When does a parking garage need sprinklers?

General guidance, not a code determination for any project. Confirm the adopted code and local amendments with the authority having jurisdiction.

A new parking garage needs sprinklers under Section 903.2.10 of the International Building Code (IBC) when it is an enclosed garage with a fire area over 12,000 sq ft, an enclosed garage beneath another occupancy, an open garage with a fire area over 48,000 sq ft, or a building that stores commercial motor vehicles in a fire area over 5,000 sq ft. The open garage threshold arrived with the 2021 edition, so jurisdictions still on the 2018 IBC have none, and a garage in the same building as apartments is sprinklered with the rest of the building under Section 903.2.8.

Three jurisdictions in the region go further. New York City (NYC) sprinklers any building over 5,000 sq ft whose main use is parking, and in Maryland and Delaware the fire codes add the Life Safety Code of the National Fire Protection Association (NFPA), NFPA 101 (2024), with NFPA 88A (2023) in Delaware; both call for sprinklers in new parking structures of any size. The sections below cover the thresholds by edition, the open and enclosed test, the 2024 changes, garages under other uses, the exceptions, the system type and each jurisdiction’s rules.

At a Glance: When a Parking Garage Needs Sprinklers

  • Threshold(s) with units: enclosed garage fire area over 12,000 sq ft; enclosed garage beneath another occupancy at any size (not beneath Group R-3); open garage fire area over 48,000 sq ft (2021 and 2024 IBC); commercial motor vehicle storage over 5,000 sq ft; mechanical-access enclosed garages at any size; a story with 30 or more occupants 55 ft or more above fire department vehicle access (2021 and 2024 IBC); in NYC, any Group S-2 building or fire area over 5,000 sq ft.
  • Code, edition, section: IBC Section 903.2.10 with Sections 406.5 and 406.6, in the 2024 edition (New Jersey, New York State, the City of New Castle in Delaware), the 2021 edition (Pennsylvania, Maryland county permits, New Castle and Sussex counties) and the 2018 edition (Kent County and Wilmington); 2022 NYC Building Code Section 903.2.10; NFPA 101 (2024) Chapter 42 in Maryland and Delaware; NFPA 88A (2023) and Regulation 702, Chapter 4, in Delaware.
  • Main exceptions: enclosed garages beneath Group R-3; open garages that pass the openings test in IBC Section 406.5.2 and stay at or under 48,000 sq ft (no area limit at all in the 2018 IBC); separations that keep each fire area under the limit; occupied roofs over Type I or II open garages (Section 903.2.1.6); in Delaware, open noncombustible structures built to NFPA 88A, from the 10,000 sq ft item only.
  • What applies once triggered: an NFPA 13 system throughout, designed as Ordinary Hazard Group 2 under the 2022 and 2025 editions (Group 1 under 2016 and 2019); a dry pipe system with a 30 percent larger design area where the piping can freeze; a standpipe where IBC Section 905.3 requires one.
  • Permit or filing: sprinkler drawings and hydraulic calculations, filed as a sprinkler (SP) filing with the Department of Buildings (DOB) in DOB NOW: Build in NYC, with the building permit in New York State and Pennsylvania (a separate suppression permit in Philadelphia and Pittsburgh), under the fire protection subcode of the construction permit in New Jersey, as a county fire protection permit in Maryland and for State Fire Marshal plan review in Delaware.
  • Who decides: the building code official applies Section 903.2.10; the fire marshal applies NFPA 101 in Maryland and Delaware and NFPA 88A in Delaware; the registered design professional classifies the garage as open or enclosed, and the authority having jurisdiction (AHJ) accepts that classification.

When does the building code require sprinklers in a parking garage?

IBC Section 903.2.10 holds the garage triggers, and the 2021 edition rewrote it. The 2018 section covered enclosed parking garages only, requiring sprinklers throughout when the enclosed garage’s fire area exceeds 12,000 sq ft or when it sits beneath other occupancy groups, except beneath Group R-3. The 2021 edition keeps both items, ties them to the enclosed garage rules in Section 406.6 and adds a third: an open parking garage under Section 406.5 whose fire area exceeds 48,000 sq ft.

