fire alarm sequence governed by NFPA 72 and ASME A17.1, and they satisfy the detection condition for leaving sprinklers out. The shutdown itself runs on heat detectors or a waterflow switch, not on smoke detection.
| Device | Requirement | Code basis |
|---|---|---|
| Machine room or control space sprinkler | Standard response; left out for a traction elevator that meets all five omission conditions | NFPA 13 (2022) Sections 9.3.6.3 and 9.3.6.4; ASME A17.1 Section 2.8 |
| Top-of-hoistway sprinkler | Required unless the passenger car and hoistway qualify for the omission | NFPA 13 (2022) Sections 9.3.6.5 and 9.3.6.6; car enclosure materials under ASME A17.1 |
| Pit sprinkler | Sidewall type, no more than 2 ft above the pit floor, unless the hoistway qualifies for the omission | NFPA 13 (2022) Ch. 9 |
| Heat detector | Within 2 ft of each sprinkler the shutdown covers; lower temperature rating and higher sensitivity than the sprinkler | NFPA 72 (2022) Ch. 21 |
| Waterflow switch (alternative trigger) | No time delay; sees flow only from the elevator sprinklers, since flow elsewhere must not cut power | NFPA 72 (2022) Ch. 21; IBC Section 3005.5 |
| Main line disconnect with shunt trip | Opens automatically before water is applied and does not reset itself; its control circuit is monitored for voltage, with a loss shown as a supervisory signal | IBC Section 3005.5; NFPA 72 (2022) Ch. 21; ASME A17.1 Section 2.8 |
| Smoke detectors | Start elevator recall and satisfy the detection condition of the traction elevator omission; not used to trip the shutdown | NFPA 72 (2022) Ch. 21; NFPA 13 (2022) Ch. 9; ASME A17.1 |
Chapter-level citations to the 2022 editions; NYC applies NFPA 13 (2016) and NFPA 72 (2016), each as modified by Appendix Q of its Building Code.
Figure 1: Where the sprinklers, detectors and shunt trip sit
DGA designs sprinkler protection for elevator machine rooms, hoistways and pits, and coordinates the heat detectors and shunt trip with the fire alarm and electrical design, across New York, New Jersey, Pennsylvania, Maryland, Delaware, Washington, Oregon and Florida. Project briefs get confirmation and preliminary code feedback within one business day. See where DGA works →
Which exceptions remove sprinklers from machine rooms or hoistways?
The broadest is the traction elevator omission in NFPA 13 (2022) Section 9.3.6.3. Sprinklers may be left out of the machine rooms, machinery spaces, control rooms, control spaces and hoistways of traction elevators when all five of these conditions hold:
- The space is dedicated to elevator equipment only.
- Smoke detectors or other automatic fire detection installed under NFPA 72 protect it.
- Walls and floor or roof assemblies with the fire-resistance rating the building code requires separate it from the rest of the building.
- No material unrelated to the elevator is stored in it.
- The elevator machinery is not hydraulic.
The rating in the third condition comes from the building code. IBC Section 3005.4 encloses machine rooms, control rooms, control spaces and machinery spaces outside the hoistway with construction rated at least as high as the hoistway they serve, with reductions for some spaces that do not abut or open into it. A hydraulic elevator fails the fifth condition, so outside NYC its machine room keeps its sprinklers.
The IBC adds exempt locations of its own in Section 903.3.1.1.1, each conditioned on an approved automatic fire detection system. Two concern elevators: the machine rooms and machinery spaces of fire service access elevators, and the machine rooms, machinery spaces, control rooms and control spaces of occupant evacuation elevators (2021 IBC). For fire service access and occupant evacuation elevators, IBC Sections 3007 and 3008 go further, barring sprinklers from the machine room, control spaces and hoistway and barring the shunt trip, because those cars have to keep running during a fire.
The same exempt-location list holds the 2-hour generator and transformer room exemption covered in DGA’s guide to sprinklers in electrical rooms and transformer vaults. NFPA 13’s other small-space omissions are set out in the guide to which closets, bathrooms and small rooms can go without sprinklers.
An omission is part of the standard, not a variance, but the reviewing official checks every condition on the drawings and at inspection. A machine room later used for storage, or a detector taken out of service, puts the space back under the sprinkler requirement.
Figure 2: Sprinklers, detectors and shunt trip at an elevator
What applies once sprinklers are installed in elevator spaces?
Sprinklers in machine rooms, machinery spaces and control spaces are standard response under NFPA 13 (2022) Section 9.3.6.4. The heat detector beside each one must be rated below the sprinkler, so the two are chosen as a pair.
