Sprinkler Systems · Definition
What are Light, Ordinary and Extra Hazard occupancies?
General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.
Light, ordinary and extra hazard are the occupancy hazard classes that NFPA 13, the National Fire Protection Association (NFPA) sprinkler standard, uses to rank a room or area by how much it holds that can burn and how fast a fire there would grow. There are five: light hazard for spaces such as offices, Ordinary Hazard Groups 1 and 2 for spaces such as restaurant kitchens, stores and machine shops, and Extra Hazard Groups 1 and 2 for spaces where fires grow fast, such as saw mills and rooms where flammable liquids are sprayed. The class sets how much water the system must deliver and over how large an area, so a wrong class means a system sized for the wrong fire.
DGA’s plain-English guide to NFPA 13 explains how the standard works with the building code. This article covers what each class means, where each edition used in New York, New Jersey, Pennsylvania, Maryland and Delaware defines the classes, how they differ from the commodity classes used for storage, when a space needs to be classified again, and what the class changes in the design.
At a Glance: Light, Ordinary and Extra Hazard Occupancies
- Definition: the five NFPA 13 occupancy hazard classes (light hazard; Ordinary Hazard Groups 1 and 2; Extra Hazard Groups 1 and 2), which rank an area by the quantity and combustibility of its contents, the expected rate of heat release, the height of stockpiles and the presence of flammable or combustible liquids.
- Governing code and section: NFPA 13 (2022) Section 4.3, with examples in the annex to Chapter 4; Section 4.3 also in the 2019 and 2025 editions, with different subsection numbers; Chapter 5 in the 2016 edition that New York City enforces through Appendix Q of its Building Code, which makes no change to that chapter.
- Who prepares it: the sprinkler system designer, who classifies every area of an NFPA 13 building from the owner’s statement of its intended use and contents; the authority having jurisdiction (AHJ) accepts or questions the classification at plan review.
- When it’s required: in every NFPA 13 design and every modification of an NFPA 13 system, and again whenever the use, contents, process or storage height of a space changes.
- Typical output: a hazard class marked on each area of the sprinkler working plans, which then sets the design density and area, the hose allowance, the sprinkler spacing and the design basis shown on the hydraulic design information sign at the riser (NFPA 13 (2022) Section 29.4).
- Often confused with: commodity classification (Class I to IV and Group A plastics) for stored goods; the building code’s occupancy groups, some of which carry the word hazard in their names; and the low, ordinary and high hazard of contents in NFPA 101, the Life Safety Code.
What is an occupancy hazard classification?
An occupancy hazard classification is the label NFPA 13 gives a room or area to describe the fire its sprinklers must control. NFPA 13 (2022) Chapter 4 assigns one of the five classes from the quantity and combustibility of the contents, the rate at which a fire would release heat, how high combustibles are piled and whether flammable or combustible liquids are present. The standard states that these classes serve sprinkler design, installation and water supply only, and are not a general ranking of how hazardous an occupancy is.
Classification works area by area, not building by building. The NFPA 13 annex lists a restaurant’s seating area as light hazard and its service areas, including the kitchen, as Ordinary Hazard Group 1, so one restaurant carries two classes. Where a more demanding area adjoins a less demanding one with no draft curtain, barrier or partition between them, NFPA 13 (2022) Section 19.1.2 carries the higher design 15 ft into the neighboring area.
The classes are also separate from the building code’s occupancy groups. The 2021 International Building Code (IBC) calls Group S-1 moderate-hazard storage, Group S-2 low-hazard storage and Group H high-hazard (Sections 311 and 307), but those groups govern construction, egress and when sprinklers are required, not how a system is designed. A parking garage shows the gap: the IBC places parking garages in Group S-2 (Section 311.3), while the NFPA 13 (2022) annex lists parking garages under Ordinary Hazard Group 2 (Group 1 still lists automobile parking with showrooms). NFPA 101 (2024), the Life Safety Code that Maryland and Delaware apply alongside the building code, adds a third scale, the low, ordinary and high hazard of contents used for egress (Section 6.2.2).