Three other items reach garages. Section 903.2.10.1 sprinklers buildings that store commercial motor vehicles, such as trucks and buses, once the fire area exceeds 5,000 sq ft, and Section 903.2.10.2, new in 2021, sprinklers mechanical-access enclosed garages, where lifts or automated equipment move the vehicles. Section 903.2.11.3 sprinklers any building with a story holding 30 or more occupants 55 ft or more above the lowest level of fire department vehicle access; the 2018 edition exempted open parking structures from that rule, but the 2021 edition keeps only an exception for Group F-2.

The table sets each trigger against the IBC editions in force in the region and the NYC rule, which differs most. Any one row is enough to require sprinklers.

Garage conditionSprinklers required whenIBC section and editions2022 NYC Building Code
Enclosed parking garageFire area over 12,000 sq ft903.2.10 item 1: 2018, 2021 and 2024Every enclosed garage, any size (903.2.10.3)
Enclosed garage beneath another occupancyAny size, except beneath Group R-3903.2.10 item 2: 2018, 2021 and 2024Open or enclosed garage beneath another occupancy, except beneath R-3 (903.2.10.3)
Open parking garage that passes Section 406.5.2Fire area over 48,000 sq ft903.2.10 item 3: 2021 and 2024; no such item in 2018Any building over 5,000 sq ft whose main use is Group S-2, and any S-2 fire area over 5,000 sq ft (903.2.10, 903.2.10.2)
Commercial motor vehicle storageFire area over 5,000 sq ft903.2.10.1: 2018, 2021 and 2024Fire area over 5,000 sq ft (903.2.10.1)
Mechanical-access enclosed garageAny size; the 2024 text calls for a specially engineered system in the mechanical-access portion903.2.10.2: new in 2021, kept in 2024No separate item; covered as an enclosed garage (903.2.10.3)
Tall garageA story with 30 or more occupants 55 ft or more above fire department vehicle access903.2.11.3: 2021 and 2024; the 2018 edition exempted open parking structures903.2.11.7 exempts open parking structures with no other occupancy

IBC editions as of November 2026: 2024 in New Jersey, New York State and the City of New Castle, Delaware; 2021 in Pennsylvania, the Maryland county permits and New Castle and Sussex counties, Delaware; 2018 in Kent County and Wilmington, Delaware.

Figure 1: Garage sprinkler triggers by fire area

  1. 448,000 sq ft: open parking garage fire area903.2.10, 2021 and 2024 IBC; no open garage item in the 2018 edition
  2. 312,000 sq ft: enclosed parking garage fire area903.2.10, 2018 to 2024 IBC
  3. 25,000 sq ft: commercial motor vehicle storage903.2.10.1; NYC applies 5,000 sq ft to any parking building or S-2 fire area
  4. 1Any size: enclosed garage beneath another occupancy other than Group R-3, or a mechanical-access enclosed garage903.2.10 and 903.2.10.2; NYC also sprinklers open garages beneath other uses
Under IBC Section 903.2.10 (2021 and 2024), an open garage needs sprinklers above 48,000 sq ft of fire area, an enclosed garage above 12,000 sq ft and commercial vehicle storage above 5,000 sq ft, while an enclosed garage beneath another occupancy other than Group R-3, or a mechanical-access enclosed garage, needs them at any size. New York City draws its line at 5,000 sq ft for any parking building, and the 2018 IBC used in Kent County and Wilmington, Delaware, has no open garage item.

What makes a garage open or enclosed, and how is the fire area measured?

A garage counts as open only when its tiers pass the openings test in IBC Section 406.5.2 (2021). The exterior walls of each tier need uniformly distributed openings on two or more sides, totaling at least 20 percent of the tier’s perimeter wall area and spread along at least 40 percent of its perimeter, and interior walls must be at least 20 percent open. The 40 percent spread does not apply when the openings are uniformly distributed over two opposing sides, and a garage that fails the test is designed as an enclosed garage under Section 406.6.