The shutdown has three fixed traits under IBC Section 3005.5: it acts automatically, it acts before water reaches the equipment, and it stays tripped until someone resets it. Flow from sprinklers elsewhere in the building must not trip it, which is why a waterflow switch serving a whole floor or riser cannot be the trigger.
That rule shapes the piping. Where a waterflow switch starts the shutdown, the elevator sprinklers are usually fed by their own branch with a dedicated control valve and waterflow switch outside the machine room and hoistway, where the valve can be supervised and reached without entering the elevator spaces. DGA’s guide to sprinkler zones and floor control valves covers how valves and zones are laid out.
The sprinkler designer, the fire alarm designer and the electrical engineer, who specifies the shunt trip device on the elevator’s main line disconnect, work from one sequence of operation. At acceptance the shutdown is tested with the rest of the system: the detectors or switch operate, the disconnect opens and stays open, and the reset is manual.
How do New York City and the other jurisdictions differ?
New York City reverses the model rule for machine rooms. The 2022 NYC Building Code does not permit sprinklers in elevator machine rooms or elevator machinery spaces (Section 903.2, exception 2), and Section 3005.5 extends the bar to control rooms and control spaces. Appendix Q of the same code edits NFPA 13 (2016) to match, striking its reference to sprinklers in elevator machine rooms.
Hoistways are treated differently. NYC allows sprinklers in a hoistway where the code otherwise requires them (Section 3002.9), and where a hoistway is sprinklered, Section 3005.5 calls, where required, for a means under NFPA 72 as modified by Appendix Q that disconnects the elevator’s main line power before water is applied and does not reset itself. Fire service access and occupant evacuation elevators get no sprinklers in their machine rooms, control spaces or hoistways (Sections 3007.2.1 and 3008.3.1), and DOB reviews the sprinkler work as an SP filing in DOB NOW: Build.
Elsewhere the model rules apply through each jurisdiction’s adopted code, and the main differences are editions. New Jersey and New York State are on the 2024 IBC, Pennsylvania and the Maryland county permits on the 2021 IBC, and Delaware’s counties and cities on the 2018, 2021 or 2024 IBC, while the Delaware State Fire Marshal reviews sprinkler plans to NFPA 13 (2025). New Jersey’s only change to the exempt-location list names its fire protection subcode official in place of the fire code official, Pennsylvania’s only change to IBC Chapter 9 is to the NFPA 13R section (903.3.1.2), the Maryland Building Performance Standards leave Section 903 unamended, and Delaware’s Regulation 701 adopts NFPA 13 without amendment.
| Jurisdiction | Codes in force (as of November 2026) | Elevator-space rule or local amendment | Who reviews the sprinkler filing |
|---|---|---|---|
| New York City | 2022 NYC Building Code; NFPA 13 (2016) and NFPA 72 (2016) as modified by Appendix Q; ASME A17.1/CSA B44 as modified by Appendix K | No sprinklers in elevator machine rooms, machinery spaces, control rooms or control spaces (Sections 903.2 and 3005.5); hoistway sprinklers where required, with a shutdown under Section 3005.5 | DOB, SP filing in DOB NOW: Build |
| New York State (outside NYC) | 2025 Building Code of New York State on the 2024 IBC, in effect since December 31, 2025; NFPA 13 (2022); NFPA 72 (2022) | The 2025 rule text adds no New York amendment to Chapter 9 or Chapter 30 of the building code | Local code enforcement official under 19 NYCRR (New York Codes, Rules and Regulations) Part 1203, with the building permit |
| New Jersey | Uniform Construction Code (UCC) on the 2024 IBC, effective August 17, 2026; NFPA 13 (2022); NFPA 72 (2022) | The only change to the exempt-location list (Section 903.3.1.1.1) names the fire protection subcode official | Fire protection subcode official in the municipal construction office |
| Pennsylvania | UCC on the 2021 IBC since January 1, 2026; NFPA 13 (2019); NFPA 72 (2019); no statewide fire code | The only change to IBC Chapter 9 is to Section 903.3.1.2 (NFPA 13R) | Municipal code official or third-party agency; Department of Labor and Industry (L&I) where the municipality does not enforce; Philadelphia’s Department of Licenses and Inspections (Fire Suppression Systems Permit); Pittsburgh’s Department of Permits, Licenses, and Inspections (Suppression Systems Permit) |
| Maryland | Maryland Building Performance Standards (2021 IBC) through the county permit, with NFPA 13 (2019) and NFPA 72 (2019); State Fire Prevention Code with NFPA 1 and 101 (2024), which reference NFPA 13 (2022) and NFPA 72 (2022) | The Building Performance Standards make no amendment to IBC Section 903 | County permit office (Montgomery, Prince George’s, Baltimore City, Baltimore County and others); Office of the State Fire Marshal where no county office reviews |
| Delaware | IBC by jurisdiction: 2021 in New Castle and Sussex counties, 2018 in Kent County and Wilmington, 2024 in the City of New Castle; Regulation 701 (2026) with NFPA 13 (2025) and NFPA 72 (2025) | Regulation 701 adopts NFPA 13 with no Delaware amendment | Office of the State Fire Marshal; city fire marshals in Wilmington, Dover, Newark and the City of New Castle |
Editions and offices as of November 2026. A complete New Jersey application filed under the prior, 2021-based codes through February 17, 2027 uses NFPA 13 (2019). The 2018 IBC references ASME A17.1-2016 and the 2021 IBC references ASME A17.1-2019.