What are the five hazard classes, and which spaces fall in each?
Each class is defined by its contents and the fire they would produce, and the annex to Chapter 4 lists typical uses for each. The ladder and the table below paraphrase the 2022 definitions and a selection of the annex examples.
Figure 1: The five occupancy hazard classes
- 5Extra Hazard Group 2Flammable liquid spraying, solvent cleaning, plastics manufacturing
- 4Extra Hazard Group 1Die casting, saw mills, combustible hydraulic fluid areas
- 3Ordinary Hazard Group 2Stores, machine shops, printing, repair garages, stages
- 2Ordinary Hazard Group 1Bakeries, laundries, restaurant kitchens
- 1Light HazardOffices, schools, churches, hospitals, residential
| Class | Contents and expected fire (paraphrased) | Typical spaces (annex examples, paraphrased) | Where the design numbers come from |
|---|---|---|---|
| Light hazard | Low quantity or low combustibility of contents, or both; fires with relatively low rates of heat release | Offices, churches, schools, hospitals and nursing homes, libraries other than large stack rooms, museums, residential occupancies, restaurant seating areas | Light hazard density and design area (Chapter 19); up to 225 sq ft per standard spray sprinkler (Chapter 10) |
| Ordinary Hazard Group 1 | Low combustibility and a moderate quantity of contents; stockpiles of combustibles no higher than 8 ft; fires with moderate rates of heat release | Bakeries, laundries, beverage and dairy plants, canneries, electronics plants, restaurant service areas; automobile parking and showrooms (showrooms only in the 2025 edition) | Ordinary Hazard Group 1 density and design area (Chapter 19); up to 130 sq ft per sprinkler (Chapter 10) |
| Ordinary Hazard Group 2 | Moderate to high quantity and combustibility of contents; stockpiles up to 12 ft of contents with moderate heat release or 8 ft with high heat release | Stores and other mercantile spaces, machine shops and metal working, printing and publishing, dry cleaners, repair garages, stages, large library stack rooms, post offices; automobile parking garages from the 2022 edition | Ordinary Hazard Group 2 density and design area (Chapter 19); up to 130 sq ft per sprinkler (Chapter 10) |
| Extra Hazard Group 1 | Very high quantity and combustibility of contents, with dust, lint or similar material that makes fires develop fast and release heat fast; little or no flammable or combustible liquid | Die casting, metal extruding, plywood and particleboard manufacturing, saw mills, rubber processing, upholstering with plastic foams, areas using combustible hydraulic fluid | Extra Hazard Group 1 density and design area (Chapter 19); up to 100 sq ft per sprinkler at 0.25 gallons per minute per sq ft or more, 130 sq ft below that (Chapter 10) |
| Extra Hazard Group 2 | Moderate to substantial amounts of flammable or combustible liquids, or extensive shielding of combustibles | Flammable liquid spraying, flow coating, open oil quenching, solvent cleaning, varnish and paint dipping, plastics manufacturing, asphalt saturating | Extra Hazard Group 2 density and design area (Chapter 19); up to 100 sq ft per sprinkler at 0.25 gallons per minute per sq ft or more, 130 sq ft below that (Chapter 10) |
Two cautions apply to the examples. They describe typical conditions, so a listed use with heavier contents than usual belongs in the class its contents justify, not the class on the list. They also change between editions: NFPA 13 listed automobile parking as Ordinary Hazard Group 1 for decades; the 2022 annex lists parking garages under Ordinary Hazard Group 2 (Group 1 still lists automobile parking with showrooms), and the 2025 annex lists them under Group 2 only.
NFPA 13 (2022) sets the density and design area for each class in Table 19.2.3.1.1, the values new systems use. The 2016 and 2019 editions used in New York City, Pennsylvania and Maryland county permits read both from density/area curves, which DGA’s guide to reading the NFPA 13 density/area curves walks through. The spacing figures in the table are the largest allowed for standard spray sprinklers, and the ceiling construction or the design method can lower them (Chapter 10).