The area tests in Section 903.2.10 measure the fire area, not the footprint. The IBC defines a fire area as the floor area bounded by fire walls, fire barriers, exterior walls or horizontal assemblies, including open-sided areas under the roof or floor above (Section 202), and DGA’s guide to when a building needs fire sprinklers explains how separations change it. Ramps open each garage tier to the next, so the tiers normally form one fire area and the 48,000 sq ft test reads against their combined floor area.

A five-tier open garage with 11,000 sq ft per tier therefore has a 55,000 sq ft fire area and needs sprinklers under the 2021 and 2024 IBC. Built in Kent County or Wilmington, Delaware, under the 2018 IBC, the same garage meets no Section 903.2.10 item, though Delaware’s State Fire Marshal rules, described below, still reach it. For the 55 ft rule, IBC Table 1004.5 (2021) counts one occupant per 200 sq ft gross in a parking garage, so a tier of 6,000 sq ft or more holds at least 30 occupants.

What changed in the 2024 IBC for garages and electric vehicle charging?

The 2024 IBC left the garage thresholds alone: the International Code Council (ICC) lists no change to Section 903.2.10 in its summaries of the 2024 edition. New Jersey and New York State therefore apply the same tests as the 2021 states, and the edition break that matters for garages is 2018 against 2021 and later.

Electric vehicle (EV) charging does not change those thresholds under the model code. The 2021 IBC sends charging equipment, where provided, to NFPA 70, the National Electrical Code (Section 406.2.7), and Section 903.2.10 has no EV item in either edition. New York State’s 2025 fire code includes emergency disconnect rules for EV chargers (Fire Code of New York State Section 611), which are an electrical safety measure, not a sprinkler trigger.

The 2024 IBC did add sprinkler triggers for buildings that store or repair vehicles powered by lithium-ion or lithium metal batteries, once a Group S-1 fire area exceeds 500 sq ft (Section 903.2). A public parking garage stays in Group S-2, so that trigger turns on how the space is classified under IBC Chapter 3. Responding to a comment on the commercial vehicle items, New York’s Department of State said the registered design professional makes that call from the fleet makeup, vehicle density and cargo.

Local amendments can go further than the model code. Montgomery County, Maryland, requires enclosed parking garages with EV charging stations to be sprinklered to NFPA 13 at a minimum density of 0.3 gallons per minute (gpm) per sq ft over the fire area or 2,500 sq ft, whichever is smaller (Executive Regulation 14-24, which amends the county’s fire code). The county’s Department of Permitting Services reviews the design under its Fire Protection System permit.

How do garages under other occupancies change the answer?

Other uses above a garage usually settle the question. Under IBC Section 903.2.10, an enclosed garage beneath any other occupancy group needs sprinklers at any size unless the group above is R-3, such as a one- or two-family dwelling. An open garage beneath other uses is not caught by that item, but the use above often brings sprinklers with it.

Apartments are the common case. IBC Section 903.2.8 (2021) requires sprinklers throughout every building with a Group R fire area, so a garage in the same building as the apartments is sprinklered with the rest of it. A podium built under Section 510.2 makes the garage a separate building below a 3-hour horizontal assembly, and the 2021 edition requires that lower building to be sprinklered throughout to NFPA 13 (Section 903.3.1.1).

New York City and Delaware close the open-garage gap in their own texts. NYC Building Code Section 903.2.10.3 sprinklers every open or enclosed garage beneath another occupancy group, except beneath Group R-3. Delaware’s Regulation 702 bars an unsprinklered open parking structure from sitting beneath any other occupancy and calls for a 2-hour fire wall where one adjoins another use.

Figure 2: Does this garage need sprinklers?