Key Takeaway: In a building sprinklered throughout to NFPA 13, elevator machine rooms and hoistways get sprinklers unless an omission applies: traction elevator spaces that are dedicated, smoke-detected, fire-rated and storage-free; the pit of an enclosed noncombustible hoistway without hydraulic fluid; the top of a passenger hoistway with a noncombustible shaft and an ASME A17.1 car; and fire service access and occupant evacuation elevator machine rooms with automatic detection. Every sprinkler that stays needs a shunt trip that cuts main line power before water flows (IBC Section 3005.5). New York City does not permit sprinklers in elevator machine rooms, machinery spaces or control spaces at all.
Frequently asked questions
Do elevator pits need sprinklers?
Conditional: NFPA 13 calls for a sidewall sprinkler no more than 2 ft above the floor of an elevator pit and lets it be left out where the hoistway is enclosed, noncombustible and free of combustible hydraulic fluid. A hydraulic elevator therefore keeps its pit sprinkler, while a traction elevator in a noncombustible shaft usually does not need one. Coated suspension belts that fail the FT-1 flame test named in NFPA 13 bring sprinklers back to the pit and the top of the hoistway.
Why do sprinklered elevator machine rooms need shunt trip?
Water on an energized controller, hoist machine or brake can leave an elevator operating unpredictably, so IBC Section 3005.5 requires a means, installed under NFPA 72, that disconnects the main line power to the elevator automatically before sprinkler water is applied. Heat detectors rated lower and more sensitive than the sprinklers, or a waterflow switch with no time delay, trip the power, and the means does not reset itself.
Can sprinklers be omitted from elevator hoistways?
Yes, in several cases. NFPA 13 lets a traction elevator hoistway go without sprinklers when it is dedicated to elevator equipment, protected by smoke detection, enclosed in rated construction and free of storage; it also drops the top sprinkler for a passenger elevator with a noncombustible or limited-combustible hoistway and an ASME A17.1 car enclosure, and the pit sprinkler in an enclosed noncombustible hoistway with no hydraulic fluid. The IBC keeps sprinklers out of fire service access elevator hoistways (Section 3007).
Do machine-room-less elevators change the sprinkler rules?
Conditional: a machine-room-less elevator moves the drive machine into the hoistway and the controller into a control space or the hoistway, so those become the spaces the omissions and the shunt trip apply to. The NFPA 13 traction elevator omission covers machinery spaces, control spaces and hoistways, so a traction machine-room-less hoistway can go without sprinklers under the same five conditions as a machine room, but coated belts that fail the FT-1 flame test bring sprinklers back. In New York City, which bars sprinklers from machinery and control spaces, the design team settles the treatment of the hoistway with the Department of Buildings.
Are sprinklers allowed in elevator machine rooms in New York City?
No. The 2022 NYC Building Code does not permit sprinklers in elevator machine rooms or machinery spaces (Section 903.2, exception 2) and extends the bar to control rooms and control spaces (Section 3005.5). Sprinklers are allowed in a hoistway where the code otherwise requires them, and a sprinklered hoistway gets, where required, a means under NFPA 72, as modified by Appendix Q, that cuts the main line power to the elevator before water is applied.
More in Sprinkler Systems
- What Is NFPA 13? A Plain-English Guide for Owners
- When Does a Sprinkler System Need Seismic Bracing?
- How Do You Size a Water Supply for a 13R or 13D System?
- Do Balconies and Decks Need Sprinklers Under NFPA 13R?
- When Does a Stage or Exhibit Hall Need Special Sprinklers?
- Do Closets, Bathrooms and Small Rooms Need Sprinklers?
This article is general information, not a substitute for a project-specific code analysis. Code editions, local amendments and reviewer practice change; confirm the adopted code and the authority having jurisdiction for each project.
Planning an Elevator in a Sprinklered Building?
Send the elevator type, the machine room or machine-room-less layout, the hoistway construction and the jurisdiction. DGA confirms where sprinklers go, which omissions apply and how the heat detectors and shunt trip tie into the fire alarm and electrical design. Project briefs get confirmation and preliminary code feedback within one business day.