Where does NFPA 13 define the hazard classes and give examples?
In NFPA 13 (2022) the five classes are defined in Section 4.3: light hazard in 4.3.2, Ordinary Hazard Groups 1 and 2 in 4.3.3.1 and 4.3.3.2, and Extra Hazard Groups 1 and 2 in 4.3.4 and 4.3.5. The same chapter holds the owner’s certificate (Section 4.2) and the low-piled storage limits (Section 4.3.1.5), and Section 4.3.3.2 includes the stockpile limits for Ordinary Hazard Group 2. The examples sit in Annex A under the matching Chapter 4 numbers. The annex explains the requirements but is not part of them, so the list guides the designer while the definitions and the actual contents decide the class.
The five classes appear in every NFPA 13 edition used in the region; the chapter, the section numbers and some annex examples differ. As of November 2026, New York State and New Jersey use NFPA 13 (2022), and the Delaware State Fire Marshal reviews to NFPA 13 (2025), both with the classes in Chapter 4, though the 2025 edition numbers the extra hazard groups 4.3.4.1 and 4.3.4.2. Pennsylvania uses NFPA 13 (2019), as do New Jersey applications filed under the prior 2021-based codes through February 17, 2027; it also defines the classes in Chapter 4, with the ordinary and extra hazard groups at 4.3.3 to 4.3.6.
In Maryland, the county building permit reviews sprinklers to NFPA 13 (2019) through the 2021 IBC, while the State Fire Prevention Code (NFPA 1, 2024) references NFPA 13 (2022). New York City uses NFPA 13 (2016) as modified by Appendix Q of the 2022 New York City Building Code; the 2016 edition defines the classes in Chapter 5, Classification of Occupancies and Commodities, and Appendix Q lists that chapter with no changes.
DGA classifies occupancy hazards and prepares NFPA 13 sprinkler designs, shop drawings and hydraulic calculations across New York, New Jersey, Pennsylvania, Maryland, Delaware, Washington, Oregon and Florida. Project briefs get confirmation and preliminary code feedback within one business day. See where DGA works →
How is occupancy hazard different from commodity classification?
Occupancy hazard classifies a space; commodity classification classifies the goods stored in it. NFPA 13 ranks a storage unit, meaning the product, its packaging and the pallet together, from Class I to Class IV and then into Group A plastics, cartoned or exposed and expanded or nonexpanded, in Chapter 20 of the 2019 and later editions. DGA’s guide to commodity classification under NFPA 13 explains the plastics thresholds and the pallet rules.
Storage height decides which system governs. Under NFPA 13 (2022), Class I to IV commodities stored up to 12 ft and Group A plastics stored up to 5 ft are low-piled storage, which stays in Chapter 4 with the occupancy classes (Section 4.3.1.5). Above those heights the storage is designed under Chapters 20 to 25 by commodity class, storage height, arrangement and sprinkler type, and fire code high-piled storage rules may also apply.
| Question | Occupancy hazard classification | Commodity classification |
|---|---|---|
| What it classifies | A room or area and everything in it | A storage unit: the product, its packaging and the pallet together |
| Scale | Light hazard; Ordinary Hazard Groups 1 and 2; Extra Hazard Groups 1 and 2 | Class I to IV, then Group A plastics, cartoned or exposed and expanded or nonexpanded |
| Where in NFPA 13 | Chapter 4 (2019, 2022 and 2025 editions); Chapter 5 (2016) | Chapter 20 (2019, 2022 and 2025 editions); Chapter 5 (2016) |
| Storage it covers | Low-piled storage: Class I to IV up to 12 ft, Group A plastics up to 5 ft (2022 Section 4.3.1.5) | Storage above the low-piled limits |
| Where the design comes from | Density, design area and hose allowance in Chapter 19 | The storage chapters, 20 to 25, by commodity, height, arrangement and sprinkler type |
| What the designer needs from the owner | The use of each area and what it contains | Products, packaging, pallet type, storage height and arrangement |
Figure 2: The room or the load: Two classifications in NFPA 13
- Classifies the room or area and everything in it
- Five classes, light hazard to Extra Hazard Group 2
- Keeps low-piled storage: Class I to IV up to 12 ft, Group A plastics up to 5 ft
- Design density and area set in Chapter 19
- Classifies a storage unit: product, packaging and pallet
- Class I to IV, then Group A plastics by packaging and form
- Governs storage above the low-piled limits
- Design read from the storage chapters, 20 to 25
When does a space need its hazard class checked again?