A new parking garage, standing alone or as part of a larger building
Does the building also hold a Group R fire area, or is the garage the lower building of a Section 510.2 podium?
YesSprinklers requiredSection 903.2.8 sprinklers a building with a Group R fire area throughout; a 510.2 podium is sprinklered throughout to NFPA 13 (2021 IBC)
NoCheck the garage on its ownGo to the openings test
Do the tiers pass the openings test for an open parking garage in Section 406.5.2?
YesOpen garageSprinklers when the fire area exceeds 48,000 sq ft under the 2021 and 2024 IBC; no area trigger in the 2018 IBC
NoEnclosed garageSprinklers when the fire area exceeds 12,000 sq ft, or at any size beneath another occupancy other than Group R-3 (903.2.10)
Does the garage store commercial motor vehicles in a fire area over 5,000 sq ft, use mechanical access, or have a story of 30 or more occupants 55 ft or more above fire department vehicle access?
YesSprinklers requiredSections 903.2.10.1 and 903.2.10.2, and 903.2.11.3 in the 2021 and 2024 IBC (the 2018 edition exempted open parking structures from the 55 ft rule)
NoNo IBC garage triggerThen check the local layer: 5,000 sq ft in NYC, NFPA 101 (2024) in Maryland and Delaware, NFPA 88A (2023) and Regulation 702 in Delaware
A garage in a building with a Group R fire area, or the lower building of a Section 510.2 podium, is sprinklered at any size; otherwise the IBC sorts the garage as open or enclosed, applies the 48,000 sq ft or 12,000 sq ft fire area test, and then checks commercial vehicles, mechanical access and the 55 ft rule. New York City, Maryland and Delaware add rules that reach smaller and open garages.

Opens the Project Desk with your sentence. Our licensed PEs review every brief and reply within one business day.

Which exceptions and alternatives apply to garage sprinklers?

The model code’s main exception is the Group R-3 carve-out: an enclosed garage beneath a one- or two-family dwelling or another Group R-3 use does not trigger the beneath-other-groups item, and NYC keeps the same exception. Size is the second route, since fire walls, fire barriers or horizontal assemblies with the ratings the IBC sets for fire area separations can split a garage into fire areas under 12,000 sq ft (enclosed) or 48,000 sq ft (open). Every opening through those separations, drive aisles and ramps included, needs rated protection.

An occupied roof brings a garage-specific exception: where an assembly use on a roof would otherwise pull sprinklers into the floors below it, IBC Section 903.2.1.6 (2021) exempts open parking garages of Type I or Type II construction. Designing a garage as open is the broadest alternative under the IBC, because an open garage escapes the 12,000 sq ft and beneath-other-groups items. That route does not help in NYC for a parking building over 5,000 sq ft, or in Maryland and Delaware, where NFPA 101 (2024) applies.

These triggers apply to new garages. An existing garage answers to the existing building code and retrofit rules instead, and the NFPA 88A (2023) and NFPA 101 (2024) rules for new parking structures do not reach existing ones.

Which sprinkler system does a garage use: Wet, dry or antifreeze?

Once a trigger applies, the garage gets an NFPA 13 system designed to its occupancy hazard class. The 2022 annex of NFPA 13 lists parking garages under Ordinary Hazard Group 2 (Group 1 still lists automobile parking with showrooms), while the 2016 and 2019 editions list automobile parking as Group 1, the class still used in NYC, Pennsylvania and the Maryland county permits; DGA’s guide to light, ordinary and extra hazard occupancies explains the classes. In Maryland, the county building permit reviews sprinklers to NFPA 13 (2019) through the 2021 IBC, while the State Fire Prevention Code (NFPA 1, 2024) references NFPA 13 (2022).

For new systems, NFPA 13 (2022) sets the density and design area for each hazard class (Table 19.2.3.1.1), and for Ordinary Hazard Group 2 that is 0.20 gpm per sq ft over 1,500 sq ft; the 2016 and 2019 editions read the design from the density/area curves. A dry pipe system enlarges the design area by 30 percent at the same density (Section 19.2.3.2.5), to 1,950 sq ft in that case.

Temperature decides the system type. A garage whose piping stays at 40 F or above can use a wet pipe system (NFPA 13 (2022) Section 16.4.1.1), while an unheated or open garage usually gets a dry pipe system, which holds air or nitrogen until a sprinkler opens and, above 500 gal of system capacity, or 750 gal with a quick-opening device, must meet a water delivery time limit (Section 8.2.3). An antifreeze system is the other option and must use a listed antifreeze solution (NFPA 25 (2023) Section 5.3.4.4), and DGA’s comparison of wet, dry, preaction and deluge systems covers the choice.

Standpipes follow their own trigger. IBC Section 406.5.8 (2021) gives an open parking garage a standpipe system where Section 905.3 requires one, and DGA’s overview of what fire protection a parking garage needs covers those thresholds alongside ventilation and freeze protection.