Every NFPA 13 system is designed to a classification, so a class is needed whenever the building code calls for an NFPA 13 system; DGA’s article on when a building needs fire sprinklers covers those triggers. Once the system is built, its class stays fixed while the building around it changes. A new tenant, a change of use, a process that brings in flammable liquids, taller stockpiles or a shift to plastic goods can each put a space in a higher class than the pipe was sized for.
NFPA 25 (2023), the inspection, testing and maintenance standard Maryland and Delaware enforce, puts that check on the owner: occupancy, use, process or materials are not changed until the sprinkler system has been evaluated for the change, and a change found later is evaluated promptly (Sections 4.1.6 and 4.1.7). Any work on the system that follows is an existing system modification under NFPA 13 (2022) Chapter 30.
Local rules lean on the class too. Several jurisdictions in the region tie permit routes or design rules to it:
- Delaware: the State Fire Marshal’s guidance for existing fire sprinkler systems (Doc. 75-01-24-04-06) lets up to 10 sprinklers outside the hydraulically most demanding area be relocated by letter instead of a plan submission, provided the hazard classification of the work area does not change.
- New Jersey: in reconstruction, the Rehabilitation Subcode accepts an existing sprinkler system built to the standards in force when it was installed only if neither the hazard of the use nor the load increases (New Jersey Administrative Code (N.J.A.C.) 5:23-6.30(f)).
- New York City: a licensed master fire suppression piping contractor may rearrange up to 30 sprinklers on a Limited Alteration Application, without plans, only in light hazard, Ordinary Hazard Group 1 restaurant service and Ordinary Hazard Group 2 mercantile areas (Administrative Code Section 28-101.5).
- Montgomery County, Maryland: the Department of Permitting Services (DPS) asks designers to use the highest hazard and most demanding use the building permit or zoning allows (DPS NFPA 13 submittal requirements).
What does the hazard class change in the sprinkler design?
The hazard class is the first input to most of the design numbers. Moving an area up one class raises the water it needs and can tighten the sprinkler layout, which is why reviewers expect the class to be marked on every area of the working plans.
| Design element | How it changes as the class rises | NFPA 13 (2022) |
|---|---|---|
| Design density and design area | Both rise from light hazard to Extra Hazard Group 2 | Table 19.2.3.1.1 |
| Hose stream allowance and water supply duration | Both rise with the class; Appendix Q removes the hose allowance in New York City but keeps the duration | Table 19.2.3.1.2 |
| Floor area per standard spray sprinkler | Up to 225 sq ft in light hazard, 130 sq ft in ordinary hazard and 100 sq ft in extra hazard | Tables 10.2.4.2.1(a) to (c) |
| Sprinkler response | Light hazard areas use quick-response, residential, quick-response control mode specific application or early suppression fast response sprinklers, with exceptions for some work on existing standard-response systems | Section 9.4.3.1 |
| Floor area per system riser | 52,000 sq ft per floor for light and ordinary hazard and 40,000 sq ft for hydraulically calculated extra hazard; the 2025 edition allows 78,000 sq ft for light hazard wet pipe systems whose alarms go to a supervising station | Section 4.4.1 |
Because the class sets the flow, it often decides whether the existing water service is enough or a fire pump is needed. DGA’s Sprinkler Design Area and Demand Calculator turns the density and design area for a class into the number of flowing sprinklers, the flow and pressure at the most remote sprinkler and an estimate of the total demand with the hose allowance.
The building codes use the classes as well. Under the 2021 IBC and the New York City Building Code, a limited area sprinkler system, capped at six sprinklers in a fire area (Section 903.3.8.1), may protect only light hazard and Ordinary Hazard Group 1 areas (Section 903.3.8.2), and New Jersey replaces those sections with its own limited area rule (N.J.A.C. 5:23-3.14(b)8). Delaware’s Regulation 702 requires sprinklers in NFPA 13 extra hazard and NFPA 101 high hazard uses on top of the county building code (Chapter 4, Section 1.2), and the State Fire Marshal’s Preliminary Sprinkler Form asks for each hazard classification to be marked on a floor plan, with the minimum design area assumed for each class where the form carries no note.
Key Takeaway: Light, ordinary and extra hazard are NFPA 13’s measure of the fire a space’s contents could produce, not the building code’s occupancy groups. The designer classifies every area from the owner’s statement of use and contents, the AHJ accepts it at plan review, and the class then fixes the density, design area, hose allowance and sprinkler spacing. The class can differ by NFPA 13 edition, as parking garages show, and it needs a fresh look whenever the use, contents or storage height of a space changes.
Frequently asked questions
Is an office a light hazard occupancy?
Yes. NFPA 13 lists offices, including data processing areas, among its light hazard examples in the annex to Chapter 4 of the 2022 edition. Rooms inside an office are classified on their own contents, so a storage room holding stockpiled supplies can be ordinary hazard and is designed for that class.
Is a parking garage Ordinary Hazard Group 1?
Conditional: it depends on the NFPA 13 edition. The 2016 and 2019 editions list automobile parking as Ordinary Hazard Group 1, which applies in New York City and Pennsylvania and to New Jersey applications still under the prior codes. The 2022 annex lists parking garages under Ordinary Hazard Group 2 (Group 1 still lists automobile parking with showrooms) and the 2025 annex lists them under Group 2 only, the class for New York State, New Jersey and Delaware. In Maryland, the county permit reviews to the 2019 edition while the State Fire Prevention Code references the 2022 edition, so the two reviews can point to different classes.
Does storage under 12 ft change the hazard class?
Conditional: it can raise the class, and plastics can take the space out of the occupancy classes altogether. NFPA 13 (2022) keeps Class I to IV commodities up to 12 ft and Group A plastics up to 5 ft in Chapter 4 as low-piled storage (Section 4.3.1.5), and Ordinary Hazard Group 2 covers stockpiles up to 12 ft of contents with moderate heat release or 8 ft with high heat release (Section 4.3.3.2). Group A plastics above 5 ft, and other storage above 12 ft, are designed under the storage chapters by commodity class.
Who decides the hazard classification for a sprinkler design?
The sprinkler designer proposes it and the authority having jurisdiction accepts it at plan review. The designer classifies each area from the owner’s certificate, the owner’s written statement of the building’s intended use and contents (NFPA 13 (2022) Section 4.2), and marks the class on the working plans. An insurer may apply its own classification on top of the code-approved design.
More in Sprinkler Systems
- What Is NFPA 13? A Plain-English Guide for Owners
- When Does a Sprinkler System Need Seismic Bracing?
- How Do You Size a Water Supply for a 13R or 13D System?
- Do Balconies and Decks Need Sprinklers Under NFPA 13R?
- When Does a Stage or Exhibit Hall Need Special Sprinklers?
- Do Closets, Bathrooms and Small Rooms Need Sprinklers?
This article is general information, not a substitute for a project-specific hazard classification. Code editions, local amendments and reviewer practice change; confirm the adopted code and the authority having jurisdiction for the project.
Not Sure Which Hazard Class Fits a Space?
Send the floor plans, the intended use of each area, what will be stored and how high, and the jurisdiction. DGA classifies each area, sets the NFPA 13 design basis and prepares the sprinkler drawings and calculations, or checks a classification before it goes to the reviewer. Project briefs get confirmation and preliminary code feedback within one business day.