How does each jurisdiction apply the garage rules?

Section 903.2.10 is the starting point across the region, but NYC writes its own section, New Jersey and New York State are on the 2024 edition, and Maryland and Delaware layer NFPA fire codes over the county building permit. The table gives each jurisdiction’s codes, its garage rules beyond Section 903.2.10 and the reviewing office, as of November 2026.

JurisdictionCodes in force (as of November 2026)Garage rules beyond IBC 903.2.10 (NFPA 88A or local rule)Who reviews the sprinkler filing
New York City2022 NYC Building Code and Fire Code; NFPA 13 (2016) as modified by Appendix QIts own Section 903.2.10: Group S-2 buildings or fire areas over 5,000 sq ft, every enclosed garage, and open or enclosed garages beneath other uses (not R-3); Fire Code Chapter 80 lists NFPA 88A (2019)DOB, SP filing in DOB NOW: Build
New York State (outside NYC)2025 Building Code of New York State on the 2024 IBC, in effect since December 31, 2025; NFPA 13 (2022)2024 IBC Section 903.2.10 as published in the state code; EV charger disconnects in Fire Code of New York State Section 611Local code enforcement official under 19 NYCRR (New York Codes, Rules and Regulations) Part 1203, with the building permit
New JerseyUniform Construction Code (UCC) on the 2024 IBC, effective August 17, 2026; NFPA 13 (2022)New Jersey’s Section 903 amendments leave 903.2.10 unchanged; complete applications under the prior codes through February 17, 2027 stay under the 2021 IBC and Table 903.2.13, which sprinklered Group S-2 buildings of Types IIB, IIIB and VB past set areas (open parking structures excepted)Fire protection subcode official in the municipal construction office
PennsylvaniaUCC on the 2021 IBC since January 1, 2026; NFPA 13 (2019); no statewide fire code2021 IBC Section 903.2.10 adopted without changeMunicipal code official or third-party agency; Department of Labor and Industry (L&I) where the municipality does not enforce; Philadelphia’s Department of Licenses and Inspections (Fire Suppression Systems Permit); Pittsburgh’s Department of Permits, Licenses, and Inspections (Suppression Systems Permit)
MarylandMaryland Building Performance Standards (2021 IBC) through the county permit; State Fire Prevention Code with NFPA 1 and 101 (2024) under COMAR (Code of Maryland Regulations) 29.06.01NFPA 101 (2024) Chapter 42: sprinklers in new parking structures; Montgomery County: enclosed garages with EV charging stations at 0.3 gpm per sq ft (Executive Regulation 14-24)County permit office (Montgomery, Prince George’s, Baltimore City, Baltimore County and others); Office of the State Fire Marshal (OSFM) where no local official reviews
DelawareIBC by jurisdiction: 2021 in New Castle and Sussex counties, 2018 in Kent County and Wilmington, 2024 in the City of New Castle; Regulation 701 (2026) with NFPA 1 and 101 (2024), NFPA 88A (2023) and NFPA 13 (2025)NFPA 88A (2023) and NFPA 101 (2024): sprinklers in new parking structures; Regulation 702, Chapter 4, section 1.2: buildings over 10,000 sq ft (open noncombustible structures not beneath another use exempt from that item only), over 40 ft or more than 4 stories, and basements over 2,500 sq ftOffice of the State Fire Marshal; city fire marshals in Wilmington, Dover, Newark and the City of New Castle

Editions and offices as of November 2026. A complete New Jersey application filed under the prior, 2021-based codes through February 17, 2027 stays subject to Table 903.2.13.

Maryland and Delaware make the largest change. NFPA 101 (2024), which both states apply to new buildings through their fire codes, and NFPA 88A (2023), which Delaware adopts in Regulation 701, call for sprinklers in new parking structures of any size, open or enclosed, so the 48,000 sq ft open garage threshold does not settle a new garage in either state.

Delaware’s Regulation 702, Chapter 4, section 1.2 shows how the layers meet. It sprinklers buildings over 10,000 sq ft of aggregate floor area and exempts open noncombustible parking structures built to NFPA 88A that sit beneath no other occupancy, but the NFPA 88A edition it now points to calls for sprinklers in new structures. Its separate items for buildings over 40 ft or more than 4 stories and for basements over 2,500 sq ft carry no parking exemption.

Key Takeaway: A new parking garage needs sprinklers under IBC Section 903.2.10 when an enclosed garage’s fire area exceeds 12,000 sq ft or it sits beneath another occupancy other than Group R-3, when an open garage’s fire area exceeds 48,000 sq ft (2021 and 2024 editions), when commercial vehicles are stored in a fire area over 5,000 sq ft, or when an enclosed garage parks vehicles mechanically. Apartments in the same building, a Section 510.2 podium or a story of 30 or more occupants 55 ft or more above fire department vehicle access brings sprinklers too. New York City sprinklers any parking building over 5,000 sq ft, and in Maryland and Delaware NFPA 101 (2024), joined by NFPA 88A (2023) in Delaware, calls for sprinklers in every new parking structure.

Frequently asked questions

Do open parking garages need sprinklers?

Conditional: under the 2021 and 2024 IBC, an open parking garage needs sprinklers when its fire area exceeds 48,000 sq ft, when a story with 30 or more occupants sits 55 ft or more above fire department vehicle access, or when it shares a building with a Group R fire area. The 2018 IBC, still used in Kent County and Wilmington, Delaware, has no area or height trigger for open garages. New York City sprinklers any parking building over 5,000 sq ft, and NFPA 101 (2024) in Maryland and Delaware, with NFPA 88A (2023) in Delaware, calls for sprinklers in new parking structures of any size.

Does electric vehicle charging change garage sprinkler requirements?

No, not under the model IBC: the Section 903.2.10 thresholds are the same with or without chargers, and the 2021 IBC sends charging equipment to NFPA 70 (Section 406.2.7). The 2024 IBC adds a 500 sq ft trigger for Group S-1 buildings that store or repair lithium-ion or lithium metal powered vehicles, which applies only where the space is classified S-1 rather than as an S-2 parking garage. Local rules can add more: Montgomery County, Maryland, requires enclosed garages with EV charging stations to be sprinklered at 0.3 gpm per sq ft over the fire area or 2,500 sq ft, whichever is smaller.

Which sprinkler system is used in an unheated garage?

A dry pipe system is the usual choice, because NFPA 13 (2022) requires wet pipe piping to be kept at 40 F or above (Section 16.4.1.1). A dry pipe design takes a 30 percent larger design area (Section 19.2.3.2.5) and, above 500 gal of system capacity, or 750 gal with a quick-opening device, must meet a water delivery time limit (Section 8.2.3). An antifreeze system is the other option and must use a listed antifreeze solution (NFPA 25 (2023) Section 5.3.4.4).

Does a garage under an apartment building need sprinklers?

Yes. An enclosed garage beneath another occupancy needs sprinklers at any size under IBC Section 903.2.10, a garage in the same building as a Group R fire area is sprinklered with the whole building under Section 903.2.8, and the building below a Section 510.2 podium must be sprinklered throughout to NFPA 13 (2021 IBC). New York City requires sprinklers in any open or enclosed garage beneath another occupancy, except beneath Group R-3.

This article is general information, not a substitute for a project-specific code analysis. Code editions, local amendments and reviewer practice change; confirm the adopted code and the authority having jurisdiction for each project.

Planning a Garage or a Building Over Parking?

Send the garage plans, the openings on each tier, the uses above and the jurisdiction. DGA confirms which sprinkler triggers apply, whether the garage qualifies as open and which system the design needs. Project briefs get confirmation and preliminary code feedback within one business day.

Send a project brief → View related services

Leave a reply

Your email address will not be published. Required fields are marked *

Quick inquiry

Ready when you are.

Your name, a way to reach you, and where the project is. A licensed PE replies within one business day. Every inquiry is confidential.

Prefer to describe it first? Open the Project Desk

FirmDGA Fire Protection Engineering
SheetFP-5208
OfficesNew York · Harrisburg · Seattle
LicensedNY NJ PA MD DE WA OR FL
Rev11.2026
Sheet index